![CDI CD52 Bandit User Manual Download Page 14](http://html.mh-extra.com/html/cdi/cd52-bandit/cd52-bandit_user-manual_2576654014.webp)
CD52 Bandit (ATEX-IECEx Certification) User Guide
Page 14 of 48
SETUP & OPERATION
FOR BATTERY OPERATION, PLACE JUMPER
HERE
FOR 24V OPERATION, PLACE JUMPER HERE
P1
DETAIL 'A'
OFF
+5
+3.3
BATT
It is the responsibility of the customer to make these connections properly whatever
pipe or conduit is chosen for the job.
1. Remove a plug in the side of the outlet body for insertion of customer wiring. 2. Remove the lid of the outlet body. 3. Install the customer provided conduit and wiring. For wiring, strip off wire insulation to expose 5/16" le
ngth of wire.
Insert a small diameter screw driver (or similar tool) i
nto a square
opening and depress the tab. This will open the adjacent
round
terminal. Insert the exposed wire into the terminal unti
l it stops,
then remove the tool from the square opening to secure t
he wire.
4. Reassemble the lid with the outlet body.
ATEX BANDIT WIRING/
INSTALLATION INSTRUCTIONS
5. Open Bandit enclosure and move jumper on PCB as shown in Detail 'A'. 6. Replace Bandit enclosure.
If 24V Connections were used,
complete steps 5 & 6
BLACK WIRE
BROWN WIRE
RED WIRE
YELLOW WIRE
WHITE WIRE
COMMON
NORMALLY OPEN
NORMALLY CLOSED
INSTALL SITE POWER +24VDC
INSTALL SITE POWER 0VDC
CDI USE ONLY
CUSTOMER
CONNECTIONS
(DO NOT CONNECT COMMON
TO 0VDC TERMINALS)
CDI CONNECTIONS
OUTLET BODY
SHOWN WITH COVER REMOVED
24V VOLTAGE REQUIREMENTS
21.6 VDC MINIMUM 26.4 VDC MAXIMUM MEASURED AT CD52 TERMINAL BLOCK
STANDARD: 0.48 WATTS HEATER OPTION: 12 WATTS INTERMITTENT RIS OPTION: 8.4 WATTS
POWER REQUIREMENTS
REVISIONS
REV.
DESCRIPTION
DATE
APPROVED
A
RELEASED
6/26/2012
DS
B
REVISED PER ECR 11251301; REPLACED OUTLET BODY; REVISED NOTES & TITLE TO INCLUDE ALL ATEX BANDITS
1/23/2014
DS
D
C
B
A
A
B
C
D
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CDI. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CDI IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
NEXT ASSY
USED ON
APPLICATION
DIMENSIONS ARE IN INCHES TOLERANCES: FRACTIONAL
1/32
ANGULAR:
2
TWO PLACE DECIMAL
.03
THREE PLACE DECIMAL
.010
MATERIAL
FINISH
DRAWN
CHECKED
ENG APPR.
MFG APPR.
Q.A.
COMMENTS:
DATE
NAME
TITLE:
SIZE
B
DWG. NO.
REV
WEIGHT:
SCALE:
UNLESS OTHERWISE SPECIFIED:
B
WIRING INSTRUCTIONS,
CD52 ATEX BANDIT
SHEET 1 OF 1
89-03-0062-00
DO NOT SCALE DRAWING
INTERPRET GEOMETRIC TOLERANCING PER: ASME Y14.5M - 1994
DS
9/23/2008
ECN #: