19
FIELD CONTROL WIRING
The 50HCQ unit requires an external temperature control device.
This device can be a thermostat (field-supplied) or a Premier-
Link™ controller (available as factory-installed option or as field-
installed accessory, for use on a Carrier Comfort Network
®
or as a
stand-alone control) or the RTU Open Controller for Building
Management Systems using non-CCN protocols (RTU Open is
available as a factory-installed option only).
THERMOSTAT
Select a Carrier-approved accessory 2-stage Cooling/Heating ther-
mostat. The 50HCQ models do not require a thermostat with an O
function to control the reversing valve operation. If using an elec-
tronic thermostat, configure it for “non-heat pump” operation. In-
stall the accessory thermostat according to installation instructions
included with the accessory.
Locate the thermostat accessory on a solid wall in the conditioned
space to sense average temperature in accordance with the ther-
mostat installation instructions.
If the thermostat contains a logic circuit requiring 24-v power, use
a thermostat cable or equivalent single leads of different colors
with minimum of seven leads. If the thermostat does not require a
24-v source (no “C” connection required), use a thermostat cable
or equivalent with minimum of six leads. See Fig. 31. Check the
thermostat installation instructions for additional features which
might require additional conductors in the cable.
For wire runs up to 50 ft. (15 m), use no. 18 AWG (American
Wire Gage) insulated wire [35°C (95°F) minimum]. For 50 to
75 ft. (15 to 23 m), use no. 16 AWG insulated wire [35°C (95°F)
minimum]. For over 75 ft. (23 m), use no. 14 AWG insulated wire
[35°C (95°F) minimum]. Wire sizes larger than no. 18 AWG can-
not be directly connected to the thermostat and will require a junc-
tion box and splice at the thermostat.
Fig. 31 — Typical Low-Voltage Control Connections
Thermostat Wiring, Units Without Thru-Base Connection Kit
Pass the thermostat control wires through the hole provided in the
corner post; then feed the wires through the raceway built into the
corner post to the control box. Pull the wires over to the terminal
strip on the upper-left corner of the Controls Connection Board.
NOTE: If thru-the-bottom connections accessory is used, refer to
the accessory installation instructions for information on routing
power and control wiring.
Fig. 32 — Field Control Wiring Raceway
HEAT ANTICIPATOR SETTINGS
Set heat anticipator settings at 0.14 amp for the first stage and
0.14 amp for second-stage heating, when available.
COMMERCIAL DEFROST CONTROL
The Commercial Defrost Control Board (DFB) coordinates ther-
mostat demands for supply fan control, 1 or 2 stage cooling, 2
stage heating, emergency heating and defrost control with unit op-
erating sequences. The DFB also provides an indoor fan off delay
feature (user selectable). See Fig. 33 for board arrangement.
Fig. 33 — Defrost Control Board Arrangement
The DFB is located in the 50HCQ unit’s main control box (see
Fig. 34). All connections are factory-made through harnesses to
the unit’s CTB, to IFC (belt-drive motor) or to ECM (direct-drive
motor), reversing valve solenoids and to defrost thermostats. Refer
to Table 3 for details of DFB Inputs and Outputs.
X
C
G
W2
R
C
W2
G
W1
O/B/Y2
Y2
W1
R
Y1
Y1
Typic
a
l
Thermo
s
t
a
t
Connection
s
T
H
E
R
M
O
S
T
A
T
(Note 1)
(Note 2)
1. Typic
a
l m
u
lti-f
u
nction m
a
rking. Follow m
a
n
u
f
a
ct
u
rer’
s
config
u
r
a
tion
in
s
tr
u
ction
s
to
s
elect Y2. Do not config
u
re for O o
u
tp
u
t.
2. W2 connection not req
u
ired on
u
nit
s
witho
u
t electric he
a
ting.
Field Wiring
Centr
a
l
Termin
a
l
Bo
a
rd
NOTE
S
:
RACEWAY
HOLE IN END PANEL (HIDDEN)
DIP
SWITCHES
SPEED-UP
JUMPERS
Summary of Contents for WeatherMaster 50HCQ 04 Series
Page 4: ...4 Fig 2 50HCQ 04 06 Units Built On and After 4 15 2019 ...
Page 5: ...5 Fig 3 50HCQ 04 06 Units Built Prior to 4 15 2019 ...
Page 6: ...6 Fig 4 50HCQ 04 06 Corner Weights and Clearances ...
Page 7: ...7 Fig 5 50HCQ 04 06 Base Rail Details ...
Page 8: ...8 Fig 6 50HCQ 04 06 Thru the Base Charts ...
Page 23: ...23 Fig 41 Electro Mechanical Control Wiring 208 230v 460v ...
Page 24: ...24 Fig 42 Electro Mechanical Control Wiring 575v ...
Page 25: ...25 Fig 43 Electro Mechanical Power Wiring 208 230 1 60 ...
Page 26: ...26 Fig 44 Electro Mechanical Power Wiring 208 230 3 60 ...
Page 27: ...27 Fig 45 Electro Mechanical Power Wiring 460 3 60 ...
Page 28: ...28 Fig 46 Electro Mechanical Power Wiring 575 3 60 ...
Page 29: ...29 Fig 47 PremierLink Wiring Schematic 208 230 460v ...
Page 30: ...30 Fig 48 PremierLink Wiring Schematic 575v ...