THRESHOLD VALUE FOR BREAK-DOWN ALARM
(available only if HCEn = On)
Upper Display
Hbd
Lower Display
Actual Value (A)
Range
0
↔
FULL SCALE (see HCHS)
Note
•
When the output that is added to the current transformer is in excited state of relays, the
instrument measures the current absorbed by the load and generates an alarm if the current is
below the value of Hbd parameter (a low current indicates a break-down partial or full load).
•
The resolution of the threshold value is equal to 0.1A for range up to 20A, 1A to 20A to 100A
range.
HYSTERESIS VALUE FOR BREAK-DOWN ALARM
(available only if HCEn = On)
Upper Display
HbdH
Lower Display
Actual Value
Range
0
↔
1.0
THRESHOLD VALUE FOR SHORT CIRCUIT ALARM
(available only if HCEn = On )
Upper Display
SCA
Lower Display
Actual Value (A)
Range
0
↔
FULL SCALE (see HCHS)
Note
•
When OUT1 relay is in unexcited state, the instrument measures the leakage current in the load and
generates an alarm if the current exceeds the value of the parameter SCA (a high current indicates a
partial break or total of the relay or SSR).
•
The resolution of the threshold value is equal to 0.1A for range up to 20A, 1A to 20A to 100A range.