background image

For more information on this product, please contact:

PC&S, Inc. at +1 (800) 523-9194 or +1 (973) 448-9400

www.pc-s.com

Battery Charger

SM82

A

Switchmode range of chargers

High Rate Float Charging

5A @ 6/12 - 3A @ 24V - 1.5A @ 48V

 

Auto 3 Stage Operation

Full LED Output Indication

A two year limited warranty on materials and workmanship is 
given with this product. Details are available upon request.

Power Supply:

 

 

General

:

operating temperature 
overall dimensions (w x h x d) 

Current Limited

95-135 and 195-277VAC

(switchable)

50/60Hz

DC Charge Output:

Output current ADC

Nominal voltage VDC

Line regulation

Load regulation

5        5          3          1.5

6       12        24          48

< 1%

-20 C to +60 C

°

°

0.56Kg (1.24lbs)

weight

Product Specification

Safety

Warranty

Low Ripple (<1%)

 

Float, bulk and charge fail outputs

VRLA and Vented Lead Acid

 

Nominal operating voltages

Nominal operating frequency

This  battery  charger  is  designed  for
Use with Lead Acid or VRLA battery packs.

Batteries  can  be  dangerous,  do  not  place  metallic 
objects  across  the  terminals  of  a  battery  or  battery 
pack.  When  handling  batteries  remove  all  loose 
jewellery, watches and rings. Take care not to place 
tools  across  the  terminals.  Only  specified  types  of 
batteries  should  be  used  with  this  unit  as  charging 
others may cause damage and result in serious injury.

Before using this unit, ensure the following: -

Unit is physically checked, in event of any damage to 
unit please return to supplier.
AC Voltage is correctly selected where appropriate.
Read and follow the “How To Use” guidelines in this 
instruction document.
It is recommended that when using the SM82 battery 
charger,  the  battery  packs  should  be  at  ambient 
temperature (20deg C) before starting charge.
Consult Table (A) to determine whether to use float 
mode  (with  manual  boost  option)  or  Auto-3  Stage 
mode.

Load regulation

< 1%

Output ripple

< 1%

Charging settings

EN61000-6-2 / EN61000-6-4

EMC emmision / immunity

Table (A) - Charging mode selection guide

FEATURES:

Or Optional Manual Boost Mode

134mm x 140mm x 85mm

(5.3” x 5.5” x 3.6”)

7.2

6.9

14.5

13.8

29.0      58.0

27.6      55.4

Float VDC
Boost VDC

Charge Fail / Loss of AC Relay

Charge Fail Relay Output:

Relay type

Contact rating

Volt free SPDT contacts

relay de-energises on fault

1A @ 30VDC

<350mA

Auto-3 Stage

>350mA

Float

<200mA

Auto-3 Stage

>200mA

Float

<100mA

Auto-3 Stage

>100mA

Float

24

48

Note: Auto-3 Stage Operation is controlled by output current of the charger, this 
determines whether charger goes into an increased 'boost' voltage mode, 
continous charging at this voltage causes gassing of batteries and shortens 
both AH capacity and life, having a continous (standing load) above this level 
whilst in the Auto-3 Stage Mode will cause the charger to be in a continous 
'boost' mode.

Nominal 

VDC

Standing Load 

(Continous Current) 

ADC

Mode Of Operation Best 

Suited

6/12

Note: The SM82A is supplied without LED indication on the front