CPR3 Relay - rev.1 

 

DATE: 11/06/13     Pag. 3 of 3 

 
Testing steps (view also the manual of testing kit for correctly setting up the device): 
 

1.  Connect the testing device to cock / ball-valve located at ground level 
2.  Open the cock / ball-valve 
3.  Open clock-wise the grey handle to release the gas into the tubing and await until the alarm 

contact operates 

4.  Close the cock / ball-valve and remove the testing device 
5. 

IMPORTANT:

 At the end of the test release the gas inside the CPR3 to reset the contact. 

To do this operation cover the cock / ball-valve at ground with a cloth (to avoid oil spraying) 
open it acting the side handle awaiting until oil leaks off. After the oil spurges off the cock / 
ball-valve close the handle. 

 

MAINTENANCE 
 

The protective relay CPR3 does not need periodic maintenance; however it is suggested to check 
on  a  regular  basis  the  contact  operation  and  the  free  movement  of  float;  this  test  can  be  easily 
made by pushing down the test button pos.3. 
 

DISPOSAL 

 
Disposal  of  all  parts  shall  be  made  according  to  local  environmental  and  waste  management 
regulations. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 