
22
COMPRESSORS
Lubrication
Compressors are charged with the correct amount of oil at the
factory.
Replacing the Compressor
The compressor using Puron
®
refrigerant contains a POE oil.
This oil has a high affinity for moisture. Do not remove the
compressor’s tube plugs until ready to insert the unit suction
and discharge tube line ends.
NOTE: Only factory-trained service technicians should remove
and replace compressor units.
COMPRESSOR MOUNTING BOLTS
Compressor mounting bolts should be periodically inspected
for proper tightness. Bolts should be tightened and have the
torque set at 65 to 75 in.-lb (7.3 to 8.5 Nm).
COMPRESSOR ROTATION
On 3-phase units with scroll compressors, it is important to be
certain compressor is rotating in the proper direction. To deter-
mine whether the compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
NOTE: If the suction pressure does not drop and the discharge
pressure does not rise to normal levels.
4. Note that the evaporator fan is probably also rotating in
the wrong direction.
5. Turn off power to the unit. Use applicable lockout/tag-out
procedures.
6. Reverse any two of the unit power leads.
7. Reapply power to the compressor.
The suction and discharge pressure levels should now move to
their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes an elevated level of noise and does not provide
cooling.
Filter Drier
Replace the filter drier whenever refrigerant system is exposed
to atmosphere. Only use factory specified liquid-line filter dri-
ers with working pressures no less than 650 psig (4482 kPa).
Do not install a suction-line filter drier in a liquid line. A liq-
uid-line filter drier is designed for use with Puron (R-410A) re-
frigerant and is required on every unit.
REPLACING THE FILTER DRIER
Use the following steps to replace the filter drier.
1. Using Puron (R-410A) gage set, recover all refrigerant
from system.
2. Use tubing cutter to remove filter drier from line.
NOTE: Do not use a torch to remove old filter drier. The heat from
the torch will allow contaminants into the air and into the open re-
frigeration system.
3. Sweat a new replacement filter drier into refrigerant line.
4. Re-charge refrigerant system.
Adjusting the Condenser-Fan
1. Shut off unit power supply. Apply appropriate lockout/tag-
out procedures.
2. Remove condenser-fan assembly (grille, motor, and fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 26.
5. Tighten setscrews to 84 in.-lb (9.5 Nm).
6. Replace condenser-fan assembly.
Fig. 26 — Condenser Fan Adjustment
TROUBLESHOOTING COOLING SYSTEM
Troubleshooting Cooling System
Refer to Table 5 for Troubleshooting Cooling System topics.
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in death, serious
personal injury and/or property damage.
Never use air or gases containing oxygen for leak testing or
for operating refrigerant compressors. Pressurized mixtures
of air or gases containing oxygen can lead to an explosion.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could cause personal injury
or death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from refriger-
ants and oils.
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in death, serious
personal injury and/or property damage.
Never use non-certified refrigerants in this product. Non-
certified refrigerants could contain contaminates that could
lead to unsafe operating conditions. Use ONLY refrigerants
that conform to AHRI Standard 700.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to
components.
The compressor is in a Puron
®
refrigerant system and uses a
polyolester (POE) oil. This oil is extremely hygroscopic,
meaning it absorbs water readily. POE oils can absorb 15
times as much water as other oils designed for HCFC and CFC
refrigerants. Avoid exposure of the oil to the atmosphere.
Summary of Contents for WeatherMaster Puron 48HC D17
Page 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Page 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Page 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Page 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Page 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Page 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Page 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Page 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Page 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Page 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Page 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Page 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Page 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Page 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Page 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Page 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Page 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Page 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Page 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Page 97: ......