
15
Fig. 19 — Thermostatic Expansion Valve (TXV)
Operation
TXV Operation
The TXV is a metering device that is used in air conditioning
and heat pump systems to adjust to the changing load condi-
tions by maintaining a preset superheat temperature at the out-
let of the evaporator coil. See Fig. 20.
The volume of refrigerant metered through the valve seat is de-
pendent upon the following:
1. Superheat temperature is sensed by the cap tube sensing
bulb on suction the tube at the outlet of evaporator coil.
This temperature is converted into pressure by refrigerant
in the bulb pushing downward on the diaphragm which
opens the valve using the push rods.
2. The suction pressure at the outlet of the evaporator coil is
transferred through the external equalizer tube to the
underside of the diaphragm.
3. The needle valve on the pin carrier is spring loaded, exert-
ing pressure on the underside of the diaphragm. Therefore,
the bulb pressure equals the evaporator pressure (at the
outlet of the coil) plus the spring pressure. If the evapora-
tor load increases, the temperature increases at the bulb,
which increases the pressure on the topside of the dia-
phragm, pushing the carrier away from the seat, opening
the valve and increasing the flow of refrigerant. The
increased refrigerant flow causes increased leaving evapo-
rator pressure which is transferred through the equalizer
tube to the underside of the diaphragm. This causes the pin
carrier spring pressure to close the TXV valve. The refrig-
erant flow is effectively stabilized to the load demand with
a negligible change in superheat.
Fig. 20 — TXV Sensor Bulb Location
OUTLET
INLET
PUSHRODS
DIAPHRAGM
NEEDLE
VALVE
SPRING
DISTRIBUTOR
FEEDER TUBES
CAPILLARY TUBE
COIL
BULB
EXTERNAL EQUALIZER TUBE
TXV SENSOR
BULB
CLAMP
CIRCUIT 1
CIRCUIT 2
TXV
(CIRCUIT 2)
TXV
(CIRCUIT 1)
TXV SENSOR
BULBS
TXV
SENSOR
BULBS
Summary of Contents for WeatherMaster Puron 48HC D17
Page 18: ...18 COOLING CHARGING CHARTS Fig 22 Cooling Charging Chart 15 Ton ...
Page 19: ...19 Fig 23 Cooling Charging Chart 17 5 Ton ...
Page 20: ...20 Fig 24 Cooling Charging Chart 20 Ton ...
Page 21: ...21 Fig 25 Cooling Charging Chart 25 Ton ...
Page 37: ...37 Fig 48 Unit Control Box IGC Location IGC Board IGC Board Side view Front view ...
Page 40: ...40 Fig 51 Typical IGC Wiring Diagram ...
Page 46: ...46 Fig 57 RTU Open Overlay for Economizer Wiring ...
Page 47: ...47 Fig 58 VFD Overlay for W2770 Controller Wiring ...
Page 84: ...84 Fig B 48HC D17 D28 Control Diagram 208 230 3 60 460 575 3 60 ...
Page 85: ...85 Fig C 48HC D17 D28 Power Diagram 208 230 3 60 ...
Page 86: ...86 Fig D 48HC D17 D28 Power Diagram 460 3 60 ...
Page 87: ...87 Fig E 48HC D17 D28 Power Diagram 575 3 60 ...
Page 88: ...88 Fig F 48HC D17 D28 Control Diagram with Humidi MiZer System ...
Page 89: ...89 Fig G 48HC D17 D28 Power Diagram 208 230 3 60 with Humidi MiZer System ...
Page 90: ...90 Fig H 48HC D17 D28 Power Diagram 460 3 60 with Humidi MiZer System ...
Page 91: ...91 Fig I 48HC D17 D28 Power Diagram 575 3 60 with Humidi MiZer System ...
Page 92: ...92 Fig J PremierLink System Control Wiring Diagram 50HE500891 F ...
Page 93: ...93 Fig K PremierLink System Control Wiring Diagram with Humidi MiZer System ...
Page 94: ...94 Fig L RTU OPEN Wiring Diagram ...
Page 95: ...95 Fig M RTU OPEN Wiring Diagram with Humidi MiZer System ...
Page 97: ......