2
cdvigroup.com
3
cdvigroup.com
Wiegand 26, 30 or 44 bit.
Direct connection.
PCB sealed in epoxy.
Audible and visual feedback.
45cm pigtail wire connection (STARPW-STARPB).
Versions available: white, black or grey.
SOLARPW-SOLARPB (L x W x D): 130 x 90 x 28mm.
STARPW-STARPB (L x W x D): 130 x 41 x 28mm.
Technology: 125 Khz.
Multi card protocol reader - Marin/HD.
Input voltage: 12V dc.
Consumption: 100mA.
1] PRODUCT PRESENTATION
3] MOUNTING KIT
2] REMINDERS AND RECOMMENDATIONS
Foam seal
Foam seal
3x30
TF screw
S5
Plastic anchor
TORX
®
bit
3x8
TORX
®
screw
Varistor
SOLARPW(PB)
1
-
2
2
1
1
1
STARPW(PB)
-
1
2
2
1
1
1
Important
To protect the device
from back-emf, do not
forget to install the varistor
across the lock terminals,
in parallel.
Suggested
power supplies
ARD12 & BS60 (in case
the reader is powered
neither by the controller
nor by the reader controller
[INTBUSW]).
Recommended cables
4 twisted pairs 0.6mm (AWG 24).
Environment
When in a humid area or
close to the sea, we recom-
mend applying varnish to the
terminals to avoid oxidation.
This product is supplied
with a varistor.
The varistor must be connec-
ted directly to the locking
system terminals (electric
strikes, electromagnet, or
lock) operated by the device.
If the device functions with
several locking systems,
each one must be fitted with
a varistor. The varistor limits
overload produced by the
strike coil, known as self-
effect or back-emf. If you are
using a “Shear Lock”, elec-
tromagnet or other type of
electric lock, we recommend
the use of a dedicated power
supply for the lock.
For optimal
illumination,
do not fold
the cable
inside the
product.
CE Certification
Certification FCC CFR 47
part 15 compliance
WEEE
IP53
-25°C to +70°C
Ref :
SOLARPW-SOLARPB
Ref :
STARPW-STARPB
3
1
Measure and mark the center lines to determine the
reader position. Drill the fixing screw holes (Diameter:
5mm). Drill the wiring access area (Diameter: 15mm).
2
Place the foam seal at the back of the reader. Take
care to begin from the bottom. (Sch. a). The foam seal
must be visible (about 2mm) on the top-back of the rea-
der (Sch. b).
4] MOUNTING
Ref:
SOLARPW-SOLARPB
Make sure that there are no pieces missing from the mounting kit. Use the correct tools according to the installa-
tion (drill, screwdrivers, tape measure,...) and follow the mounting instructions of the reader.
1
2
Sch. a
Sch. b
fig. c
Sch. c
Foam seal
3
Insert the plastic plugs in the mounting holes, connect the cable (refer to wiring diagram on page 11), then fasten
the reader with the TORX
®
screw using the TORX
®
bit (Sch. c). Make sure that the varistor is connected across the
lock (refer to page 8 “Reminders and recommendations”).
EN
EN
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125Khz Proximity Readers
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125Khz Proximity Readers
INSTALLATION MANUAL