Table 25 — RTU Open Controller Inputs and Outputs
LEGEND
NOTES:
1. Safety Chain Feedback: 24 vac required at this terminal to pro-
vide “Run Enable” status. See Input/Output section for additional
instructions.
2. These inputs are configurable. If installed, they take the place of
the default input on the specific channel. See appropriate Input
Configuration Section for wiring and setup instructions.
3. Parallel pins J5-1 = J2-6, J5-3 = J1-10, J5-5 = J1-2 are used for
field installation.
4. Refer to the input configuration and accessory sections of the
RTU Open Multi-Protocol Controller Controls, Start-Up, Opera-
tion and Troubleshooting manual for more detail.
The RTU Open controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with the
RTU Open system.
SUPPLY AIR TEMPERATURE (SAT) SENSOR
On FIOP-equipped 50HC**14 unit, the unit is supplied
with a supply-air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6-in. (152 mm) in
length. It is a nominal 10k ohm thermistor.
The SAT is factory-wired. The SAT probe is wire-tied to
the supply-air opening (on the horizontal opening end) in its
shipping position. Remove the sensor for installation.
Re-position the sensor in the flange of the supply-air opening
or in the supply air duct (as required by local codes). Drill or
punch a
1
/
2
-in. hole in the flange or duct. Use two field-
supplied, self-drilling screws to secure the sensor probe in a
horizontal orientation. See Fig. 62.
OUTDOOR AIR TEMPERATURE (OAT) SENSOR
The OAT is factory-mounted in the EconoMi$er2 (FIOP
or accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
POINT NAME
BACNET OBJECT
NAME
TYPE OF I/O
CONNECTION PIN
NUMBER(S)
CHANNEL DESIGNATION
DEDICATED INPUTS
Space Temp / Zone Temp
zone_temp
AI (10K Thermistor)
J20-1 & 2
Analog Input 10
Supply Air Temperature
sa_temp
AI (10K Thermistor)
J2-1 & 2
Analog Input 6
Outside Air Temperature
oa_temp
AI (10K Thermistor)
J2-3 & 4
Analog Input 7
Space Temperature Offset Pot
stpt_adj_offset
AI (100K Potentiometer)
J20-3 & 4
Analog Input 11
Safety Chain Feedback
safety_status
BI (24 vac)
J1-9
Binary Input 4
Compressor Safety Status
(Note 1)
comp_status
BI (24 vac)
J1-2
Binary Input 3
Fire Shutdown Status
firedown_status
BI (24 vac)
J1-10
Binary Input 5
Enthalpy Status
enthalpy_status
BI (24 vac)
J2-6 & 7
Binary Input 8
Humidistat Input Status
humstat_status
BI (24 vac)
J5-7 & 8
Binary Input 9
Zone Temperature
N/A
N/A
J13-1-4
Rnet
CONFIGURABLE INPUTS (Note 4)
Indoor Air CO
2
iaq
AI (4-20 mA)
J4-2 & 3 or J4-5 & 6
Analog Input 2
Outdoor Air CO
2
oaq
AI (4-20 mA)
Analog Input 1
Space Relative Humidity
space_rh
AI (4-20 mA)
Analog Input 10
Supply Fan Status (Note 2)
sfan_status
BI (24 vac)
J5-1 & 2 or J5-3 & 4, J5-5 &
6 or J5-7 & 8 (Note 3)
Binary Input 3, 5, 8, or 9, except
where intrinsic input is used
Filter Status (Note 2)
filter_status
BI (24 vac)
Binary Input 3, 5, 8, or 9, except
where intrinsic input is used
Door Contact (Note 2)
door_contact_status BI (24 vac)
Binary Input 3, 5, 8, or 9, except
where intrinsic input is used
Remote Occupancy input
(Note 2)
occ_contact_status
BI (24 vac)
Binary Input 3, 5, 8, or 9, except
where intrinsic input is used
IGC input (Note 2)
igcovr_status
BI (24 vac)
Binary Input 9. Mandatory input
on gas heat units.
OUTPUTS
Economizer Output
econ_output
AO (4-20 mA)
J2-5
Analog Output 1
Supply Fan VFD
vfd_output
AO (2-10 vdc)
J22-1 & 2
Analog Output 2
Supply Fan Relay
sfan
BO Relay (24 vac, 1A)
J1-4
Binary Output 1 (G)
Cool 1 Relay State
comp_1
BO Relay (24 vac, 1A)
J1-8
Binary Output 5 (Y1)
Cool 2 Relay State
comp_2
BO Relay (24 vac, 1A)
J1-7
Binary Output 4 (Y2)
Cool 3 Relay State
comp_3
BO Relay (24 vac, 1A)
J11-5 & 6
Binary Output 7 (Y3)
Heat 1 Relay State
heat_1
BO Relay (24 vac, 1A)
J1-6
Binary Output 3 (W1)
Heat 2 Relay State
heat_2
BO Relay (24 vac, 1A)
J1-5
Binary Output 2 (W2)
Power Exhaust Relay State
pexh
BO Relay (24 vac, 1A)
J11-2 & 3 (N.O.)
Binary Output 8 (PE)
Dehumidification Relay
dehum
BO Relay (24 vac, 1A)
J11-7 & 8 (N.O.)
Binary Output 6
AI
—
Analog Input
AO
—
Analog Output
BI
—
Binary Input
BO
—
Binary Output
Summary of Contents for WeatherMaster 50HC14
Page 4: ...4 Fig 2 Unit Dimensional Drawing 14 Size Unit ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing 14 Size Unit cont HORIZONTAL ECONOMIZER VERTICAL ECONOMIZER ...
Page 8: ...8 Fig 4 Roof Curb Details ...
Page 24: ...24 Fig 46 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 39: ...39 Fig 54 50HC14 Control Box Component Locations with ComfortLink Controls ...
Page 40: ...40 Fig 55 50HC14 ComfortLink Control Wiring Diagram ...
Page 41: ...41 Fig 56 50HC14 ComfortLink Power Wiring Diagram ...
Page 42: ...42 Fig 57 50HC14 ComfortLink with Humidi MiZer Power Wiring Diagram ...
Page 44: ...44 Fig 60 PremierLink Wiring Schematic ...
Page 45: ...45 Fig 61 PremierLink Wiring Schematic with Humidi MiZer System Option ...
Page 53: ...53 Fig 80 RTU Open System Control Wiring Diagram ...
Page 54: ...54 Fig 81 RTU Open System Control Wiring Diagram with Humidi MiZer System Option ...
Page 64: ......
Page 65: ......