1] GENERAL INFORMATION
Flush mounting.
High corrosion resistance.
Delivered with armature plate.
No mechanical wear.
Ease of installation.
Recommended for indoor use.
Positive safety (frees access immediately
in the event of a power cut).
Holding force:
180 - 400kg.
No residual magnetism.
Built-in electronic protection
to eliminate back EMF.
Electromagnetic lock dimensions (L x W x D):
- V1ER = 202 x 34 x 21mm
-
V3E series = 227 x 38 x 26mm
-
V4E series = 227 x 43,5 x 29mm
- V3E32 = 299 x 32 x 27mm
- V3E35R = 235 x 35 x 24mm
- V3E36R = 228 x 36 x 27mm
Armature dimensions (L x W x D):
- 180kg = 130 x 32 x 9mm
-
300kg = 185 x 38 x 11mm
-
400kg = 185 x 45 x 12mm
- V3E32 = 249 x 32 x 11mm
Power supply: 12/24V dc.
Power absorption:
- 12 V DC = 500mA,
- 24 V DC = 250mA.
References
Holding force
Monitored
V1ER
180kg
V3E
300kg
-
V3ER
300kg
V4E
400kg
-
V4ER
400kg
V3E32
300kg
-
V3E35R
300kg
V3E36R
300kg
IP42
ARD212
BS60
Recommended
power supplies
2] REMINDERS AND RECOMMENDATIONS
2] REMINDERS AND RECOMMENDATIONS
The function of an electromagnetic lock is to ensure the locking of an access point. This document is a guide
of installation which will allow you to secure the installation according to the characteristics of the product,
the site and the environmental requirements.
APPROVAL RELATIVE TO EMERGENCY EXITS:
In the case of an installation of electromagnetic lock on emergency exits, it is imperative to make sure that
these exit points will be automatically free in case of fire alarm, to open in the event of a fire alarm to allow
evacuation of the premises. The electromagnetic lock installed on emergency exits must be in accordance
with the fire approval department (Ex: In France = NF 61-937).
For more information, contact CDVI, the local fire officer or the safety officer responsible for the building.