background image

Page 6 of 16 WND-WR-MB-Inst-1.03 

2.2.5  Three-Phase, Four-Wire Wye

This is a common commercial and industrial service that includes a neutral conductor. The CTs 
should be placed around the L1, L2 and L3 line conductors and connected to the 

CT1

CT2

, and 

CT3

 terminals respectively. The meter will be powered from the 

V

N

V

A

, and 

V

B

 terminals.

V

B

V

C

V

N

V

A

W

ATT

N

ODE

®

CT2 CT1

CT3

L3

L2

L1

Neutral

Earth

Figure 6: Three-Phase Four-Wire Wye with Neutral

2.2.6  Grounded Leg Service

In rare cases with delta services or single-phase two-wire, line-to-line services, one of the phases 
may be grounded.

The meter will correctly measure services with a grounded leg, but the measured voltage and power 
for the grounded phase will be zero. The status LEDs will not light for the grounded phase because 
the voltage is near zero. This type of service may result in unusual power factors.

See the web article 

Corner-Grounded Delta Circuits

 for more information.

2.2.7  Four-Wire Delta Service

There are several names for this service type including “high-leg”, “wild-leg”, “stinger leg”, or “wild 
phase”. This is a three-phase delta service with a center-tap on one of the transformer windings 
to create a neutral for single-phase loads. These occur in North America in two configurations: 
120/208/240 Vac and 240/415/480 Vac.

With the WattNode Wide-Range meter, this service type can be measured just like any three-phase, 
four-wire wye service (

Figure 6

) using three CTs. By convention, you should connect the 

V

B

 terminal 

to the high leg. See 

Four-Wire Delta Circuits

 for more information.

3  Installation

3.1  Installation Checklist

See the sections referenced below for installation details.

 

Turn off power

 before making line voltage connections. 

 

Mount the meter (see 

3.2

).

 

Connect circuit breakers or fuses and disconnects (see 

3.3.1

).

 

Connect the line voltage wires to the meter’s green terminal block (see 

3.3.2

).

 

Mount the CTs around the line conductors. Make sure the CTs face the source (see 

3.4

).

 

Connect the twisted white and black wires from the CTs to the black terminal block on the 
meter, matching the wire colors to the white and black dots on the meter label (see 

3.4.2

).

 

Check that the CT phases match the line voltage phases: 

CT1

 with 

V

A

CT2

 with 

V

B

, and 

CT3

 

with 

V

C

, unless you have specially configured the 

ConnectionType

 or 

MeterConfig

 registers 

(see 

3.4

).

 

Record the CT rated current for each CT. They will be required during commissioning.

 

Connect the output terminals of the meter to the monitoring equipment (see 

3.5

).

 

Check that all the wires are securely installed in the terminal blocks by tugging on each wire.

 

Turn on power to the meter.

 

Verify that the LEDs indicate correct operation (see 

4.2

4.3

).

Summary of Contents for WattNode WND-WR-MB

Page 1: ...www ctlsys com WattNode Wide Range Modbus Electric Power Meter Installation Guide Model WND WR MB ...

Page 2: ...als 7 3 4 Connect Current Transformers 7 3 5 RS 485 Communication 8 4 Operation 10 4 1 Initial Configuration 10 4 2 Power Status LEDs 10 4 3 Modbus Communication LED 11 4 4 Monitoring 12 4 5 Maintenance and Repair 12 5 Specifications 12 5 1 Measurement 12 5 2 Electrical 12 5 3 EIA RS 485 Interface 13 5 4 Certifications 13 5 5 Environmental 14 5 6 Mechanical 14 5 7 FCC Information 14 5 8 Warranty 1...

Page 3: ...ck Hazard from Dangerous High Voltage Functional ground should be connected to earth ground if possible but is not re quired for safety grounding UL Listing mark for U S A and Canada FCC Mark This logo indicates compliance with part 15 of the FCC rules Complies with the regulations of the European Union for Product Safety and Electro Magnetic Compatibility Low Voltage Directive EN 61010 1 2010 3rd...

Page 4: ... VN CT2 with VBN and CT3 with VCN This default configuration may be changed using the ConnectionType register or the MeterConfig regis ters See the Reference Manual for details When describing service types the number of wires only includes neutral and line conductors not the ground conductor 2 2 1 Single Phase Two Wire Line to Neutral This is a common residential and branch circuit connection The...

Page 5: ...rican residential service at 120 240 Vac with a neutral connection The CTs should be placed around the L1 and L2 line conductors and connected to the CT1 and CT2 terminals respectively The meter will be powered from the VN VA and VB terminals VB VC VN VA WATTNODE CT2 CT1 CT3 L2 L1 Neutral Earth Figure 4 Single Phase Three Wire 2 2 4 Three Phase Three Wire Delta This service is common in commercial...

Page 6: ... in two configurations 120 208 240 Vac and 240 415 480 Vac With the WattNode Wide Range meter this service type can be measured just like any three phase four wire wye service Figure 6 using three CTs By convention you should connect the VB terminal to the high leg See Four Wire Delta Circuits for more information 3 Installation 3 1 Installation Checklist See the sections referenced below for inst...

Page 7: ... monitoring more than one line voltage The circuit breakers or fuses must protect whichever of the mains terminals VA VB or VC are connected to the mains Neutral does not need overcurrent protection The circuit protection disconnect system must meet IEC 60947 1 and IEC 60947 3 as well as all national and local electrical codes 3 3 2 Line Wiring Always turn off power before connecting the line volt...

Page 8: ...D SOURCE on the CT and face point toward the source of current CTs are directional so if they are mounted backwards or with their white and black wires swapped the measured power will be negative The power status LEDs indicate negative measured power by flashing red Install the CTs around the phase conductors to be measured as shown in Figure 1 through Figure 6 above Connect the CT leads to the me...

Page 9: ...y questions consult the Reference Manual The meter outputs are electrically isolated from dangerous voltages If the output wiring is near line voltage wiring use wires or cables with a 300 V or 600 V rating not less than the service voltage If the output wiring is near bare conductors it should be double insulated or jacketed RS 485 wiring is daisy chained between meters with up to 64 devices per ...

Page 10: ...odbus ParityMode register 4 Operation 4 1 Initial Configuration Generally the network integrator will remotely configure the WattNode meter and the variables For details on configuring the WattNode meter see the appropriate Reference Manual for your model The meter does not include a display or buttons so it is not possible to configure or monitor the meter directly other than the basic LED diagno...

Page 11: ...ollowing indicates that the line voltage is too high for this model Disconnect power immedi ately Check the line voltages and the meter ratings in the white box on the label 1 0sec G R G R G R G R G R G R G R G R G R G R G R G R G R G R G R G R G R G R CT3 CT2 CT1 4 2 7 Meter Not Operating If none of the LEDs light then check that the correct line voltages are applied to the meter If the voltages ...

Page 12: ...ble parts except the pluggable screw terminals There are no diagnostic tests that can be per formed by the user other than checking for errors via the Modbus interface or the status LEDs In the event of any failure the meter must be returned for service contact CCS for an RMA For a new installation follow the troubleshooting instructions in the Reference Manual before returning the meter for servi...

Page 13: ...Voltage Mode Nominal Input Voltage At CT Rated Current 0 33333 Vac RMS Absolute Maximum Input Voltage 5 0 Vac RMS Input Impedance at 50 60 Hz 23 kΩ Current Mode Opt MA Nominal Input Current At CT Rated Current 40 mA RMS Absolute Maximum Input Current 200 mA RMS Input Impedance at 50 60 Hz 10 Ω 5 3 EIA RS 485 Interface RS 485 Output Isolation 4500 Vac RMS Driver Output Voltage Open Circuit 6 Vdc ma...

Page 14: ...Outdoor Use Suitable for outdoor use if mounted inside an electrical enclosure Hammond Mfg Type EJ Series rated NEMA 3R or 4 IP 66 5 6 Mechanical Enclosure High impact ABS PC plastic Flame Resistance Rating UL 94V 0 IEC FV 0 Size 6 02 in 3 35 in 1 50 in 153 mm 85 mm 38 mm Connectors Euroblock pluggable terminal blocks Green up to 12 AWG 2 5 mm2 600 V screw torque 3 5 lbf in 0 4 N m Black up to 12 ...

Page 15: ...rantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment ...

Page 16: ... nature lightning product modifications alterations or repairs by anyone other than CCS Except as set forth herein CCS makes no warranties expressed or implied and CCS dis claims and negates all other warranties including without limitation implied warranties of merchantability and fitness for a particular purpose 5 9 Limitation of Liability In no event shall CCS be liable for any indirect special...

Reviews: