22
Single Point Boxes and Supplementary Fuses
When the unit MOCP device value exceeds 60-A, unit-mounted
supplementary fuses are required for each heater circuit. These
fuses are included in accessory single point boxes, with power dis-
tribution and fuse blocks. The single point box will be installed di-
rectly under the unit control box, just to the left of the partition
separating the indoor section (with electric heaters) from the out-
door section. The single point box has a hinged access cover. See
Fig. 39. The single point box also includes a set of power taps and
pigtails to complete the wiring between the single point box and
the unit’s main control box terminals. Refer to the accessory heater
and single point box installation instructions for details on tap con-
nections on the field-installed electric heat accessory.
All fuses on 50HCQA units are 60-A. (Note that all heaters are
qualified for use with a 60-A fuse, regardless of actual heater am-
pacity, so only 60-A fuses are necessary.)
Single Point Boxes without Fuses
Refer to accessory heater and single point box installation instruc-
tions for details on tap connections.
Fig. 39 — Typical Single Point Installation
Low Voltage Control Connections
Run the low-voltage control leads from the heater module(s) —
VIO and BRN (two of each if two modules are installed; identify
for Module #1) — to the 4-pole terminal board TB4 located on the
heater bulkhead to the left of Heater #1. Connect the VIO leads
from Heater #1 and Heater #2 to terminal TB4-1. Connect the
BRN leads to terminal TB4-3. See Fig. 40.
Fig. 40 — Accessory Electric Heater Control
Connections
CONTROL AND POWER WIRING DIAGRAMS
Figures 41-49 are typical control and power wiring diagrams.
ALLIED PA
MODEL NO.
ERIAL NO.
CORP.
11
13
21
23
OD
22.2
3
1
23
ISTED AIR
NDITIONING
UIP ACCESS
346N
.
P / N
2-
5610-4
REV
1
1
1
3
2
1
2
3
CONTROL
BOX
BUSHING
SINGLE
POINT BOX
MOUNTING
SCREWS
FOAM
BUSHING
DRIP BOOT
BRACKET
MOUNTING
SCREWS
HEATER
RELAYS
POWER
WIRES
HEATER
MOUNTING
SCREWS
DEFRO
S
T
BOARD
ORN
BRN
Field
Connection
s
E-HEAT
P
3
-
3
3
1
ORN
BRN
VIO
BRN BRN
VIO
TB4
VIO
HR2
HR1
BRN
VIO
BRN
Elec Htr
HR1: On He
a
ter 1 in Po
s
ition #1
HR2: On He
a
ter 2 in Po
s
ition #2 (if in
s
t
a
lled)
Summary of Contents for WeatherMaster 50HCQ 04 Series
Page 4: ...4 Fig 2 50HCQ 04 06 Units Built On and After 4 15 2019 ...
Page 5: ...5 Fig 3 50HCQ 04 06 Units Built Prior to 4 15 2019 ...
Page 6: ...6 Fig 4 50HCQ 04 06 Corner Weights and Clearances ...
Page 7: ...7 Fig 5 50HCQ 04 06 Base Rail Details ...
Page 8: ...8 Fig 6 50HCQ 04 06 Thru the Base Charts ...
Page 23: ...23 Fig 41 Electro Mechanical Control Wiring 208 230v 460v ...
Page 24: ...24 Fig 42 Electro Mechanical Control Wiring 575v ...
Page 25: ...25 Fig 43 Electro Mechanical Power Wiring 208 230 1 60 ...
Page 26: ...26 Fig 44 Electro Mechanical Power Wiring 208 230 3 60 ...
Page 27: ...27 Fig 45 Electro Mechanical Power Wiring 460 3 60 ...
Page 28: ...28 Fig 46 Electro Mechanical Power Wiring 575 3 60 ...
Page 29: ...29 Fig 47 PremierLink Wiring Schematic 208 230 460v ...
Page 30: ...30 Fig 48 PremierLink Wiring Schematic 575v ...