6.Specifications – Tower Models
MODEL
UPO 11-1(AX)
UPO 11-1.5(AX)
UPO 11-2(AX)
UPO 11-3(AX)
CAPACITY*
1000VA/1000W
1500VA/1500W
2000VA/2000W
3000VA / 3000W
INPUT
Voltage
Range
Low Line
Transfer
80VAC/70VAC/60VAC/55VAC ± 5 %
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line
Comeback
87VAC/77VAC/67VAC/52VAC ± 5 %
High Line
Transfer
152 VAC ± 5 %
High Line
Comeback
145 VAC ± 5 %
Frequency Range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power Factor
≧
0.99 @ full load
THDi
≦
5% @ 100~130VAC THDU < 1.6% @ input and full linear load condition
OUTPUT
Output voltage
100*/110*/115*/120/127 VAC
AC Voltage Regulation
± 1% (Batt. Mode)
Frequency Range
(Synchronized Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
Current Crest Ratio
3:01
Harmonic Distortion
≦
2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
Transfer
Time
AC Mode to
Batt. Mode
Zero
Inverter to
Bypass
< 4 ms
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
≧
90% @ full charged battery
≧
91% @ full charged battery
ECO Mode
≧
98% @ full charged Battery
Battery Mode
≧
88%
≧
90%
BATTERY
Battery Type
12V/7AH
12V/9AH
12V/7AH
12V/9AH
Numbers
3
3
6
6
Recharge Time
3 hours recover to 95% capacity for internal battery@ 2A charging current, Discharge FV
time at 25° C / 10,20V
Charging Current
Default 2A, max. 16A adjustable opcional
Charging Voltage
41.0 VDC ± 1%
41.0 VDC ± 1%
82.1 VDC ±1%
82.1 VDC ±1%
PHYSICAL
Dimension, DxWxH (mm)
397 X 145 X 220
421 X 190 X 318
Net
Weight
With battery
13.0kg
14.6kg
23.2kg
28.0kg
Without battery
6.6kg
7kg
9.9kg
12.3kg
ENVIRONMENT
Operation Humidity
20-95 % RH @ 0- 40°C (non-condensing) / -45°C to 74°C without Batteries
Noise Level
Less than 50dBA @ 1 Meter (With fan speed control)
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Summary of Contents for UPO11-1RT
Page 14: ...2 Battery kit 3 Battery kit...
Page 15: ...4 Battery kit 5 Battery kit...
Page 17: ......