background image

4.3 

Electrical connections

Carry out the electrical wiring by connecting only one wire to 
each terminal, according to the following diagram, checking 
that power supply is the same as indicated on the instrument 
and the load current absorption is no higher than the maxi-
mum electricity current permitted.
As the instrument is built-in equipment with permanent con-
nection inside housing, it is not equipped with either switches 
or internal devices to protect against current overloads: the 
installation will include an overload protection and a two-
phase circuit-breaker, placed as near as possible to the in-
strument and located in a position that can easily be reached 
by the user and marked as 

instrument disconnecting 

device

 which interrupts the power supply to the equipment.

It is also recommended that the supply of all the electrical circuits 
connected to the instrument must be properly protected, using 
devices (ex. fuses) proportionate to the circulating currents.
It is strongly recommended that cables with proper insulation, 
according to the working voltages and temperatures, be used.
If some cables are shielded, the shield must be connected to 
ground at only one side.

D

D

Moreover, check that the parameters set are the de-
sired ones and the application works correctly

 before 

connecting the outputs to the actuators

 in order to 

avoid malfunctions in the plant that could cause dam-
age to people, things or animals.

4.3.1 

Electrical connection diagram

Out1 16 (9)A  10 (4)A  12A Res.

30   LRA

  

 5   FLA

Out2  5 (1)A  2 (1)A  2A   Gen. Use
(12 A max. for ext. conn. models)

SSR: 12 VDC, 15 mA

61810

EN

60730

EN

UL

External

Buzzer

SUPPLY

OUT1

OUT2

NC

NO

C

NO

C

1 2 3 4 5 6 7 8 9 101112

INPUTS

+

-

+

-

T

X40

RST CNT

Internal

Buzzer

5. OPERATING MODE

5.1 

Display operation

CNT

 LED indicates:

 

Count in progress (flashing);

 

Count stopped before the end (steady on);

 

Count ended/Reset status (off).

After Reset display shows 

0000

 when counting mode is 

UP

 

(

F.Cnt

 = 

uP

) or 

Set time

 value if the count mode is 

DOWN

 

(

F.Cnt

 = 

dn

).

While counting display shows the time that elapses: increas-
ing if 

F.Cnt

 = 

uP

 or decreasing if 

F.Cnt

 = 

dn

.

For functions that require a cycle end (

F.o1t

 = 

1

2

) at the 

end of the count, the display flashes: 

0000

 if 

F.Cnt

 = 

dn

 or 

the 

Set time

 value if 

F.Cnt

 = 

uP

.

5.2 

Operation of the Counting commands

Counting can be enabled and disabled using the 

-Start/

Stop

 key or via the digital inputs 

CNT

 and 

RST

.

The operating mode of the 

-Start/Stop

 key is established 

by parameters 

t.UFt

 and 

I.Fct

, the operating mode of 

CNT

 

input is established by 

i.Fct

 parameter while the 

RST

 input 

always acts as a 

Reset

, i.e. 

blocks 

and 

resets

 the count 

when it is activated and also has priority over the other com-
mands (while 

RST

 is active, the count cannot start).

The counting 

Start

 signal can therefore be given by the  

-Start/Stop

 key, which normally has bistable (toggle) 

operation, or via the 

CNT

 count enable digital input.

The operating mode of  the 

CNT

 input can be programmed 

using the 

i.Fct

 parameter to operate in different modes:

i.Fct

 = 

1

 - 

Bistable Start/Stop

By activating the 

CNT

 input the count starts and it is 

therefore possible to deactivate the input.
Activating 

CNT

 again, the count stops on the value reached 

(without disabling the output if this was activated), the next 

CNT

 impulse resumes the count from the point it stopped 

and so on until the end of the count or the 

Reset

 signal.

In this mode, the front 

-Start/Stop

 button (if 

t.UFt

 = 

2

acts exactly in the same way as the 

CNT

 input with the 

addition that, when kept pressed for 2 s during the count-
ing, carries out the 

Reset

 command.

If the counting is finished, pressing the key carries out 
the 

Reset-Start

 command at the same time.

CNT

Count

RESET

0 . 1 . 2 . 3 . 4 . 5

. 6 . 7 . 8 . 0

i.fct

 = 

1

Start

Stop

Start

Stop/

Reset

ELETTROMECCANICA CDC S.r.l - TX40

 

- MANUAL rev.2 - PAG.

5

Nota: attenzione schema collegamento,

        new pin input e output. 

Summary of Contents for TX40

Page 1: ...r external buzzer for signaling the end of the count The 4 digits display normally shows the counting status while the outputs status is signalled by 2 LEDs The instru ment has also 2 digital inputs for voltage free contacts that can be used for the count enabling CNT EN and Reset RES commands and can have up to 2 relay outputs or SSR for driving Solid State Relays The instrument is programmed by ...

Page 2: ... short key if pressed and released the key has no effect 1 Only s t1 Set Time value can be set with this procedure 2 Only s t2 Set Time value can be set with this procedure 3 s t1 and s t2 Set Times can be set with this procedure 4 Only s t3 Set Time value can be set with this procedure 5 s t1 and s t3 Set Times can be set with this procedure 6 s t2 and s t3 Set Times can be set with this procedur...

Page 3: ... without password unprotected To change the parameter visibility press the key and keeping it pressed press also the button The SET LED changes its state indicating the new level of parameter accessibility ON Not protected Flashing Password protected In case some parameters are set as Not protected access ing the programming mode the display first shows the Not protected parameters then the r p pa...

Page 4: ...To obtain the declared protection degree IP65 use screw type bracket optional Avoid placing the instrument in dirty environments or with very high humidity levels that may create condensation and avoid the introduction of conductive substances into the instrument Ensure adequate ventilation to the instrument and avoid installation in containers that house devices which may overheat or which may ca...

Page 5: ...fore the end steady on Count ended Reset status off After Reset display shows 0000 when counting mode is UP F Cnt uP or Set time value if the count mode is DOWN F Cnt dn While counting display shows the time that elapses increas ing if F Cnt uP or decreasing if F Cnt dn For functions that require a cycle end F o1t 1 2 at the end of the count the display flashes 0000 if F Cnt dn or the Set time val...

Page 6: ...Ft is different from oF only acts as a Reset CNT Count RESET 0 1 2 3 i fct 4 Reset Start Reset Start Stop 0 1 2 3 0 1 2 3 0 Stop Reset i Fct 5 Bistable Reset Start Stop At 1st CNT impulse the timer is reset at the 2nd the count starts at the 3rd impulse the count stops disabling the output if active and so on In this mode the front Start Stop button if t UFt 2 acts in exactly the same way as the C...

Page 7: ...in 5 different modes with F o2t parameter Se si desidera utilizzare OUT2 è possibile stabilirne il funzi onamento tramite il parametro F o2t secondo 5 diversi modi F o2t oF OUT2 Output disabled F o2t 1 OUT2 works like OUT1 OUT2 output operates exactly like OUT1 output in order to have a double output contact F o2t 2 OUT2 output works as an instant contact ON during count OUT2 is activated during t...

Page 8: ...peration The internal buzzer can be programmed using the F buF parameter to operate in the following ways oF Internal buzzer disabled 1 Activated at end of S t1 time for S t2 period sound also when keys are pressed If Reset command is given with key or digital input the buzzer is silenced immediately This mode is only active for operations that normally do not involve the use of the S t2 time this...

Page 9: ...tput operating mode oF No function 1 Out2 operates as Out1 2 Instantaneous Contact Output ON during count 3 Out2 operates as Out1 but with absolute Set time s t3 4 Out2 operates as Out1 but with relative Set time s t3 in advance 5 Out2 operates as the buzzer oF 13 F Cnt Count mode uP UP dn DOWN uP 14 F buF Buzzer operating mode oF Disable 1 Sounds at end of the cycle for the s t2 period key pressu...

Page 10: ...er supply and relay outputs and front panel Reinforced insulation between low voltage parts H or L type power supply and outputs if both are relays and the extra low voltage parts inputs Reinforced insulation between power supply and relay outputs Basic insulation between relay outputs and between relay and SSR drive output Basic insulation between H or L type power supply and inputs when a relay ...

Page 11: ...Codice d ordine T X 4 0 H I R R 1 0 Y Y P ZZ Relè Relay R Statica Static S YY OLP 3RZHU 9DF GF OLP 3RZHU 9DF H Morsettiera estraibile Removable screw terminal M Faston Faston F 0 I Terminali a vite Screw terminal Buzzer With buzzer B No buzzer Not buzzer 0 ...

Reviews: