background image

LOCATION

  

The heater must be installed at least 2.0m above floor 

level. All round minimum clearance dimensions must be 

observed.

For optimum effect the heater should be mounted as close 

as possible to the top of the doorway. The maximum 

recommended mounting height is 2.3m for 3kW and 2.8m 

for 4.5, 6.0 and 9.0kW units.

The heater is designed to take input air from the 

ceiling void it is therefore imperative that a suitably 

sized inlet grille is provided within the ceiling or 

enclosure.

The heater must not be covered or the airflow impeded 

in any way. 

If one inlet grille is at its minimum dimension the other 

must have an unrestricted airflow

CONTROL

Remote Switch
Thermostat (CRST16 )

 

The Remote Switch Unit allows ON/OFF, Fan only with 1,2 or 3 kW.

 

 

If a thermostat is required a unit of sufficient current carrying capacity (16A) can be connected in the power 

supply to the Remote switch thus switching the heater off when set temperature is reached.

Alternatively it can be connected to 

Remove the ìfan switchî to ìheat switchî links and link the supply side of the heat 

switches together then connect the thermostat between the fan switch and the heat switches.

control the heating elements only, the fan will run continuously 

maintaining air circulation. 

CONTENTS

- grille frame and 2 no roundhead woodscrews

Remove from carton and check contents ;

- heater unit

- 2 no support brackets,  4 no. machine screws and 4 no woodscrews

- ODH-RSW three switch control unit

- 25mm cord grip bush and locknut

ELECTRICAL CONNECTION

 

 

The heater should be installed in accordance with the latest edition of the IEE Requirements for Electrical 

Installation (BS 7671:2001)

The unit should be permanently connected to a suitable 230Vac power supply incorporating a means of 

isolation having a contact separation of at least 3mm in all poles.

 remote switch unit in suitable location. 

Select cabling with 4 cores and earth and of appropriate size for current and volt drop. 

Pass cable/s through cord grip in back of unit. Leave sufficient length for connection but ensuring cables do 

not foul blower unit. Make off connections to connector block and earth stud in accordance with circuit 

diagram RDH-W-001 (copy on back page )

If remote  switching is not required connect power supply to L and N and link L,LI and LII with  2.5sqmm 

cable.

Tighten up cord grip. Replace cover.

   

 

   

 

 

 

 

   

 

 

 

 

Remove heater cover, position heater in ceiling (See Fixing). Fix

A means of disconnection having a contact separation of 3mm in all poles should be incorporated.

IMPORTANT : always check to ensure the heating elements cannot be energised without the fan

running.
WARNING THE HEATER MUST BE EARTHED 
OVER TEMPERATURE CUT OUT

To RESET -

 

 

 

Should the heater exceed normal operating temperature the over temperature cut out on the heating 

elements will operate.

 

   switch off power to the unit and allow to cool before switching on again. If the problem persists 

consult a suitably qualified person.  

min

 20

min

100

min

 30

SAFETY

The correct procedures for working at height must be adopted when installing this heater.

The heater must be installed by a suitably qualified person in accordance with current regulations.

Summary of Contents for RDH 3000

Page 1: ...H UNIT for Fan only 3 2 and 1kW RDH 3000 Recessed Over Door Heater Please retain for future reference Commercial Electric Heat Limited Burnfoot Industrial Estate HAWICK Roxburghshire TD9 8SL Tel 01450 372103 Fax 01450 377800 Email sales cehltd co uk Web www cehltd co uk ...

Page 2: ...ip bush and locknut ELECTRICAL CONNECTION The heater should be installed in accordance with the latest edition of the IEE Requirements for Electrical Installation BS 7671 2001 The unit should be permanently connected to a suitable 230Vac power supply incorporating a means of isolation having a contact separation of at least 3mm in all poles remote switch unit in suitable location Select cabling wi...

Page 3: ...ter weight Two 8mm holes are provided in the top of the heater to allow the fixing of drop rods by others Fitting in modular ceiling Drop rod fixing This unit is designed for installation in a plasterboard or similar ceiling where a free height above the surface of the ceiling is at least 230mm It is also sized to fit within A 580mm x 130mm hole should be made in the ceiling and suitably framed Fi...

Page 4: ...ement Fan motor Connector block 4 C002 Blower unit 2kW 1kW L LI L LII 2kW 1kW N N 5 ODH RSW Remote Switch Unit Add external cut outs 11 04 6 O T cut out IMPORTANT Any modification to the switching in this circuit must ensure that the heating elements cannot be energised without the fan running Remote Switch ODH RSW 1 Heating element incorporates over temperature cut out To reset Switch off and all...

Reviews: