TERMINAL BLOCK 

OUTPUTS 

VOLTAGE

+

+12V dc

+

+12V dc

-

0V

-

0V

1

230V ac

2

230V ac

230V ac

Primary

500mA Fuse

+ + - - 

outputs

Secondary

3.15A Fuse

Do not adjust the factory-set

potentiometer

BS602

Uninterruptible PSU

INSTALLATION MANUAL

BA

TTER

Y

  Regulated PSU.

  7 A/H battery included.

  Polycarbonate casing.

  Primary and secondary inputs 

   protected by fuses.

  VO: fi re-retardant.

 

Input voltage: 230V ± 10%, 50/60 Hz.

 

Power consumption: 0.25A.

 

Output: 12V dc regulated, uninterruptible.

 

Maximum load current: 2A (nominal), 2,5A (peak).

INSTALLATION

 

Do not use the central contact on the 230V  

 

  terminal block.

 

When mounting on a wall, use the screw  

 

  holes at the four corners of the casing.

 

Pass the wires through the hole designed 

  for this purpose.

 

Put the battery in the casing.

 

Connect the wires of the battery.

  - Red wire: + terminal,

  - Black wire: - terminal.

PRODUCT PRESENTATION

IP30

0°C to +40°C

CE certifi cation

WEEE & RoHS 

COMPLIANT WITH EUROPEAN STANDARDS 

EN 55022

EN 61000-3-2

EN 61000-3-3

EN 61000-4-2

EN 61000-4-3

EN 61000-4-4 

EN 61000-4-5

EN 61000-4-6

EN 61000-4-11

This product must be installed in accordance

with the local safety standards.

Position the PSU

as on the left,

with the label 

horizontal.