63
Hydronic Heating Control Derivative Gain (HW.D)
This configuration is the derivative term for the PID which
runs in the HVAC mode LOW HEAT.
Hydronic Heating Control Run Time Rate (HW.TM)
This configuration is the PID run time rate which runs in the
HVAC mode LOW HEAT.
Hydronic Heating Logic
If the HVAC mode is LOW HEAT:
• The control will command the supply fan on
• The control will modulate the hot water coil actuator to the
heating control point (
Run Status
VIEW
HT.C.P
).
The heating control point for hydronic heat is the heating
supply air set point (
Setpoints
SA.HT
).
If the HVAC mode is HIGH HEAT:
• The control will command the supply fan on
• The control will command the hot water coil actuator to
100%.
Hydronic Heating PID Process
If the HVAC mode is LOW HEAT, then the hydronic heating
actuator will modulate to the heating control point (
Run Sta-
tus
VIEW
HT.C.P
). Control is performed with a generic
PID loop where:
Error = Heating Control Point (
HT.C.P
) – Leaving Air Tem-
perature (LAT)
The PID terms are calculated as follows:
P = K *
HW.P
* error
I = K *
HW.I
* error + “I” last time through
D = K *
HW.D
* (error – error last time through)
Where K =
HW.TM
/60 to normalize the effect of changing the
run time rate.
NOTE: The PID values should be not be modified without ap-
proval from Carrier.
Freeze Status Switch Logic (Inputs
GEN.I
FRZ.S)
If the freezestat input (FRZ) alarms, indicating that the coil is
freezing, normal heat control is overridden and the following
actions will be taken:
1. Command the hot water coil actuator to 100%.
2. Command the economizer damper to 0%.
3. Command the supply fan on.
Configuring Hydronic Heat to Communicate Via Actuator
Serial Number
Every actuator used in the P Series control system has its own
unique serial number. The rooftop control uses this serial num-
ber to communicate with the actuator. These serial numbers are
programmed at the factory and should not need changing.
Should field replacement of an actuator become necessary, it
will be required to configure the serial numbers of the new ac-
tuator. Four individual numbers make up this serial number
and these can be programmed to match the serial number of the
actuator in its Hydronic Heating Actuator Configs group,
ACT.C
(
SN.1, SN.2, SN.3, SN.4
). See Fig. 9.
Fig. 9 — Actuator Serial Number Configuration
NOTE: The serial numbers for all actuators can be found inside
the control doors of the unit as well as on the actuator itself. If an
actuator is replaced in the field, it is a good idea to remove the ad-
ditional peel off serial number sticker on the actuator and cover up
the old one inside the control doors.
STAGED GAS HEAT CONTROL (
HT.CF
= 3 AND
HT.ST
=
0, 1, OR 2)
As an option, the units with gas heat can be equipped with
staged gas heat controls that will provide from 2 to 9 stages of
heat capacity. This is intended for tempering mode and temper-
ing economizer air when in a cooling mode and the dampers
are at minimum vent position. Tempering can also be used
during a pre-occupancy purge to prevent low temperature air
from being delivered to the space. Tempering for staged gas,
modulating gas, and hydronic heat will be discussed in its own
section. This section will focus on heat mode control, which ul-
timately is relevant to tempering, minus the consideration of
the supply air heating control point.
MODULATING GAS HEAT CONTROL (
HT.CF
= 3 AND
HT.ST
= 3, 4, OR 5)
As an option, the units with gas heat can be equipped with
modulating gas heat controls that will provide infinite stages of
heat capacity. This is intended for tempering mode and temper-
ing economizer air when in a cooling mode and the dampers
are at minimum vent position. Tempering can also be used
during a pre-occupancy purge to prevent low temperature air
from being delivered to the space. Tempering for staged gas,
modulating gas, and hydronic heat will be discussed in its own
section. This section will focus on heat mode control, which ul-
timately is relevant to tempering, minus the consideration of
the supply air heating control point.
The staged and modulating gas and SCR electric heat configu-
rations are located at the local display under
Configura-
tion
HEAT
SG.CF
.
See Table 44.
Table 44 — Staged Heat Configuration
*Some configurations are model number dependent.
00
8
50 -
3
006
3
- 0
8
4 -0
83
ACTUATOR
S
ERIAL NUMBER
{
NOT
U
S
ED
{
S
N.1
{
{
S
N.2
S
N.
3
{
NOT
U
S
ED
{
S
N.4
S
N.1 =
8
50
S
N.2 =
3
S
N.
3
= 6
3
S
N.4 =
83
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
SG.CF
STAGED HEAT CONFIGS
HT.ST
Staged Heat Type
0 to 8
HTSTGTYP
0*
CAP.M
Max Cap Change per Cycle
5 to 45
HTCAPMAX
45*
M.R.DB
St.Ht DB min.dF/PID Rate
0 to 5
HT_MR_DB
0.5
S.G.DB
St.Heat Temp. Dead Band
0 to 5
^F
HT_SG_DB
2
RISE
Heat Rise dF/sec Clamp
0.05 to 0.2
HTSGRISE
0.06
LAT.L
LAT Limit Config
0 to 20
^F
HTLATLIM
10
LIM.M
Limit Switch Monitoring?
Yes/No
HTLIMMON
Yes
SW.H.T
Limit Switch High Temp
80 to 210
dF
HT_LIMHI
170*
SW.L.T
Limit Switch Low Temp
80 to 210
dF
HT_LIMLO
160*
HT.P
Heat Control Prop. Gain
0 to 1.5
HT_PGAIN
1
HT.D
Heat Control Derv. Gain
0 to 1.5
HT_DGAIN
1
HT.TM
Heat PID Rate Config
30 to 300
sec
HTSGPIDR
90*
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...