REVEX
2PH 280A
User’s manual
33
Parameter Name
Description
Default
Modbus
Address
Par.
Type
DI1 Functn
Choose how the signal detected by digital input 1
is used
2
32
Read
Write
Option
Description
Value
Enable
Enable power output
0
V Feedback
Use voltage feed-back when on
2
Local / Rmt
Local when on / Remote when off
3
SP AI1/AI2
Select remote set point source: analog input 1 when off or analog input 2 when on
5
FastEn
Fast Enable
8
DEFAULT:
Voltage Feed-back
2
SSR Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 3HZ Max on time min. 100 ms
Parameter Name
Description
Default
Modbus
Address
Par.
Type
DI2 Functn
Choose how the signal detected by digital input 2
is used
0
33
Read
Write
Option
Description
Value
Enable
Enable power output
0
V Feedback
Use voltage feed-back when on
2
Local / Rmt
Local when on / Remote when off
3
SP AI1/AI2
Select remote set point source: analog input 1 when off or analog input 2 when on
5
FastEn
Fast Enable
8
DEFAULT:
Enable
0
SSR Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 3HZ Max on time min. 100 ms
Summary of Contents for M-RX2-280
Page 2: ......