2
cdvi.com
cdvigroup.com
TERMINAL BLOCK
OUTPUTS
VOLTAGE
+
+12V dc
+
+12V dc
-
0V
-
0V
1
230V ac
2
230V ac
230V ac
Primary
500mA Fuse
+ + - -
outputs
Secondary
3.15A Fuse
Do not adjust the factory-set
potentiometer
BS602
Uninterruptible PSU
INSTALLATION MANUAL
BA
TTER
Y
Regulated PSU.
7 A/H battery included.
Polycarbonate casing.
Primary and secondary inputs
protected by fuses.
VO: fi re-retardant.
Input voltage: 230V ± 10%, 50/60 Hz.
Power consumption: 0.25A.
Output: 12V dc regulated, uninterruptible.
Maximum load current: 2A (nominal), 2,5A (peak).
INSTALLATION
Do not use the central contact on the 230V
terminal block.
When mounting on a wall, use the screw
holes at the four corners of the casing.
Pass the wires through the hole designed
for this purpose.
Put the battery in the casing.
Connect the wires of the battery.
- Red wire: + terminal,
- Black wire: - terminal.
PRODUCT PRESENTATION
IP30
0°C to +40°C
CE certifi cation
WEEE & RoHS
COMPLIANT WITH EUROPEAN STANDARDS
EN 55022
EN 61000-3-2
EN 61000-3-3
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
This product must be installed in accordance
with the local safety standards.
Position the PSU
as on the left,
with the label
horizontal.