33
CONTROLS QUICK START
The following section will provide a quick user guide to setting
up and configuring the P Series units with
Comfort
Link con-
trols. See Basic Control Usage section on page 4 for informa-
tion on operating the control.
VAV Units Using Return Air Sensor or Space
Temperature Sensor
To configure the unit, perform the following:
1. The type of control is configured under
Configuration
UNIT
C.TYP
.
Set
C.TYP
to 1 (VAV-RAT) for return air
sensor. Set
C.TYP
to 2 (VAV-SPT) for space temperature
sensor.
NOTE: For VAV with a space sensor (VAV-SPT), under
Configu-
ration
UNIT
SENS
SPT.S
, enable the space sensor by set-
ting
SPT.S
to ENBL.
NOTE: Configuration of the machine control type (
C.TYP
) has
no effect on whether a unit has a VFD or just a supply fan in-
stalled for static pressure control. No matter what the control
type is, it is possible to run the unit in either CV or VAV mode,
provided there are enough stages to accommodate lower air vol-
umes for VAV operation. Refer to the section on static pressure
control for information on how to set up the unit for the type of
supply fan control desired.
2. The space temperature set points and the supply air set
points are configured under the Setpoints menu. The heat-
ing and cooling set points must be configured. See the
Heating Control and Cooling Control sections for further
description on these configurations. Configure the follow-
ing set points:
Also configure the following points in the
Configuration
D.LV.T
menu:
3. To program time schedules, make sure
SCH.N
=1 under
Configuration
CCN
SC.OV
SCH.N
to configure the
control to use local schedules.
4. Under the
Timeclock
SCH.L
submenu, enter the desired
schedule. See Time Clock section for further descriptions
of these configurations.
5. Under
Configuration
SP
SP.SP
, the Supply Duct
Static Pressure set point should be configured.
6. If supply air temperature reset is desired, under the
Con-
figuration
EDT.R
submenu, the following set points
should be configured:
This applies to both TSTAT MULTI and SENSOR MULTI
modes.
NOTE: Configure either
RTIO
and
LIMT
or
RES.S
. Do not use
all three.
7. See the Economizer Options section on page 34 for addi-
tional economizer option configurations.
8. See the Exhaust Options section on page 34 for addition
exhaust option configurations.
Multi-Stage CV Units with Mechanical Thermostat
To configure the unit, perform the following:
1. Under
Configuration
UNIT
C.TYP
, set
C.TYP
to 3
(TSTAT MULTI).
2. Under the
Setpoints
menu, set the following configurations:
3. See the Economizer Options section on page 34 for addi-
tional economizer option configurations.
4. See the Exhaust Options section on page 34 for additional
exhaust option configurations.
Multi-Stage CV Units with Space Sensor
To configure the unit, perform the following:
1. Under
Configuration
UNIT
C.TYP
, set
C.TYP
to 4
(SPT MULTI).
2. Under the
Setpoints
menu, the following configurations
should be set:
3. Under the
Setpoints
submenu, the heating and cooling set
points must be configured:
4. Under
Configuration
UNIT
SENS
SPT.S
, enable
the space sensor by setting
SPT.S
to ENBL.
5. Under
Configuration
UNIT
FN.MD
, set
FN.MD
to 1
for continuous fan or 0 for automatic fan.
6. To program time schedules, set
SCH.N
=1 under
Configu-
ration
CCN
SC.OV
SCH.N
to configure the control
to use local schedules.
7. Under the
Timeclock
SCH.L
submenu, enter the desired
schedule. See Time Clock section for further descriptions
of these configurations.
8. See the Economizer Options section on page 34 for addi-
tional economizer option configurations.
9. See the Exhaust Options section on page 34 for additional
exhaust option configurations.
OHSP
Occupied Heat Setpoint
OCSP
Occupied Cool Setpoint
UHSP
Unoccupied Heat Setpoint
UCSP
Unoccupied Cool Setpoint
GAP
Heat-Cool Setpoint Gap
V.C.ON
VAV Occupied Cool On Delta
V.C.OF
VAV Occupied Cool Off Delta
L.H.ON
Demand Level Low Heat On
L.H.OF
Demand Level Low Heat Off
RS.CF
EDT Reset Configuration
RTIO
Reset Ratio
LIMT
Reset Limit
RES.S
EDT 4-20 mA Reset Input
SA.HI
Supply Air Set Point Hi
SA.LO
Supply Air Set Point Lo
SA.HI
Supply Air Set Point Hi
SA.LO
Supply Air Set Point Lo
OHSP
Occupied Heat Setpoint
OCSP
Occupied Cool Setpoint
UHSP
Unoccupied Heat Setpoint
UCSP
Unoccupied Cool Setpoint
GAP
Heat-Cool Setpoint Gap
D.LV.T
Cool/Heat Set Point Offsets (located in the
Configuration
menu)
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...