8-pin terminal of the control plug-in unit:

Label

Description

GND

Negative power supply connection

(0 V = direct current, DC)

+24 V

Positive power supply connection

(24 V = direct current, DC)

WK

Common contact

RK

NC output. Status is in idle, respectively 

monitored area interrupted or "SigIn" = 0 V 

connected with the WK connection

AK

NO output. In operation and monitored area 

free/uninterrupted, connected with the WK 

connection

SigIn

Test input for the testing of the system

Status

Status of surveillance area, independent of 

signal "SigIn", semiconductor output

SigOut

Status of surveillance area, dependent of 

signal "SigIn", (analogue relay output)
Electrical data of the interfaces (Chapter 14)

10.4  Display elements

The display elements are illuminated if the following 

conditions are fulfilled:

Control unit plug-in

Power

Control unit plug-in is receiving power

Sig_Out

Light curtain is enabled and the relay in the 

control plug-in module is actuated

Sig_In

Sig_In

 connection is HIGH

Alarm R

Calibration, self-test or error in the receiver 

edge

Alarm T

Calibration, self-test or error in the emitter 

edge

Plug-in system controller

Flush 

position

Input for the Flush position 

(Bündigstellung)

Override 

delay

Input for the Override Delay 

(Überbrückungsverzögerung)

Latch_In

Input for the Latch_In 

(Riegel_In)

Safety 

circuit

Safety circuit closed

Power

Plug-in system controller receiving power

The display on the plug-in system controller is used for 

various 

status

 displays during normal operating mode. 

These help the elevator technician to check the system 

for correct function. This can be particularly helpful when 

checking whether the wiring to the elevator control system 

is correct.

 

The small area in the lower right-hand 

corner of the displays flashes with approx. 

3 Hz. The system is in normal state if this 

area is flashing.

 

The small ‘

r

’ signals a Reset and is 

displayed for about half a second. 

(Exception: the small ‘

r

’ can be displayed 

longer during the latch holding time; max. 

10 min).

F

The ‘

F

’ indicates that travel is enabled. The 

system status is “live” (i.e. an emergency 

stop will be triggered if the protective field 

is penetrated). A flashing “

F

” signals that 

the system is “live”, even though 

Latch_In 

(Riegel_In)

 is LOW. The reason is that at 

least one of the 

Option 2

 and 

Override 

Delay

 inputs is still at ‘HIGH’.

U

The ‘

U

’ indicates that the light curtain has 

been overridden when the elevator is at 

floor level. Penetration of the protective 

field does not trigger an emergency stop. 

The 

Option 2

 and 

Override Delay

 inputs 

are at ‘LOW’.

H

The system is experiencing an emergency 

stop triggered by penetration of the 

protective field. The safety circuits have 

been broken. The elevator can only 

recommence operation via a 

Reset

 or an 

internal call signal (Innenruf)

 while the 

light curtain is uninterrupted.

0

Rotating segment in circle. The self-test 

is being conducted after activation of the 

plug-in system controller.

C

Component test for production has been 

activated. You should never experience this 

display. However, please check the wiring 

of your 

internal call signal (Innenruf)

 

should it occur.

10.5  Display and operation in cabin interior

The elevator stops immediately after elevator users or 

objects penetrate the protective zone. It is recommended 

that the user be made aware of the emergency with the 

optional alarm detector (CEDES Part No.: 101 243) and an 

informational notice. The user can acknowledge (reset) the 

emergency simply be re-actuating the floor button (internal 

call signal (Innenruf)).

Appropriate instructions in the case of elevators with their 

own exactly defined group of users can simplify use and 

help avoid incorrect conduct.

Summary of Contents for cegard/Lift LX/LY

Page 1: ...RoHS Installation and Operation Manual 100 953 220503 V 2 10 English Pages 2 26 Original version German Seiten 27 51 CEDES AG is certified according to ISO 9001 2015 cegard Lift LX LY...

Page 2: ...three phase latch solenoid 13 8 3 Connecting two external output contactors to safety circuit 13 8 4 Overriding the light curtain 13 8 5 Avoidance of errors 14 8 6 Latch stopping time following the en...

Page 3: ...authorized and instructed by the system integrator are allowed to operate install and maintain the cegard Lift LX LY Any alterations to the system by anyone e g the buyer installer or user may result...

Page 4: ...ut Cost effective Simple integration into almost all existing elevator control systems without additional travelling cables Simple space saving installation No setting or optical adjustment of the lig...

Page 5: ...ain can be bypassed with the Override delay bypass delay and Option 2 inputs An U is displayed Bypassing can begin before the Latch signal switches to LOW The light curtain is then overridden if both...

Page 6: ...motor A maximum latch holding time of 10 min is defined precisely for this reason Latch_Out Riegel_Out is adapted to Latch_In Riegel_In after this time period expires However the elevator remains in t...

Page 7: ...out The following three versions are possible 1 The output relays are automatically tested 5 s after Latch_In Riegel_In drops out if the input remains broken The test is carried out immediately if a...

Page 8: ...ing 5 3 3 Timing diagram without premature door opening Drive Zone ON Zone OFF Slow Stop Driving release Latch_In Active Inactive Option 2 Override delay Flush position Safety circuit Latch_Out Protec...

Page 9: ...Calibration is carried out during activation and by pressing the T button on the control unit plug in The control device automatically carries out a calibration if no change occurs in the protective...

Page 10: ...roof with the 4 screws provided or the 2 support strips included in the delivery It is imperative that the following be observed Connections K18 K20 K22 and K24 should be actuated with the positive si...

Page 11: ...DC K13 Internal call signal 7 12 265 VAC DC K14 Internal call signal 8 12 265 VAC DC K15 Internal call signals common potential K16 17 Option 1 not used K18 19 Option 2 12 380 VAC DC K20 21 Flush posi...

Page 12: ...ntactor cegard Lift LX 7 2 cegard Lift LY with latch voltage rectifier The LY version is fitted with a standard rectifier allowing the connection of direct current latch motors or latch solenoids from...

Page 13: ...with the diagram below 22 21 A1 A2 1 3 5 2 6 4 K45 K40 K41 K42 K43 K44 Mounting rail Connections already available N T S R M Latch solenoid Figure 14 Connection diagram latch solenoid 8 3 Connecting...

Page 14: ...call signal 1 8 Innenruf 1 8 Signals created by capacitive or inductive coupling can as a result lead to errors It is particularly important to ensure that the low level at these inputs is less than...

Page 15: ...utton Door lock signal Power supply Latch solenoid Safety circuit Inside calls Reset button Reference potential To the elevator control P N PE berbr ckungsverz gerung B ndigstellung Sicherheitskreis P...

Page 16: ...l signals Innenrufe must also be possible during a safety circuit interruption Cross reference See Chapter 5 3 2 for timing diagram Auswerteeinschub cegard Lift Inside calls or Reset button Door lock...

Page 17: ...Reset button Door lock signal Power supply Latch solenoid Safety circuit Inside calls Reset button Reference potential To the elevator control P N PE berbr ckungsverz gerung B ndigstellung Sicherheit...

Page 18: ...signals Innenrufe must also be possible during a safety circuit interruption Cross reference See Chapter 5 3 2 for timing diagram Auswerteeinschub cegard Lift Inside calls or Reset button Door lock s...

Page 19: ...rol unit plug in and associated opto edges are now ready for operation Both control unit plug ins undergo this procedure in the case of throughloading elevators 9 2 Installation check SAFETY ADVICE Th...

Page 20: ...set and wait briefly It should only be possible to open the landing door if the cabin is flush with it No step should be visible Plug in latch stopping time jumper at 10 min The latch stopping time sh...

Page 21: ...he lower right hand corner of the displays flashes with approx 3 Hz The system is in normal state if this area is flashing The small r signals a Reset and is displayed for about half a second Exceptio...

Page 22: ...signal is permanently LOW Same procedure as with error 5 but involving the Option 2 input 7 The safety circuit the safety check circuit or an external contactor is either permanently broken or closed...

Page 23: ...testing The cegard Lift should be checked for correct function at each legally prescribed elevator service This should involve checking whether the light curtain can be triggered throughout the entir...

Page 24: ...ve positive action contacts with auxiliary contact and meet the requirements of respective regulations in EN 81 and along with other national regulations type testing Electrical Supply voltage USP 195...

Page 25: ...r for one elevator cabin entrance for opto edges with 16 elements 101 071 cegard Lift LX system control rack with latch contactor for two elevator cabin entrances for opto edges with 16 elements 102 8...

Page 26: ...unting material only for standard opto edges 16 elements 114 745 Door control relay for the actuation of an automatic door or for load control display one unit required per entrance 100 849 Alarm tran...

Page 27: ...s von zwei externen Leistungssch tzen am Sicherheitskreis 38 8 4 berbr ckung des Lichtvorhangs 38 8 5 Vermeidung von St rungen 39 8 6 Riegel Haltezeit nach Quittierung des Nothalts durch Reset 39 8 7...

Page 28: ...richtung durch K ufer Monteur oder Benutzer k nnen zu unsicheren Betriebsbedingungen f hren CEDES bernimmt f r Sch den die durch solche Manipulationen entstanden sind keine Haftung oder Garantieanspr...

Page 29: ...sgang auch zur Ansteuerung automatischer T ren geeignet Kosteng nstig Einfache Einbindung in nahezu alle bestehenden Aufzugssteuerungen ohne zus tzliche H ngekabel Einfache und platzsparende Montage K...

Page 30: ...br ckungsverz gerung und Option 2 wird der Lichtvorhang in der T rzone berbr ckt Im Display erscheint ein U Die berbr ckung kann schon vor Abfallen des Riegelsignals eintreten Der Lichtvorhang ist dan...

Page 31: ...r Riegel maximal 10 min festgehalten Nach dieser Zeit wird der Riegel_Out dem Riegel_In angepasst Der Zustand Nothalt wird aber nicht verlassen WICHTIGER HINWEIS Ein Nothalt muss in jedem Fall aus dem...

Page 32: ...nem Riegel zu testen Folgende drei Varianten sind m glich 1 Wenn der Eingang offen gelassen wird werden die Ausgangsrelais automatisch 5 s nach Abfallen der Riegelspannung getestet Kommt innerhalb die...

Page 33: ...3 3 Zeitdiagramm ohne vorzeitige T r ffnung Fahrt Zone EIN Zone AUS Langsam Stop Fahrt freigabe Riegel_In Aktiv Inaktiv Option 2 berbr ckungs verz gerung B ndigstellung Sicherheitskreis Riegel_Out Sch...

Page 34: ...nd beim Dr cken der Taste T an den Steuereinsch ben durchgef hrt Findet w hrend 30 min im Schutzfeld keine Ver nderung statt f hrt das Steuerger t selbstt tig eine Kalibrierung durch Grosse nderungen...

Page 35: ...t den 2 im Lieferumfang enthaltenen Tr gerleisten am Fahrkorbdach befestigt Es ist unbedingt zu beachten dass die Anschl sse K18 K20 K22 und K24 bei Ansteuerung mit Gleichspannung mit dem positiven Po...

Page 36: ...enruf 7 12 265 VAC DC K14 Innenruf 8 12 265 VAC DC K15 Gemeinsames Potential Innenrufe K16 17 Option 1 nicht benutzt K18 19 Option 2 12 380 VAC DC K20 21 B ndigstellung 12 380 VAC DC K22 23 berbr ckun...

Page 37: ...ift LX 7 2 cegard Lift LY mit Riegelspannungs Gleichrichter Die Ausf hrung LY ist werkseitig mit einem Gleichrichter ausgestattet der es erlaubt Gleichstrom Riegelmagnete oder motoren ab 180 VDC anzus...

Page 38: ...A2 1 3 5 2 6 4 K45 K40 K41 K42 K43 K44 Hutschiene bereits vorhandene Verbindung N T S R M Riegel motor Abb 14 Anschlussschema Riegelmotor 8 3 Anschluss von zwei externen Leistungs sch tzen am Sicherhe...

Page 39: ...ut Dadurch k nnen Signale hervorgerufen durch kapazitive oder induktive Kopplungen zu unerw nschten St rungen f hren Insbesondere muss sichergestellt werden dass der LOW Pegel an diesen Eing ngen in j...

Page 40: ...esettaste Riegelmagnet Ansteuerung Power supply Riegelmagnet Sicherheitskreis Innenruf Reset Bezugspotential Zur Aufzugssteuerung P N Schutzerde berbr ckungsverz gerung B ndigstellung Sicherheitskreis...

Page 41: ...den sein Die Innenrufe m ssen bei einem Sicherheitskreisunterbruch mit Strom versorgt werden Querverweis Zeitdiagramm siehe Kapitel 5 3 2 Auswerteeinschub cegard Lift Innenrufe oder Resettaste Riegelm...

Page 42: ...r Resettaste Riegelmagnet Ansteuerung Netzspannung DC Riegelmagnet Sicherheitskreis Innenruf Reset Bezugspotential Zur Aufzugssteuerung P N Schutzerde berbr ckungsverz gerung B ndigstellung Sicherheit...

Page 43: ...den sein Die Innenrufe m ssen auch bei einem Sicherheitskreisunterbruch mit Strom versorgt werden Querverweis Zeitdiagramm siehe Kapitel 5 3 2 Auswerteeinschub cegard Lift Innenrufe oder Resettaste Ri...

Page 44: ...ereinschub mit den zugeh rigen Optoleisten ist nun betriebsbereit Bei Durchladeaufz gen f hren beide Steuereinsch be diese Prozedur durch 9 2 berpr fung der Montage SICHERHEITSHINWEIS Die in diesem Ab...

Page 45: ...ng nochmals anw hlen Fahrtbefehl Reset und kurz warten Die Aufzugst r darf sich nur ffnen lassen wenn der Fahrkorb b ndig steht Es darf keine Stufe sichtbar sein Riegel Haltezeit Jumper auf 10 min ste...

Page 46: ...plays blinkt mit ca 3 Hz Blinkt dieser Punkt befindet sich das System in einem Normalzustand Das kleine r signalisiert einen Reset Es wird f r die Dauer von etwa einer halben Sekunde angezeigt Ausnahm...

Page 47: ...l Option 2 ist permanent LOW Gleiches Prozedere wie unter Fehlernummer 5 bezogen auf den Eingang Option 2 7 Die Sicherheitskreise der Sicherheits Checkkreis oder ein externer Sch tz ist entweder perma...

Page 48: ...nktion hin zu berpr fen Dabei muss kontrolliert werden ob der Lichtvorhang im gesamten berwachungsbereich anspricht z B mit Hilfe des Piepsers 12 4 Umspiegelung Auch eine sehr pr zise Kalibrierung wie...

Page 49: ...65 VAC 50 60 Hz Stromaufnahme 100 mA at 230 VAC Sicherung USP 100 mAF Sicherung Sicherheitskreise 2 x 4 AF Ausg nge Sicherheitskreis Relaiskontakte zwei kanalig mit Wiederanlauf sperre Belastbarkeit 2...

Page 50: ...mente berwachungsh he 2 012 mm 15 2 Ersatzteile Einzelteile Art Nummer Beschreibung 100 949 Steuereinschub 100 937 Sendeleiste 16 Elemente 100 936 Empf ngerleiste 0 7 4 m 16 Elemente 100 951 Empf nger...

Page 51: ...n view without cover Ansicht von oben ohne Deckel Cable inlet sleeves Kabeldurchf hrungst llen For opto edge connection cables F r die Anschlusskabel der Optoleisten Cable screw fittings Kabelverschra...

Page 52: ...630 505 380 255 170 120 70 20 0 16 2 Opto edges Lift LX LY Optoleisten cegard Lift LX LY Part No Art Nr 101 072 101 073 Optional 70 beams 24 elements Operating range 4 8 m Customer specific solutions...

Reviews: