English
Duration test
Duration test
Duration test
Duration test
Duration test
For battery duration test,
please disconnect luminaire
from mains.
The battery will be discharged
until the deep charging
protection activates.
The time between
disconnecting the luminaire
from mains and activation of the
deep charging protection must
correspond to the rated
duration.
Replace battery if the
Replace battery if the
Replace battery if the
Replace battery if the
Replace battery if the
duration test is not met.
duration test is not met.
duration test is not met.
duration test is not met.
duration test is not met.
Button/LED-foil-
Button/LED-foil-
Button/LED-foil-
Button/LED-foil-
Button/LED-foil-
connection
connection
connection
connection
connection
Changing button/LED or printed
circuit please see marker 1 on
the printed circuit and on the
printed conductor.
Variation in lightoutput
Technical data
Viewing distance
Material
Dimensions in mm (LxHxT)
Supply terminals
Supply voltage
Permissible temperature
Illuminant
Insulation class
Protection category
17m
Plastic
240 x 100 x 65
2,5mm²
230 V 50/60 Hz
-10°C to +40°C
non maintained 4x2,4V/0,75W
maintained 2x230/260V/5W
II
IP 41
Installation
Connect mains
to terminal L and N .
1) Maintained light:
Bridge between L and L' .
2) Switched maintained light:
(common switch for emergency
lighting and general lighting):
Connect general lighting switch
between L and L' .
Set switch S1 into position "on"
for operating state.
Testing
Change between mains
and emergency lighting
The mains and emergency
lighting function can be tested
by disconnecting the luminaire
from mains or by pressing the
testing push button at the
luminaire.
Light output during first minute
Maintained
Non maintained