2.6.8 J6 Speed Inputs
If the application is a generator, the speed inputs on connector J6 are optional as the AC Voltage sensing inputs
can be used to sense speed via the frequency.
The speed inputs are rated to a maximum of 50 VAC.
Magnetic Pickup Sensor
These items must be followed:
•
The sensor must be of a shielded type
•
A twisted pair shielded cable must be used for the connection
•
The shield must be connected to ground on one side only
•
One side of the sensor must be grounded in addition to connecting to the controller. Not grounding one
side of the sensor can cause erratic behavior
The first three requirements in this list can be ignored at the customer
’s own risk, but the fourth requirement must
be followed; otherwise, unreliable operation may result.
The polarity of the speed inputs does not matter.
Other Speed Signal Sources
Other speed sources such as those from an alternator or tachometer can be used but note that these are often
very noisy and must be filtered before connecting to the speed inputs. Filtering means must be provided by the
installer if required. The installer must determine the suitability for their application. Cattron does not provide any
means of filtering and cannot guarantee compatibility.
Summary of Contents for DYNAGEN TOUGH Series TE410
Page 1: ...TOUGH SeriesTM TE410 User Manual ...
Page 22: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 22 9M02 9249 A001 EN Revision A CT Wiring ...
Page 24: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 24 9M02 9249 A001 EN Revision A ...
Page 28: ...DynaGenTM TOUGH SeriesTM TE410 EN User Manual 28 9M02 9249 A001 EN Revision A ...