Table 66 — Building Pressure Configuration
*Some configurations are model number dependent.
Building Pressure SETP (BP.SP)
This set point is the building pressure control set point. If the
unit is configured for a type of modulating building pressure
control, then this is the set point that the control will control to.
BP Setpoint Offset (BP.SO)
For building pressure configurations
BP.CF
=2, 3, and 4, this is
the offset below the building pressure set point that the build-
ing pressure must fall below to turn off power exhaust control.
Power Exhaust on Setp.1 (BP.P1)
When configured for building pressure control type
BP.CF
= 1
(constant volume two-stage control), the control will turn on
the first power exhaust fan when the economizer’s position ex-
ceeds this set point.
Power Exhaust on Setp.2 (BP.P2)
When configured for building pressure control type
BP.CF
= 1
(constant volume two-stage control), the control will turn on
the second power exhaust fan when the economizer’s position
exceeds this set point.
VFD/Act. Fire Speed/Pos (BP.FS)
For
BP.CF
= 2, 3, 4, and 5, this configuration is the VFD
speed/actuator position override when the control is in the
purge and evacuation smoke control modes.
VFD/Act. Min Speed/Pos (BP.MN)
For
BP.CF
= 2, 3, 4, and 5, this configuration is the minimum
VFD speed/actuator position during building pressure control.
VFD Maximum Speed/Pos (BP.MX)
For
BP.CF
= 3 and 5, this configuration is the maximum VFD
speed during building pressure control.
BP 1 Actuator Max Pos. (BP.1M)
For
BP.CF
= 2, this configuration is the maximum actuator no.
1 position during building pressure control.
BP 2 Actuator Max Pos. (BP.2M)
For
BP.CF
= 2, this configuration is the maximum actuator no.
2 position during building pressure control.
BP Hi Cap VFD Clamp Val. (BP.CL)
For
BP.CF
= 4, this configuration is a limit that creates a deadband
which controls the action of the second power exhaust relay.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
BP
BUILDING PRESS. CONFIGS
BP.CF
Building Press. Config
0 to 5
BLDG_CFG
0*
BP.S
Building Pressure Sensor
Enable/Disable
BPSENS
Disable*
BP.R
Bldg. Press. (+/-) Range
0.10 to 0.25
" H2O
BP_RANGE
0.25
BP.SP
Building Pressure Setp.
–0.25 to 0.25
" H2O
BPSP
0.05
BP.SO
BP Setpoint Offset
0 to 0.5
" H2O
BPSO
0.05
BP.P1
Power Exhaust On Setp.1
0 to 100
%
PES1
25
BP.P2
Power Exhaust On Setp.2
0 to 100
%
PES2
75
B.V.A
VFD/ACTUATOR CONFIG
BP.FS
VFD/Act. Fire Speed/Pos.
0 to 100
%
BLDGPFSO
100
BP.MN
VFD/Act. Min.Speed/Pos.
0 to 50
%
BLDGPMIN
10
BP.MX
VFD Maximum Speed
50 to 100
%
BLDGPMAX
100
BP.1M
BP 1 Actuator Max Pos.
85 to 100
%
BP1SETMX
100
BP.2M
BP 2 Actuator Max Pos.
85 to 100
%
BP2SETMX
100
BP.CL
BP Hi Cap VFD Clamp Val.
5 to 25
%
BLDGCLMP
10
FAN.T
FAN TRACKING CONFIG
FT.CF
Fan Track Learn Enable
Yes/No
DCFM_CFG
No
FT.TM
Fan Track Learn Rate
5 to 60
min
DCFMRATE
15
FT.ST
Fan Track Initial DCFM
–20000 to 20000
CFM
DCFMSTRT
2000
FT.MX
Fan Track Max Clamp
0 to 20000
CFM
DCFM_MAX
4000
FT.AD
Fan Track Max Correction
0 to 20000
CFM
DCFM_ADJ
1000
FT.OF
Fan Track Internl EEPROM
–20000 to 20000
CFM
DCFM_OFF
0
FT.RM
Fan Track Internal RAM
–20000 to 20000
CFM
DCFM_RAM
0
FT.RS
Fan Track Reset Internal
Yes/No
DCFMRSET
No
SCF.C
Supply Air CFM Config
1 to 2
SCFM_CFG
1
B.PID
BLDG.PRESS.PID CONFIGS
BP.TM
Bldg.Pres.PID Run Rate
5 to 120
sec
BPIDRATE
10
BP.P
Bldg.Press. Prop. Gain
0 to 5
BLDGP_PG
0.5
BP.I
Bldg.Press. Integ. Gain
0 to 2
BLDGP_IG
0.5
BP.D
Bldg.Press. Deriv. Gain
0 to 5
BLDGP_DG
0.3
ACT.C
BLDG.PRES. ACTUATOR CFGS
BP.1
BLDG.PRES. ACT.1 CONFIGS
SN.1
BP 1 Serial Number 1
0 to 9999
BP_1_SN1
0
SN.2
BP 1 Serial Number 2
0 to 6
BP_1_SN2
0
SN.3
BP 1 Serial Number 3
0 to 9999
BP_1_SN3
0
SN.4
BP 1 Serial Number 4
0 to 254
BP_1_SN4
0
C.A.LM
BP1 Cntrl Angle Lo Limit
0 to 90
BP1_CALM
35
BP.2
BLDG.PRES. ACT.2 CONFIGS
SN.1
BP 2 Serial Number 1
0 to 9999
BP_2_SN1
0
SN.2
BP 2 Serial Number 2
0 to 6
BP_2_SN2
0
SN.3
BP 2 Serial Number 3
0 to 9999
BP_2_SN3
0
SN.4
BP 2 Serial Number 4
0 to 254
BP_2_SN4
0
C.A.LM
BP2 Cntrl Angle Lo Limit
0 to 90
BP2_CALM
35
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...