Installation Instructions

CONTENTS

SAFETY CONSIDERATIONS   . . . . . . . . . . . . . . . . . . . 1
MODEL NUMBER NOMENCLATURE AND 

DIMENSIONS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Rated Indoor Airflow  . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 1 — Plan for Unit Location   . . . . . . . . . . . . . . . . 7

• ROOF MOUNT

Step 2 — Plan for Sequence of Unit Installation   . . . 7

• CURB-MOUNTED INSTALLATION

• PAD-MOUNTED INSTALLATION

• FRAME-MOUNTED INSTALLATION

Step 3 — Inspect Unit  . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 — Provide Unit Support   . . . . . . . . . . . . . . . . . 7

• ROOF CURB MOUNT

• SLAB MOUNT (HORIZONTAL UNITS ONLY)

• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR 

SLAB MOUNT)

Step 5 — Field Fabricate Ductwork  . . . . . . . . . . . . . . 9

• UNITS WITH ACCESSORY OR OPTIONAL ELECTRIC 

HEATERS

Step 6 — Rig and Place Unit   . . . . . . . . . . . . . . . . . . . 9

• POSITIONING ON CURB

Step 7 — Convert to Horizontal and Connect 

Ductwork (When Required)  . . . . . . . . . . . . . . . . . 10

Step 8 — Install Outside Air Hood  . . . . . . . . . . . . . . 11

• ECONOMIZER HOOD PACKAGE REMOVAL AND 

SETUP (FACTORY OPTION)

• ECONOMIZER HOOD

Step 9 — Units with Hinged Panels Only   . . . . . . . . 12
Step 10 — Install External Condensate Trap and

Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Step 11 — Make Electrical Connections  . . . . . . . . . 12

• FIELD POWER SUPPLY

• UNITS WITH FACTORY-INSTALLED NON-FUSED 

DISCONNECT OR HACR

• UNITS WITHOUT FACTORY-INSTALLED NON-

FUSED DISCONNECT OR HACR

• ALL UNITS

• CONVENIENCE OUTLETS

• HACR AMP RATING

• FACTORY OPTION THRU-BASE CONNECTIONS

• UNITS WITHOUT THRU-BASE CONNECTIONS 

(ELECTRICAL CONNECTIONS)

• FIELD CONTROL WIRING

• THERMOSTAT

• HEAT ANTICIPATOR SETTINGS

• ELECTRIC HEATERS

• HUMIDI-MIZER® CONTROL CONNECTIONS

• TYPICAL UNIT WIRING DIAGRAMS

EconoMi$er® X (Factory Option) . . . . . . . . . . . . . . . 24

• SYSTEM COMPONENTS

• SPECIFICATIONS

• INPUTS

• OUTPUTS

• ENVIRONMENTAL

• ECONOMIZER MODULE WIRING DETAILS

• S-BUS SENSOR WIRING

• CO2 SENSOR WIRING

• INTERFACE OVERVIEW

• SETUP AND CONFIGURATION

• TIME-OUT AND SCREENSAVER

• ENTHALPY SETTINGS

• STANDARD OR SINGLE SPEED FAN OPERATION

• 2 SPEED FAN OPERATION

• 2SP H/C AND 3 SPEED FAN OPERATION

•  CHECKOUT

• TROUBLESHOOTING

RTU Open Controller (Factory Option)   . . . . . . . . . .35
SystemVu™ Controller (Factory Option) . . . . . . . . .35
Controller Options  . . . . . . . . . . . . . . . . . . . . . . . . . . .35

• LOW AMBIENT

Smoke Detectors  . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Step 12 — Adjust Factory-Installed Options  . . . . . .37

• SMOKE DETECTORS

• ECONOMI$ER® IV OCCUPANCY SWITCH

Step 13 — Install Accessories   . . . . . . . . . . . . . . . . .37
Step 14 — Fan Speed Set Up   . . . . . . . . . . . . . . . . . .38

• UNITS WITH ELECTRO-MECHANICAL CONTROLS

• UNITS WITH SYSTEMVU™ CONTROLS

START-UP CHECKLIST  . . . . . . . . . . . . . . . . . . . .  CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be

hazardous due to system pressure and electrical components. Only

trained and qualified service personnel should install, repair, or

service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of

cleaning coils and filters and replacing filters. All other operations

should be performed by trained service personnel. When working

on air-conditioning equipment, observe precautions in the litera-

ture, tags and labels attached to the unit, and other safety precau-

tions that may apply.
Follow all safety codes, including ANSI (American National Stan-

dards Institute) Z223.1. Wear safety glasses and work gloves. Use

quenching cloth for unbrazing operations. Have fire extinguisher

available for all brazing operations.
It is important to recognize safety information. This is the safety-

alert symbol 

. When you see this symbol on the unit and in in-

structions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,

and NOTE. These words are used with the safety-alert symbol.

DANGER identifies the most serious hazards which 

will

 result in

severe personal injury or death. WARNING signifies hazards

which 

could

 result in personal injury or death. CAUTION is used

to identify unsafe practices, which 

may

 result in minor personal

injury or product and property damage. NOTE is used to highlight

suggestions which 

will

 result in enhanced installation, reliability,

or operation.

WeatherMaster

®

50GC**04-06

Single Package Rooftop Cooling Only/Electric Heat Unit

with Puron

®

 (R-410A) Refrigerant

Summary of Contents for WeatherMaster 50GC 04-06 Series

Page 1: ...FAN OPERATION 2SP H C AND 3 SPEED FAN OPERATION CHECKOUT TROUBLESHOOTING RTU Open Controller Factory Option 35 SystemVu Controller Factory Option 35 Controller Options 35 LOW AMBIENT Smoke Detectors 3...

Page 2: ...uld cause personal injury death and or equipment damage R 410A refrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or components on R 410A refr...

Page 3: ...installed W7212 EconoMi er IV Non Fault Detection and Diagnostic 2 RTU Open Multi Protocol Controller 3 SystemVu Controller 6 Electro mechanical can be used with W7220 EconoMi er X with Fault Detecti...

Page 4: ...4 Fig 2 50GC 04 06 Unit Dimensional Drawing...

Page 5: ...5 Fig 2 50GC 04 06 Unit Dimensional Drawing cont...

Page 6: ...6 Fig 2 50GC 04 06 Unit Dimensional Drawing cont...

Page 7: ...ions 9 Install other accessories PAD MOUNTED INSTALLATION 1 Prepare pad and unit supports 2 Check and tighten the bottom condensate drain connection plug 3 Rig and place unit 4 Convert unit to side du...

Page 8: ...ENGINEERING MANUFACTURING ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRAFTER CHECKER D 48TC400427 B WEIGHT MMC 06 17 11 SHEET 5 OF 5 SURFACE FINISH MFG PURCH MODEL INTERNAL USE ONLY...

Page 9: ...using unit frame as a refer ence See Table 2 on page 7 and Fig 5 for additional information Lifting holes are provided in base rails as shown in Fig 5 Refer to rigging instructions on unit Rigging mat...

Page 10: ...weatherproof all external ductwork joints and roof or build ing openings with counter flashing and mastic in accordance with applicable codes Do not cover or obscure visibility to the unit s informati...

Page 11: ...Save the aluminum filter for use in the power exhaust hood assembly 1 The indoor coil access panel will be used as the top of the hood Remove the screws along the sides and bottom of the indoor coil a...

Page 12: ...owered convenience outlet the power source leads to the convenience outlet s transformer primary are not factory connected Installer must connect these leads accord ing to required operation of the co...

Page 13: ...ndle Fig 18 Power Wiring Connections Field Install the NFD Shaft and Handle 1 Remove the Control Box access panel The NFD enclosure is located below the Control Box see Fig 19 2 Remove 3 cap head scre...

Page 14: ...sition See Fig 22 6 Tighten the locking screw to secure the shaft to the HACR 7 Turn the handle to the OFF position with red arrow pointing at OFF 8 Install the handle on to the painted cover horizont...

Page 15: ...over Aweatherproof while in use cover for the factory installed conve nience outlets is now required by UL standards This cover cannot be factory mounted due its depth it must be installed at unit ins...

Page 16: ...zation is con firmed Observe National Electrical CodeArticle 210 Branch Cir cuits for use of convenience outlets Fuse On Power Type The factory fuse is a Bussman1 Fusetron T 15 non renewable screw in...

Page 17: ...rminals during operation must be within voltage range indicated on unit nameplate On 3 phase units volt ages between phases must be balanced within 2 and the current within 10 Use the formula shown in...

Page 18: ...terminal strip on the upper left corner of the Unit Control Board See Fig 32 NOTE If thru the bottom connections accessory is used refer to the accessory installation instructions for information on r...

Page 19: ...e heater module VIO and BRN two of each if a two circuit heater module is installed identify for circuit 1 to the 4 pole terminal board TB4 located on the heater bulkhead to the left of the Heater mod...

Page 20: ...ee Fig 40 Fig 40 Humidistat Connections to UCB Connecting the Thermidistat device 33CS2PPRH 01 1 Route the Thermidistat multi conductor thermostat cable field supplied through the hole provided in the...

Page 21: ...it with Humidi MiZer Adaptive Dehumidification System and Edge Pro Thermidistat Device Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg C HUM G W2 W1 Y2 Y1 R PROGRAMMABLE THERMOSTAT UNIT CONTROL...

Page 22: ...22 Fig 42 Typical 50GC 04 06 Control Wiring Diagram 208 230V W7220 Control Unit Shown...

Page 23: ...23 Fig 43 Typical 50GC 04 06 Power Wiring Diagram 208 230V Unit Shown...

Page 24: ...ce Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display and four button keypad Electrical Rated Voltage 20 to 30 V...

Page 25: ...Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source ACT 2 10 2 10 vdc Damper Actuator Output 2 10 vdc ACT COM COM Damper Actuator Output C...

Page 26: ...t a menu s item and return to the list of menus Fig 48 W7220 Controller Navigation Buttons To use the keypad when working with Setpoints System and Ad vanced Settings Checkout tests and Alarms 1 Navig...

Page 27: ...the and arrow buttons to move forward and back ward through the menus and press the button to select and confirm setup item changes TIME OUT AND SCREENSAVER When no buttons have been pressed for 10 m...

Page 28: ...re Displays _ _ _F if sensor sends invalid value if not connected short or out of range OA TEMP _ _ _ F 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMP Displays measured value of outdoor air temperature D...

Page 29: ...TILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used If using 2 speed with 1 heat and 1 cool then set for HEATING ventilation If using 3 speed with...

Page 30: ...If using 2 speed fan mode you must program CONV mode for W Shutdown is not available in 2 speed fan mode See Menu Note 4 In HP O B mode HP O energize heat pump on Cool default HP B energize heat pump...

Page 31: ...o adjust for an out of calibration temperature sensor 2SP FAN DELAY 5 Minutes 0 to 20 minutes in 1 minute increments TIME DELAY ON SECOND STAGE ECONOMIZING When in economizing mode this is the delay f...

Page 32: ...A OUTSIDE AIR TEMPERATURE SENSOR ERROR Outdoor air temperature sensor has failed or become disconnected check wiring then replace if the alarm continues ACT ERROR N A N A ACTUATOR ERROR Actuator has f...

Page 33: ...dary the conditions are not good to economize and the mode is set to NO Figure 49 shows the 5 current boundaries There is also a high lim it boundary for differential enthalpy The high limit boundary...

Page 34: ...delay time specified N A Not applicable Table 9 Fan Speed STATE FAN SPEED OCC Low Y1 Low Y2 High W High Table 10 Economizer Operation FAN TYPE 2SPEED INPUTS OUTPUTS DEMAND CONTROLLED VENTILATION DCV O...

Page 35: ...Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the following 1 Navigate to the desired...

Page 36: ...e sure that the elbow fitting is pointing down See Fig 51 Step 2 3 Screw the sensor and detector plate into its operating position using screws from Step 1 See Fig 51 Step 3 4 Connect the flexible tub...

Page 37: ...oc cupied sequence at terminals marked OCCUPANCY Detach the jumper covering the Occupancy terminals on the UCB and then attach the required connections Step 13 Install Accessories Available accessorie...

Page 38: ...for the base unit Then add Vdc for any accessories installed per the Field Accessories section of the label NOTE The fan speed set up labels are located on the High Volt age cover in the Control Box...

Page 39: ...he following determin ing the values per the RPM Calculator label see Fig 55 Use the UP and DOWN arrow keys and the BACK key to set the values Press ENTER after setting each value to continue to the n...

Page 40: ...75 66 80 107 0 4 1477 1544 1615 1688 1764 1842 1921 2003 2068 66 0 6 1639 1699 1763 1828 1897 1967 2040 2115 2191 0 8 1788 1843 1902 1962 2025 2090 2157 2227 2298 66 1 0 1925 1976 2031 2087 2146 2208...

Page 41: ......

Page 42: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500269 01 Printed in U S A Form 50GC 4 6 03SI Pg 42 12 19A 12 19 Replaces 50...

Page 43: ...ns Y N _____ Verify that all electrical connections and terminals are tight Y N _____ Check that indoor air filters are clean and in place Y N _____ Check that outdoor air inlet screens are in place Y...

Page 44: ...______________ F D Liquid line temperature at outlet or reheat coil _______________ F E Confirm correct rotation for compressor Y N _____ F Check for correct ramp up of outdoor fan motor as condenser...

Reviews: