Digiway SR Easy Start Guide
Pre Calibration:
Check door has full free movement.
Make sure any locking is completely released.
Check the door travel area is free of any potential blockages.
Assure no one can enter the area while calibration is in progress, set “DANGER TESTING
PROGRESS” signs or similar.
Set the external rocker switch to “0”
Spring Preload:
Make sure unit is set
‘
Free Mode
’
–
rocker switch in centre position
“
0
”
.
Set up the Spring preload: enter the menus and navigate to the calibration menu.
Enter the Spring preload menu and select
‘
Reset
’
, now increase the preload to around 90° in the direction of the
arrow and attempt to fit the arm to the drive shaft, if adjustment is required increase the rotation until the arm
fits onto the drive pins.
Save the setting but DO NOT ENTER DOOR LIMITS.
Tighten the arm fixing bolt.
Exit the menu and carry a out a spring force test by open the door manually and releasing to make sure the door
closes; it will shut hard as the motor is not controlling the closing force.
If Ok proceed to
‘
Arm Type
’
and set to
‘
Articulated
’
, if not repeat the spring preload phase unit the door closes
adequately.
Calibration:
Select
‘
Door Limits
’
from the menu set up.
Press “OK” and follow the on
-screen instructions to set the open/close limits.
Note: Set open limit 10cm more than required.
When finished “Thank You” will be displayed
Press “Up”, “Auto Calibration” will be displayed, press
OK.
Follow the on-screen prompts.
Note: The door will open and close very quickly over 5 actuations.
Once completed “Save will appear on the display, press Ok.
Press scroll to exit and press ok.
Set external rocker switch to “I”
Carry out a full cycle without interruption, on completion the LP LED (on the end cap) will be green and an upper
and lower case I will appear on screen
‘
iI
’
.
Individual settings can n
ow be entered using the “Main Settings” menu, Fine tuning of the door motion can then be
completed via the Advanced Settings” menu. Please refer to the manual.