Wiring.
Standard.
Group Configuration.
A 10-amp, 230-volt power supply is applied to
terminals L, N & E (Without heater kit.)
Local controllers are connected to terminals A & B
Central controllers / BMS gateways are connected to
terminals U3 & U4
When being used as an Individual unit, “bit” switch
SW703 bit 4
must be turned to the
ON
position,
factory default is OFF.
* HE models ONLY*
Slightly different set-up for the
HE1
models.
When being used as an individual unit, “
Link CN71
”
must be “
Unplugged
” from the PCB.
Factory default is link plugged in.
Up to 8 units can be group
controlled.
Using a 2-core 0.5mm cable
Connected to terminals A & B at
each unit within the group.