![Carrier WeatherMaster 50HC*A07 Series Installation Instructions Manual Download Page 15](http://html.mh-extra.com/html/carrier/weathermaster-50hc-a07-series/weathermaster-50hc-a07-series_installation-instructions-manual_2560340015.webp)
15
Step 10 — Make Electrical Connections
NOTE: Field-supplied wiring shall conform with the limitations
of minimum 63°F (33°C) rise.
FIELD POWER SUPPLY
If equipped with optional Powered Convenience Outlet:
The power source leads to the convenience outlet’s trans-
former primary are not factory connected. Installer must con-
nect these leads according to required operation of the conve-
nience outlet. If an always-energized convenience outlet op-
eration is desired, connect the source leads to the line side of
the unit-mounted disconnect. (Check with local codes to en-
sure this method is acceptable in your area.) If a de-energize
via unit disconnect switch operation of the convenience outlet
is desired, connect the source leads to the load side of the unit
disconnect. On a unit without a unit-mounted disconnect,
connect the source leads to compressor contactor C and in-
door fan contactor (IFC) pressure lugs with unit field power
leads.
Field power wires will be connected at the line-side pres-
sure lugs on the power terminal block or at factory-installed
option non-fused disconnect or HACR.
Field power wires are connected to the unit at line-side
pressure lugs on compressor contactor C and indoor fan con-
tactor IFC (see wiring diagram label for control box compo-
nent arrangement), or at factory-installed option non-fused
disconnect switch or HACR or electric heat single point box.
Max wire size is #4ga AWG (copper only) per pole on con-
tactors, #4ga AWG (copper only) or 1/0 AWG (copper only)
per pole on optional disconnect (max wire size depends on
the disconnect size supplied with unit), 1/0 AWG (copper on-
ly) on optional HACR and 4/0 AWG (copper only) per pole
on terminal or fuse block on units with single point box. See
Fig. 18 and unit label diagram for field power wiring
connections.
NOTE: TEST LEADS — Unit may be equipped with short
leads (pigtails) on the field line connection points on contactor C
or optional disconnect switch or HACR. These leads are for fac-
tory run-test purposes only; remove and discard before connect-
ing field power wires to unit connection points. Make field pow-
er connections directly to line connection pressure lugs only.
Fig. 18 — Power Wiring Connections
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Do not use gas piping as an electrical ground.
Unit cabinet
must have an uninterrupted, unbroken electrical ground to
minimize the possibility of personal injury if an electrical
fault should occur. This ground may consist of electrical wire
connected to unit ground lug in control compartment, or
conduit approved for electrical ground when installed in
accordance with NEC (National Electrical Code); ANSI/
NFPA 70, latest edition (in Canada, Canadian Electrical
Code CSA [Canadian Standards Association] C22.1), and
local electrical codes.
TB
TB
11
12
Disconnect
per
NEC
208/230-1-60
Disconnect
per
NEC
11
12
13
L1
L2
L3
208/230-3-60
460-3-60
Units Without Single Point Box, Disconnect or HACR Option
Units With Disconnect or HACR Option
L1
L2
L3
2
4
6
1
5
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
3
Equip
GR Lug
Ground
(GR)
Equip GR Lug
Ground
(GR)
3 Phase Only
3 Phase Only
Units With Electric Heat Option with Single Point Box
and Without Disconnect or HACR Option
L1
L2
L3
Single Point Box
Factory
Wiring
Equip GR
Lug
Ground (GR)
Terminal Block
— OR —
L1
L2
L3
Single Point Box
Factory
Wiring
Equip GR
Lug
Ground (GR)
Fuse/Terminal Block
Fuse
Fuse
Fuse
Summary of Contents for WeatherMaster 50HC*A07 Series
Page 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 07 09 ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Page 25: ...25 Fig 42 Electro Mechanical Control Wiring Diagram ...
Page 26: ...26 Fig 43 Electro Mechanical Control Wiring Diagram with Humidi MiZer System ...
Page 27: ...27 Fig 44 Typical ComfortLink Control Wiring Diagram 50HC 08 09 shown ...
Page 29: ...29 Fig 46 Typical PremierLink Control Wiring Diagram ...
Page 30: ...30 Fig 47 Typical PremierLink Control Wiring Diagram with Humidi MiZer System Option ...
Page 31: ...31 Fig 48 Typical RTU Open Controller Wiring Diagram ...
Page 32: ...32 Fig 49 Typical RTU Open Controller Wiring Diagram with Humidi MiZer System Option ...