3.0 Closing/Opening Operation 

 

DANGER! 

Ensure  that  all  applicable  interlocks  are  defeated  before  beginning  any  remote  switching 
operation  on  the  switchgear.    Failure  to  do  so  will  damage  interlocks,  switchgear,  and/or 
RSA.    Please  follow  all  applicable  operation  instructions  and  take  necessary  precautions  as 
stated in the switchgear operation manual. 

 

1.

 

Ensure that the switch is fully charged as outlined in the previous section. 

 

2.

 

Next, pull the spring-loaded shaft outward using the T-handle on the backside of 
the shaft to disengage the tooling from the switching mechanism and bypass the 
interlock.  With the shaft disengaged, rotate it slightly to ensure that when it is 
released it will not engage the switching mechanism. 

 

3.

 

On the RSA-138 Interface Module, switch the two position switch to the setting 
labeled “Open/Close Actuator.” 

 

4.

 

Power on the RSO-I AR and ensure that the AR function is “ON.” 

 

5.

 

To  perform  the  applicable  opening  or  closing  operation  press  and  hold  the 
“CLOSE”  button  to  extend  the  linear  actuator  and  engage  the  opening/closing 
lever located above the shaft.  The actuator will automatically retract when the 
“CLOSE” button is released. 

 
 

ATTENTION! 

Please note that even if the desired effect is to open the switch, the “CLOSE” button must still 
be pressed on the RSO-I AR.  Because of this misnomer, operators must be aware of the 
actions being performed on the switch. 