the beginning (Start Point) of the E-bus
Network. Otherwise, place the A+ and B-
BIAS jumpers on HIGH (see Figure 2 and
Figure 3).
Figure 3: Setting the BIAS A+ and BIAS B- jumpers
A+
B-
LOW
HIGH
A+
B-
LOW
HIGH
Jumpers
set to LOW
Jumpers
set to HIGH
350mA/700mA Battery
Charging Jumper
The 350mA/700mA Jumper allows you to
select the charging current for the backup
battery of the 2-Door Expansion Module.
Charging the battery at 350mA takes
longer, but consumes less power. Charging
the battery at 700mA takes less time, but
consumes more power.
Figure 4: Setting the 350mA/700mA jumper
Jumper set to
350mA
Jumper set to
700mA
Programming in Centaur
Using the Centaur Access Control Software,
program the inputs, outputs, readers, and
keypads connected to the 2-Door Expansion
Module. The options are explained in the
Centaur Access Control Software Reference
Manual
. Centaur will identify the 2-Door
Expansion Module by its address (defined by
the DIP Switches 1 & 2) and will recognize
the devices as follow:
Address 1 Address 2 Address 3
Doors
Keypad/Reader 1
Door 3
Door 5
Door 7
Keypad/Reader 2
Door 4
Door 6
Door 8
Inputs
Z1
Input 17
Input 21
Input 25
Z2
Input 18
Input 22
Input 26
Z3
Input 19
Input 23
Input 27
Z4
Input 20
Input 24
Input 28
outputs
OUT1
Output 7
Output 13
Output 19
OUT2
Output 8
Output 14
Output 20
OUT3
Output 9
Output 15
Output 21
OUT4
Output 10
Output 16
Output 22
OUT5
Output 11
Output 17
Output 23
OUT6
Output 12
Output 18
Output 24
Doors cannot be defined as Door
Type
Elevator (
Door Properties
window,
General
tab,
Door Type
:
Elevator
) and the module does
not support Interlock Inputs (
Door
Properties
window,
Inputs and
outputs
tab,
Interlock Input
).
Other modules in the system cannot
activate the 2-Door Expansion
Module’s outputs. The 2-Door
Expansion Module does not support
Zone Doubling (see Figure 6).
CAA470A
2-Door expansion module
INSTALLATIoN MANUAL
Figure 5: CAA470A indicators
Green “AC oK” LED:
ON = AC power
OFF = Power failure
Green “AUx oK” LED:
ON = Auxiliary power
OFF = Auxiliary power failure
red “CoMM” LED:
ON = Communication failure
OFF = OK
Green “CHECK BATT” LED:
ON = Battery verification in
progress (every minute)
red “BATT TrBL” LED:
ON = Battery low or
disconnected
Red “TX” LED and
green “RX” LED:
Brief or steady ON =
Communication OK
OFF = Communication
failure
Green “READER#2 data” and “READER#1 data” LED:
Long flash = Receiving card data
Short flash = Receiving card data but unknown or invalid format
OFF = Not receiving card data
Green “lock#1” and “lock#2” LEDs:
ON = Relay activated.
Green “STATUS” LED:
1-second flash = Module OK
Slow flash = Communication failure
(see also “COMM” LED)
+
SP
+12V
R1/KPD
R1/KPC
R1/KPB
R1/KP
A
OUT2 OUT1
R1/D1
R1/D0
R1/0V
R1/+5V
SP
+12V
R2/KPD
R2/KPC
R2/KPB
R2/KP
A
OUT4 OUT3
R2/D1
R2/D0
R2/0V
R2/+5V
AC
AC
BAT+
BAT-
V+
V+
V-
V-
OUT5
OUT6
A+
B-
GND
TMP
TMP
D1NC
COM
D1NO
D2NC
COM
D2NO
Z1
COM
Z2
Z3
COM
Z4
CAA470A
2-Door Expansion Module
LOCK#1
AC OK
EOL
BACKUP
SWITCH
ADD 1
SW1
ADD 2
SW2
L1Energize
SW3
L2Energize
SW4
BACKUP1
SW5
BACKUP2
SW6
PULSE 5&6
SW7
N/D
SW8
READER#1
DATA
READER#2
DATA
NO CARD
LOW HIGH
TX RX
E-BUS
B-
A+
2 CARDS
ALL CARDS
UNLOCK DOOR
2
0
0
1
1
1
0
1
0
1
AUX OK
COMM
CHECK BATT
BATT TRBL
LOCK#2
STATUS
JP120
350mA/700mA
ON
1 2 3 4 5 6 7 8