
5
Position 5 tap, the motor speed is approximately 1050 rpm
(17.5 r/s) but varies depending on fan wheel loading.
Selecting speed tap
The five communication terminals are each programmed to pro-
vide a different motor torque output. See Table 1. Factory default
tap selection is Position 1 for lowest torque/speed operation.
Table 1 — Motor Tap Programing
(percent of full-load torque)
Factory Default: Tap 1 (VIO).
Selecting another speed:
1. Disconnect main power to the unit. Apply lockout/tag-out
procedures.
2. Remove the default motor signal lead (VIO) from terminal
1 at the motor communications terminal.
3. Reconnect the motor signal lead to the desired speed (ter-
minals 1 through 5).
4. Connect main power to the unit.
Motor “rocking” on start-up
When the motor first starts, the rotor (and attached wheel) will
“rock” back and forth as the motor tests for rotational direction.
Once the correct rotational direction is determined by the motor
circuitry, the motor will ramp up to the specified speed. The
“rocking” is a normal operating characteristic of ECM motors.
Troubleshooting the ECM motor
ECM Motor Testing Procedure
1. Inspect motor bearing. ECM motors have sealed stainless
steel bearings. Turn the motor shaft by hand to ensure that it
turns freely and that there is no excessive play or friction as it
rotates. Be mindful that motors have permanent magnetized
rotors, which will add a stepping feel to the shaft rotation.
2. Inspect motor windings. ECM motors have 3 electrically
identical windings. Once the motor is detached from the
module, check the winding resistance.
a. Using an Ohm meter set to the 200
Ω
scale, measure
resistance as follows (see Fig. 7).
Blue (A) to Black (B)
Blue (A) to Red (C)
Black (B) to Red (C)
The difference between any two leads should be less than
20 Ohms. The resistance from A to B, A to C, and B to C
should be approximately the same (should differ by a maxi-
mum of ±10%). See Fig. 8.
3. Inspect resistance to ground.
a. Measure the resistance of each lead to the unpainted
motor plate (see Fig. 9).
b. Resistance should be >100K
Ω
.
c. If measure resistance is outside the above range,
replace the motor.
Fig. 7 — Winding Leads
Fig. 8 — Testing Winding Resistance
Fig. 9 — Resistance to Ground
If the motor passes steps 1-3, then it is in good condition.
Troubleshooting the X13 ECM requires a voltmeter.
1. Disconnect main power to the unit.
2. Remove the motor power plug (including the control BRN
lead) and VIO control signal lead at the motor terminals.
3. Restore main unit power.
4. Check for proper line voltage at motor power leads BLK
(at L terminal) and YEL (at N terminal). See Table 2.
Table 2 — Motor Test Volts
5. Using a jumper wire from unit control terminals R to G,
engage motor operation. Check for 24-v output at the
defrost board terminal IFO.
6. Check for proper control signal voltages of 22-v to 28-v at
motor signal leads VIO and BRN.
7. Disconnect unit main power. Apply lockout/tag-out
procedures.
8. Reconnect motor power and control signal leads at the
motor terminals.
9. Restore unit main power.
10. The motor should start and run. If the motor does not start,
remove the motor assembly. Replace the motor with one
having the same part number. Do not substitute with an
alternate design motor as the torque/speed programming
will not be the same as that on an original factory motor.
50HC UNIT
SIZE
TAP 1
TAP 2
TAP 3
TAP 4
TAP 5
04
32 38 45 50
100
05
46 58 61 69
100
06
73 82 85 90
100
50HC UNIT
VOLTAGE
MOTOR VOLTAGE
MIN-MAX VOLTS
208/230
230 190-250
460
230 210-250
575
460 420-500
>100 KΩ
Summary of Contents for WeatherMaster 50HC04
Page 32: ...32 Fig 63 RTU Open Overlay for Economizer Wiring ...
Page 33: ...33 Fig 64 VFD Overlay for W2770 Controller Wiring ...
Page 86: ...86 Fig C 50HC A07 PAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 91: ...91 Fig H 50HC D12 PAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 93: ...93 Fig J 50HC A04 A06 PAC Power Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Page 95: ...95 Fig L 50HC A07 PAC Power Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 100: ...100 Fig Q 50HC D11 PAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 101: ...101 Fig R 50HC D11 PAC Power Diagram 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 103: ...103 Fig T 50HC D14 PAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 104: ...104 Fig U 50HC D14 PAC Power Diagram 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 124: ...124 Fig AO PremierLink System A04 A06 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 125: ...125 Fig AP RTU Open System Control A04 A06 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 126: ...126 Fig AQ PremierLink System A07 D14 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 127: ...127 Fig AR RTU Open A07 D14 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...