background image

LCDA-P Power Display

 

1

Continental Control Systems

 LLC

Application Note: AN-116

July 2008

LCDA-P Power Display

Overview

The power display has eight digits with an adjustable scale factor and decimal point posi-
tion, to allow for the accurate display of power levels from tenths of a watt to megawatts. 
The power display is self-powered for use with the Advanced Pulse WattNode models with 
an output frequency up to 20Hz. For Advanced Pulse WattNode models with an output fre-
quency greater than 20Hz an external DC power supply and pull-up resistor are required. 

Wiring

Low Pulse Frequency (up to 20Hz) 

Connect the WattNode’s ‘P1’ terminal of the output to the IN B (Terminal 2) on the LCD 
display. Connect the WattNode’s ‘COM’ terminal of the output to the GND (Terminal 1) on 
the LCD display.

P1

P2

P3

COM

A  CT

O

 /

B  CT

O

 /

C  CT

O

 /

tu

pt

u

O

B

O

 /

C

O

 /

Status

Status

Status

W

ATT

N

ODE

®

WNB-3Y-208-P

N

A

O

 /

5 Enable/R

RST 4

IN A 3

IN B 2

GND 1

6 DC Common

7 +10-30VDC

LCDA-P Low Pulse Frequency Wiring Diagram

Figure 1: 

High Pulse Frequency (greater than 20Hz)

Connect the WattNode’s ‘P1’ terminal of the output to the IN A (Terminal 3) on the LCD 
display. Connect the WattNode’s ‘COM’ terminal of the output to the GND (Terminal 1) on 
the LCD display. Add a pull-up resistor on the P1 line as shown below. See 

Table 1

 below 

for recommended pull-up resistor values.

P1

P2

P3

COM

A  CT

O

 /

B  CT

O

 /

C  CT

O

 /

tu

pt

u

O

B

O

 /

C

O

 /

Status

Status

Status

W

ATT

N

ODE

®

WNB-3Y-208-P

N

A

O

 /

5 Enable/R

RST 4

IN A 3

IN B 2

GND 1

6 DC Common

7 +10-30VDC

+5V to +28Vdc

Resistor values

See Table 1

LCDA-P High Pulse Frequency Wiring Diagram

Figure 2: 