7] FAULT FINDING

PROBLEM

POSSIBLE CAUSE

SOLUTION

Door locking 

impossible

The lock is not receiving 

DC current.

- Check that the wires are connected to the right  

  terminals.

- Check that the power supply is compatible.

- Check that the lock is connected to the circuit  

  correctly.

Holding force 

reduced

The lock and the armature are not 

lined up with each other.

- Check that the lock is connected to the circuit    

  correctly.

- Check that the electromagnet and the armature

  are properly aligned. 

- Check that the contact faces are free from dirt and rust.

- Check that the armature is soft mounted.

Low voltage or armature jammed.

- Check that the lock is receiving the correct power    

  supply satisfactorily.

- check the tightening of the armature 

  and the condition of the rubber.

Faulty reed 

switch

Voltage too low. Misalignment.

- Check the power supply.

- Cable cross section to be determined according 

  to the power supply and the locking.

- e.g.: 2 x 1.5mm2 ≥ 10m.

8] NOTES

EN

V1ER - V3E - V3ER - V3E35R - V4E - V4ER - V5E

Mortice Electromagnetic locks 

  INSTALLATION MANUAL

Summary of Contents for V1ER

Page 1: ...The installer s choice cdvigroup com V1ER V3E V3ER V3E35R V4E V4ER V5E Mortice Electromagnets V1ER V3E V3ER V3E35R V5SRB V4E V4ER V5SRB ENGLISH EN V5E ...

Page 2: ...g V3E 300kg V3ER 300kg V3E35R 300kg V4E 400kg V4ER 400kg V5E 500kg EC certification WEEE IP42 2 cdvigroup com RoHS ARD212 BS602 Recommended power supplies Depending on the version The function of an electromagnetic lock is to ensure the locking of an access point This document is a guide of installation which will allow you to secure the installation according to the characteristics of the product...

Page 3: ...re solid and resistant to damage or wear over a period of time Consider any bracketry required for the assembly according to the type of support receiving the electromagnetic lock and armature plate Define the passage of cables to ensure the protection against the vandalism and the environmental requirements in particular through flexible hoses of door glands gutters cross cables plastic tubes POW...

Page 4: ... the lock This type of damage is not covered by the warranty IMPORTANT NOTE 12V dc factory setup ELECTROMAGNETIC LOCK V3E V3ER V3E35R V4E V4ER V5E 4 OPTIONAL ACCESSORIES References AMCCHANFR16 AMCCHANFR20 Description Armature mounting plate Mortice magnetic lock Armature plate Roll pin 5x16 Steel washer Joggle bracket excepted for the V5E M5x8 screw Key 5mm 1 1 2 2 2 8 1 M8x35 screw M8x25 screw Gu...

Page 5: ...ONNECTION 12V DC Red White Green Black 24V DC Red White Green Black CONTACT Yellow NC Blue COM Orange NO Steel washer Roll pin Armature plate Rubber washer Screw Screw Screw Joggle bracket Joggle bracket Armature plate support AMCCHANFR20 or AMCCHANFR16 Optional Screw Armature screw EN V1ER V3E V3ER V3E35R V4E V4ER V5E Mortice Electromagnetic locks INSTALLATION MANUAL ...

Page 6: ...correctly Check that the electromagnet and the armature are properly aligned Check that the contact faces are free from dirt and rust Check that the armature is soft mounted Low voltage or armature jammed Check that the lock is receiving the correct power supply satisfactorily check the tightening of the armature and the condition of the rubber Faulty reed switch Voltage too low Misalignment Check...

Page 7: ...7 cdvigroup com FR V1ER V3E V3ER V3E35R V4E V4ER V5E Ventouse électromagnétiques encastrées MANUEL D INSTALLATION ...

Page 8: ...0 682 7945 Fax 1 450 682 9590 CDVI BENELUX BELGIUM NETHERLAND LUXEMBOURG Phone 32 0 56 73 93 00 Fax 32 0 56 73 93 05 CDVI TAIWAN Phone 886 0 42471 2188 Fax 886 0 42471 2131 CDVI SUISSE Phone 41 0 21 882 18 41 Fax 41 0 21 882 18 42 CDVI CHINA Phone 86 0 10 62414516 Fax 86 0 10 62414519 CDVI IBÉRICA SPAIN PORTUGAL Phone 34 0 935 390 966 Fax 34 0 935 390 970 CDVI ITALIA Phone 39 0321 90 573 Fax 39 33...

Reviews: