REVO S
1PH from 300A to 800A
User’s manual
23
M2
M1
+24V
GND
L1
T1
L1
L2/N
L1
L2/N
1
*
2
Relay
Thermal or
SC/HB/CL
Analog Inp.1
0-10VDC /4-20mA
ANALOG SET POINT
Branch Circuit
Protection
LOAD
Fan Power Supply
See order code for the value
AUX Voltage Supply
See order code for the value
SLAVE OUT
*
2
CT Output only for “Y” option
Note:
Aux Voltage and Load Voltage
must be synchronized
5.7.1 SSR Control Input schematic
For SSR input use follow the schematic below and configure Digital Input 1 as Fast Enable.
5.8 Connection Diagram for Single-phase
Caution:
this procedure must be performed only by qualified persons.
M1
9
6
5
13
12
11
10
Analog Input 1
SSR
INPUT
X = not connected
*1 The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator.
The Fuse must be branch circuit protection. For UL any listed UL branch circuit fuse would be accettable as an external
fuse, following national electric code guide for resistive heating of 125% load current rating to protect external wires.
*SSR Input:
4÷30Vdc 5mA Max (ON >4Vdc / OFF <1Vdc)
Frequency 3Hz Max - On time min. 100 ms