background image

EN

EN

V1SR - V3SR - V4SR - V5SR 

Internal surface maglock

3

cdvigroup.com

POWER SUPPLY

An electromagnetic lock always operates in DC current, a very low safety voltage. The Diax

®

 electromagnetic 

lock is recommended for use with power supplies manufactured by CDVI, however, other power supplies 

may be used on condition that they are of equivalent quality and characteristics rectified, filtered, regulated 

and protected by fuse in primary and secondary sectors.

MOUNTING RECOMMENDATIONS

- Define the level of security of the access.

- Determine the maximum strength of holding force to this level of security.

- Select the Diax

®

 electromagnetic lock according to the environment, the inside, the outside, the climatic  

  constraints, (For example: stainless steel dedicated to an outside use).

- Always install the electromagnetic lock on the secure side of the place to be secured.

- Indeed make sure that the frame and opening, receiving or supporting the electromagnetic lock, armature  

  plate and their accessories, are solid and resistant to damage or wear over a period of time. 

- Consider any bracketry required for the assembly according to the type of support receiving

  the electromagnetic lock and armature plate.

- Define the passage of cables to ensure the protection against the vandalism and the environmental

  requirements (in particular through flexible hoses of door, glands, gutters, cross cables, plastic tubes).

Security ropes

The electromagnetic lock undergoes repeated 

shocks and the vibration at the points of fixation 

on the frame (frequencies of openings / closures, 

attempt of opening wears closed and attempts 

of vandalism) which can loosen the fixing bolts/

screws. To prevent the risk of the electromagnetic 

block from falling, install both security ropes 

supplied, to guarantee the safety of the users 

(see attached plan).

Security rope

(fixing on the magnetic lock and the frame)

APPROVAL RELATIVE TO EMERGENCY EXITS:

In the case of an installation of electromagnetic lock on emergency exits, it is imperative to make sure that 

these exit points will be automatically free in case of fire alarm, to open in the event of a fire alarm to allow 

evacuation of the premises. The electromagnetic lock installed on emergency exits must be in accordance 

with the fire approval department (Ex: In France = NF 61-937).

For more information, contact CDVI, the local fire officer or the safety officer responsible for the building. 

Armature plate

- It is vital to fix the electromagnetic lock

  and armature plate solidly on their supports.

- Make sure that the magnet and the armature  

  meet evenly over their entire mating surfaces.

- The Armature plate must be able to pivot  

  slightly about its center mounting screw 

  to compensate for any door misalignment.

Summary of Contents for V1SR

Page 1: ...1 FI NO DK SE EN V1SR V3S V3SR V3SRB V4S V4SR V4SRB V5S V5SR V5SRB Internal surface maglock V4SR V1SR V3SR V5SR...

Page 2: ...s 254 x 50 x 30mm V5S series 272 x 66 x 40mm Armature dimensions L x W x D 180kg 130 x 32 x 9mm 300kg 185 x 38 x 11mm 400kg 185 x 45 x 12mm 500kg 185 x 60 x 12mm Power supply 12 24V dc Power absorptio...

Page 3: ...vandalism and the environmental requirements in particular through flexible hoses of door glands gutters cross cables plastic tubes Security ropes The electromagnetic lock undergoes repeated shocks an...

Page 4: ...AGNETIC LOCK V1SR ELECTROMAGNETIC LOCK V3S V4S AND V5S SERIES MAINTENANCE The Electro magnet and armature plate have a specific treatment which strengthens the protection against wear and corrosion Th...

Page 5: ...lly closed COM COM N O NO Normally open WITH BUILT IN PCB BOARD 12V dc Factory Setup 12V dc 24V dc 24V dc Voltage selection jumpers Voltage selection jumpers 4 OPTIONAL ACCESSORIES References L3L4L5 Z...

Page 6: ...mature plate M8 screw Cap nut Guide piece Rubber washer Roll pin Steel washer Rubber washer Fixing plate Door frame Outwards opening door push door Electromagnetic lock Armature plate Cap nut Guide pi...

Page 7: ...ing door Pull door Fixing screw Rubber washer Roll pin Steel washer Armature plate M8 screw DOOR FRAME OUTSIDE INSIDE DOOR 7 INSTALLATION WITH ACCESSORIES Fixing plate Security rope Security rope Secu...

Page 8: ...ss door OUTSIDE INSIDE DOOR FRAME Electromagnetic lock Universal base for glass door UBKU DOOR Fixing plate Armature plate DOOR GLASS FRAME Adjustable UBKP Inward opening door Pull door installed with...

Page 9: ...circuit correctly Holding force reduced The lock and the armature are not lined up with each other Check that the lock is connected to the circuit correctly Check that the electromagnet and the armatu...

Page 10: ...tans dimensioner L x B x H 180kg 130 x 32 x 9mm 300kg 185 x 38 x 11mm 400kg 185 x 45 x 12mm 500kg 185 x 60 x 12mm Sp nningsmatning 12 24V dc Str mf rbrukning 12 V DC 500mA 24 V DC 250mA Produkt H llkr...

Page 11: ...derf rh llanden t ex genom flexibla karm verf ringar kabelr nnor plastr r S kerhetsvajrar Elektromagnetens f sten uts tts f r upprepade vibrationer och andra p frestningar under sin livstid ppningsfre...

Page 12: ...monteringsskruvarna p elektromagneten regelbundet Kontrollera ven att ankarplattan kan vicka runt monteringsskruven Vi rekommenderar att l sbrickor anv nds till alla monteringsskruvarna 3 MONTERINGSSA...

Page 13: ...inst ll ning 12 V 4 TILLBEH R Produkt L3L4 300KG L5 500KG Z3Z4Z5 UBKU UBKP AMA3 AMA5 DPM300 DPM500 LZ1 Beskrivning L format vinkelf ste 300 400 500kg Z format vinkelf ste 300 400 500kg Monteringsplatt...

Page 14: ...rses med str m En felaktigt placerad bygel kan skada elektromagneten Den h r typen av skada t cks inte av garantin VIKTIGT 6 MONTERING EXEMPEL V3SR Monterings f ste S kerhets vajer S kerhets vajer An...

Page 15: ...agnet Ankarplatta D RR Ut tg ende d rr Ankarplatta Skruv M8 S kerhets vajer Monterings f ste S kerhets vajer Gummibricka Bricka Styrpinne Elektromagnet Ankarplatta Reglerbart In tg ende d rr installer...

Page 16: ...atta Monteringsf ste f r glasd rrar UBKU D rr Monteringsf ste Elektromagnet Z3Z4Z5 L3L4L5 Ankarplatta D rr Glasv gg Reglerbart UBKP In tg ende d rr installerad med monteringsplatta f r ankarplattan p...

Page 17: ...edsatt Elektromagneten och ankarplattan r inte helt parallella med varandra Kontrollera att elektromagneten f r r tt sp nningsmatning Kontrollera att elektromagneten och ankarplattan r parallella och...

Page 18: ...185 x 45 x 12 mm 500 kg 185 x 60 x 12 mm Str mforsyning 12 24V DC Str mforbrug 12 V DC 500 mA 24 V DC 250 mA 1 PRODUKTSPECIFIKATION V3S V4S og V5S serierne er tilpasset kravene i den nye standard for...

Page 19: ...m de for at beskytte mod h rv rk og vejrlig fx gennem fleksible karmoverf ringer kabelrender eller plastr r Sikkerhedswirer Magnetl sens beslag uds ttes i deres levetid for gentagne st d og vibration...

Page 20: ...mm Afstands muffe Monterings bolt Brugs anvisning 1 1 1 2 2 5 1 1 1 1 1 MAGNETL S V1SR MAGNETL SENE V3S V4S OG V5S VEDLIGEHOLD Elektromagneten og ankerpladen er specialbehandlet for at modst korrosio...

Page 21: ...sed COM COM N O NO Normally open MED INDBYGGET PCB KORT Fabriks indstilling 12 V 12V dc 24V dc 24V dc Jumpere til sp ndingsvalg Jumpere til sp ndingsvalg 4 TILBEH R Produkt L3L4L5 Z3Z4Z5 UBKU UBKP AMA...

Page 22: ...Sikkerheds wire Sikkerheds wire Ankerplade M8 skrue Monteringsbolt Afstandsmuffe Gummiskive Styretap St lskive Gummiskive Monterings beslag D rramme Udad bnende d r Elektro magnet Anker plade Monteri...

Page 23: ...ing p indadg ende d r Sikkerhedswire Gummiskive Styretap St lring Ankerplade M8 skrue D RRAMME UDEFRA INDEFRA D R 7 MONTERING MED TILBEH R Monteringsbeslag Sikkerheds wire Fastg relses skrue Sikkerhed...

Page 24: ...asd r UDEFRA INDEFRA D RRAMME Elektromagnet Universalbeslag til glasd r UBKU D R Monteringsplade Ankerplade D R GLAS RAMME Justerbar UBKP Indad bnende d r Installeret med UBKP L3L4L5 og Z3Z4Z5 beslag...

Page 25: ...raften er nedsat Elektromagneten og ankerpladen er ikke helt parallelle Kontroller at elektromagneten modtager den rigtige sp nding Kontroller at elektromagneten og ankerpladen er parallelle og m des...

Page 26: ...EN V1SR V3SR V4SR V5SR Internal surface maglock 26 cdvigroup com...

Page 27: ...EN V1SR V3SR V4SR V5SR Internal surface maglock 27 cdvigroup com...

Page 28: ...LGIUM NETHERLANDS LUXEMBOURG 32 0 56 73 93 00 www cdvibenelux com CDVI TAIWAN 886 0 42471 2188 www cdvichina cn CDVI SUISSE 41 0 21 882 18 41 www cdvi ch CDVI CHINA 86 0 10 84606132 82 www cdvichina c...

Reviews: