background image

2

IOM-8310HP/LP-BASIC

SECTION III

III.  PRINCIPLE OF OPERATION

1.  Movement occurs as pressure variations register on the 

diaphragm.  The registering pressure is the outlet P

2

or downstream pressure.  The range spring opposes 

diaphragm movement.  As outlet pressure drops, the 

range  spring  pushes  the  diaphragm  down,  opening 

the ports; as outlet pressure increases, the diaphragm 

pushes up and the port opening closes.

2.  A complete diaphragm failure will cause the regulator 

to fail open.

IV.  START-UP

1.  Start with the block valves closed.  A bypass valve may 

be used to maintain outlet pressure in the downstream 

system without changing the following steps.

2.  Relax the range spring by turning the adjusting screw 

counter clockwise (CCW) (viewed from above)  a min-

imum  of  three  (3)  full  revolutions.    This  reduces  the 

outlet (downstream) pressure setpoint.

3.  If it is a “hot” piping system, and equipped with a by-

pass valve, slowly open the bypass valve to preheat 

the system piping and to allow slow expansion of the 

piping.  Ensure proper steam trap operation, if installed.  

Closely monitor outlet (downstream) pressure via gauge 

to ensure not over-pressurizing.  

NOTE:  If no bypass 

valve is installed, extra caution should be used in start-

ing up a cold system; i.e. do everything slowly.

4.  Crack open the outlet (downstream) block valve.

5.  Slowly open the inlet (upstream) block valve observing 

the outlet (downstream) pressure gauge.  Determine if 

the regulator is flowing.  If not, slowly rotate the regulator 

adjusting screw clockwise (CW) (viewed from above) 

until flow begins.

6.  Continue to slowly open the inlet (upstream) block valve 

until fully open.

SECTION V

V.  SHUTDOWN

1.  On systems with a bypass valve, and where system 

pressure is to be maintained as the regulator is shut 

down, slowly open the bypass valve while closing the inlet 

(upstream) block valve.  Fully close the inlet (upstream) 

block valve.  (When on bypass, the system pressure 

must be constantly observed and manually regulated.)  

Close the outlet (downstream) block valve.

Do  not  walk  away  and  leave  a  bypassed  regulator 

unattended!

2.  If the regulator and system are to both be shutdown, 

slowly close the inlet (upstream) block valve.  Close the 

outlet (downstream) valve only if regulator removal is 

required.

7.  Continue to slowly open the outlet (downstream) block 

valve, especially when the downstream piping system 

isn’t pressurized.  If the outlet (downstream) pressure 

exceeds the desired pressure, close the block valve 

and go to Step 2, then return to Step 4.

8.  When flow is established steady enough that the outlet 

(downstream) block valve is fully open, begin to slowly 

close the bypass valve, if installed.  

NOTE:  The needle 

valve (39) is shipped in a full open position.  If the system 

is unstable due to pressure fluctuations, slowly close 

the needle valve (39) until the system becomes stable.  

This needle valve (39) should never be in a fully closed 

position.

9.  Develop system flow to a level near its expected normal 

rate,  and  reset  the  regulator  setpoint  by  turning  the 

adjusting screw CW (viewed from above) to increase 

outlet pressure, or CCW to reduce outlet pressure.

10.  Reduce system flow to a minimum level and observe 

setpoint.    Outlet  pressure  will  rise  from  the  setpoint 

of  Step  9.    The  maximum  rise  in  outlet  pressure  on 

decreasing flow should not exceed the stated upper 

limit of the range spring by greater than 10%; i.e. 10-40 

psig (.69-2.8 Barg) range spring, at low flow the outlet 

pressure should not exceed 44 psig (3 Barg).  If it does, 

consult factory.

SECTION IV

 

CAUTION C

DO  NOT  HYDROSTATIC  TEST  THRU  AN  INSTALLED 

UNIT; ISOLATE REGULATOR FROM TEST.  The upper 

range spring pressure level listed on the nameplate is 

the recommended “upper operative limit” for the sensing 

diaphragm (see Section IV. Start-up, Number 7.)  Higher 

pressures could cause internal damage. In addition, note 

on the nameplate that the Inlet and Outlet pressure and 

temperature ratings are at different levels.

10.  Basic Regulator - (Refer to Figure 1):  Regulator may 

be rotated around the pipe axis 360°.  Recommended 

position is with spring chamber vertical upwards.  Orient 

such that the spring chamber vent hole does not collect 

rainwater or debris.

11.  Regulators are not to be direct buried underground.

12.  For insulated piping systems, recommendation is to not 

insulate regulator.

CAUTION D

Summary of Contents for 8310HP

Page 1: ...orizontal pipe properly trapped if a steam service application Recommended Piping Schematic For Pressure Reducing Station CAUTION B Installation of adequate overpressure protection is recommended to protect the regulator and all downstream equipment from damage in the event of regulator failure 1 An inlet block valve should always be installed 2 If service application is continuous such that shut ...

Page 2: ...attended 2 If the regulator and system are to both be shutdown slowly close the inlet upstream block valve Close the outlet downstream valve only if regulator removal is required 7 Continue to slowly open the outlet downstream block valve especially when the downstream piping system isn t pressurized If the outlet downstream pressure exceeds the desired pressure close the block valve and go to Ste...

Page 3: ...tall new diaphragm gasket 21 on diaphragm case 14 flange and new pusher plate gasket 18 on pusher plate if required NOTE No gaskets utilized with a composition soft diaphragm 11 Position new diaphragm s 20 over threaded end of valve plug assembly 12 12 Ensuring that the curved outer rim side of the pres sure plate 22 rests against the diaphragm s 20 directly placethepressureplate 22 overthreaded e...

Page 4: ...leastmid rangespringlevel i e 10 40psig 69 2 8 Barg rangespring 25psig 1 7Barg testpressure minimum C Trim Inspection 1 To inspect the internal trim parts refer to Section VI A andB 1through9fordiaphragmreplacement and proceed as follows 2 Secure the flats on the threaded end of the valve plug assembly 12 with adjustable wrench and remove pusher plate 17 and stem lock nut 19 by rotating CCW viewed...

Page 5: ... Contact factory Remedies Possible Causes 5 Sluggish operation A Regulator not closing tightly A Inspect trim and plug alignment B Downstream block B Check system isolate block flow at regulator inlet not outlet Relocate regulator if necessary C No pressure relief protection C Install safety relief valve or rupture disc D Restricted diaphragm movement D Ensure no moisture in spring chamber at temp...

Page 6: ... REPAIR Contact your local Cashco Inc Sales Representative with the Serial Number and Product code Identify the parts and the quantity required to repair the unit from the Bill of Materials sheet that was provided when unit was originally shipped NOTE Those part numbers that have a quantity indicated un der Spare Parts in column A reflect minimum parts required for inspection and rebuild Soft Good...

Page 7: ...7 IOM 8310HP LP BASIC NOTES ...

Page 8: ...te Nut 25 Diaphragm Ring 27 Spring Button 28 Range Spring 29 Flange Bolt 30 Flange Nut 31 Nameplate 32 Adjusting Screw or Handwheel Assy 33 Adjusting Screw Lock nut or Lever 34 Seal Washer 35 Closing Cap 36 Closing Cap Gasket 37 Bleeder Valve 38 Pipe Nipple 39 Needle Valve 40 Spring 41 Diaphragm Case Nut 42 Flush Bushing 43 Pipe Plug 51 Pipe Nipple Not Shown 44 Pipe Nipple 45 Elbow 54 Drive Screw ...

Reviews: