background image

relatively loud click).   

To increase the delay time, adjust the potentiometer marked “A” clockwise.  After the floodlight relay times 

out, repeat the cycle until the desired time is achieved.  Re-connect the photocell wire to terminal No. 7. 

special note:  

Do not use the MANUAL-ON button on the FC-9 annunciator plate to set the entry delay 

time.  On the CF-2C (Issue 5), the MANUAL-ON button on the FC-9 instantly activates the floodlight 
timer, bypassing the entry delay timer circuit. 

 A

DJUSTING

 F

LOODLIGHT

 T

IME

 

See Figure 5. The amount of time the floodlights remain on after the system is tripped may be adjusted from 

15 seconds to 15 minutes. The normal floodlight time is 5-10 minutes.  

To set the floodlight time, remove the photocell wire from terminal No. 7. Push the TRIP-TEST button. 

Measure from the moment the floodlight relay clicks on to the moment it clicks off. Adjust potentiometer 
"B" (clockwise for time increase) and repeat until desired time is achieved. Reconnect the photocell wire to 
terminal No. 7. 

A

DJUSTING

 P

HOTOCELL

 S

ENSITIVITY

 

See Figure 5.  Photocell sensitivity determines the level of outdoor light at which the lights are allowed to 

come on. The factory sets the floodlights to come on at dusk.  

To set the photocell sensitivity, make all adjustments at the precise moment when the amount of daylight is 

visible at which time you want the floodlights to come on. Adjust potentiometer "D" counter clockwise in very 
small increments and push the TRIP-TEST button after each adjustment (see page 5). Stop adjusting at the 
point where the floodlight relay clicks on.  The floodlights will be allowed to turn on at that same daylight level 
from then on.  

A

DJUSTING

 P

ROBE

 S

ENSITIVITY

 

See Figure 5. Probe sensitivity is set at the factory and does not usually need to be adjusted. Factory setting 

allows a single standard probe to cover a 12 foot wide driveway when installed beside it). Increasing the 
sensitivity above the factory setting is not recommended unless the probe is located in a low sensitivity area.  

When the probe is placed in the center of a driveway that is 18 feet wide or less, the sensitivity may be 

decreased considerably, allowing the probe to be installed close to highway traffic, power lines, etc. 

To adjust probe sensitivity, turn the potentiometer "G" clockwise to increase, counter-clockwise to decrease.  

A typical setting should be such that the CF-2C reliably detects a small car going 5 MPH.  You may increase 
sensitivity if necessary.  Be aware, increasing sensitivity may cause false alarms.  

A

DJUSTING

 T

RANSIENT

 S

UPPRESSOR

 

See Figure 5.  The factory setting for the transient suppressor circuit potentiometer "H" is in the "on" position 

(fully clockwise). In this setting, short duration transient signals will be ignored. With the circuit activated, false 
alarms from lightning will be reduced. 

Note: if the probe sensitivity cannot be properly set as described in the "Adjusting Probe Sensitivity" section 

above, turn off the transient suppressor by adjusting potentiometer "H" full counter-clockwise.  

F

IELD

 T

ROUBLESHOOTING

  

Preferred does not provide schematic diagrams or service manuals for our products. However, we try our 

best to provide technical support through our 800 number and fast repair service for our products. 

Before calling Preferred, refer to the “

Special Note

” sections under the following headings: 

Š

Initial power-up and exit delay, page 4; 

Š

 Purchasing ground rod, page 5;  

Š

 Using Probe Fault Mode to

test circuit board, page 5; 

Š

 Entry delay time, p. 7. 

When trouble-shooting a CF-2C system that is false alarming, check the ground system.  House electrical 

panel grounds can cause transient feedback that could cause false alarms. 

To determine if false alarms are board related or probe system related, disconnect the probe and connect a 

Back to Table of Contents 

Back to Table of Contents 

Back to Table of Contents 

Back to Table of Contents 

Back to Table of Contents 

www.GateOpenerSafety.com  |  (800) 878-7829  |  [email protected]

Summary of Contents for CF-2C

Page 1: ...CF 2C CF 3C CONTROL UNIT ONLY Sound Lights INSTALLATION OPERATION MANUAL www GateOpenerSafety com 800 878 7829 sales GateOpenerSafety com...

Page 2: ...sting CT A1 formerly FC 9 Exit Delay 6 Adjusting Sounder Annunciator Time 6 Adjusting Re Trigger Hold Off 6 Adjusting Floodlight Entry Delay Time 6 Adjusting Floodlight Time 7 Adjusting Photocell Sens...

Page 3: ...of box when installed outside The weatherproof box must have a thermostatically controlled light bulb or heater to maintain temperatures above freezing Drastic changes in temperature cause condensatio...

Page 4: ...asonic Industries Co or G S Battery Inc The positive RED lead connected to terminal No 4 and the negative BLACK lead connected to terminal No 5 are provided for connections to the battery When an outs...

Page 5: ...UTOMATION PANEL See Figure 2 on page 2 The CF 2C has a floating dry relay contact that can be used in conjunction with any security or home automation H A system Two things will help you to have a suc...

Page 6: ...witch to hear your adjustment Adjust until the desired time is achieved ADJUSTING RE TRIGGER HOLD OFF See Figure 5 The re trigger hold off keeps the system from re triggering and thus annunciating sho...

Page 7: ...beside it Increasing the sensitivity above the factory setting is not recommended unless the probe is located in a low sensitivity area When the probe is placed in the center of a driveway that is 18...

Page 8: ...llation abuse fire and water damage electrical surges and damage to cable caused by slicing pulling tangling or improper splicing For more information visit www cartell com MERCHANDISE RETURN INFORMAT...

Reviews: