Fig. 52 — Condenser-Fan Adjustment
(All Units Except Size 035)
CONDENSER FAN ADJUSTMENT (SIZE 035)
Each fan is supported by a formed wire mount bolted to a fan deck
and covered with a wire guard. The exposed end of the fan motor
shaft is protected from weather by grease. If the fan motor must be
removed for service or replacement, be sure to regrease fan shaft
and reinstall fan cover, retaining clips, and fan guard. For proper
performance, the fans should be positioned as shown in Fig. 53.
Tighten setscrews to 14
1 ft-lb (18
1.3 N-m).
Check for proper rotation of the fan(s) once reinstalled (coun-
terclockwise viewed from above). If necessary to reverse,
switch leads at contactor(s) in control box.
Fig. 53 — Condenser Fan Position (Size 035 Units)
AIR PRESSURE TRANSDUCER FIELD ADJUSTMENT
All transducers have been factory calibrated and should not re-
quire field adjustment. If field adjustment is necessary, follow
the instructions below. To re-calibrate a transducer:
1. Shut the unit power off.
2. Take the wiring and pressure tubing off the transducer.
Take the transducer out of the unit.
3. Connect a 24-vdc power supply to transducer terminals
EXC(+) and COM(–). See Fig. 54.
4. Using a digital multimeter measure the current between
terminals EXC(+) and OUT.
5. With both pressure ports open to atmosphere, adjust the
Zero (Z) screw potentiometer on the transducer and read
the multimeter until the desired current output at 0 in. wg
pressure is obtained (see Fig. 54).
6. Reinstall the transducer in the unit.
7. Restore power to the unit.
Fig. 54 — Transducer Details
Cleaning
Inspect unit at the beginning of each heating and cooling season
and during each season as operating conditions may require.
MICROCHANNEL HEAT EXCHANGER (MCHX)
CONDENSER COIL MAINTENANCE AND CLEANING
RECOMMENDATIONS
Routine cleaning of coil surfaces is essential to maintain proper
operation of the unit. Elimination of contamination and remov-
al of harmful residues will greatly increase the life of the coil
and extend the life of the unit. The following steps should be
taken to clean MCHX condenser coils:
1. Remove any foreign objects or debris attached to the coil
face or trapped within the mounting frame and brackets.
2. Put on personal protective equipment including safety
glasses and/or face shield, waterproof clothing and gloves.
It is recommended to use full coverage clothing.
3. Start high pressure water sprayer and purge any soap or
industrial cleaners from sprayer before cleaning condenser
coils. Only clean potable water is authorized for cleaning
condenser coils.
4. Clean condenser face by spraying the coil steady and uni-
formly from top to bottom while directing the spray
straight toward the coil. Do not exceed 900 psig or
30 degree angle. The nozzle must be at least 12-in. from
the coil face. Reduce pressure and use caution to prevent
damage to air centers.
PLASTIC FAN
PROPELLER
CLEARANCE OF 0.25 INCHES
(6.4 MM) FOR STANDARD
CONDENSER FANS
FAN DECK
SURFACE
FAN ORIFICE
TRANSDUCER
PART
NUMBER
INPUT
RANGE
(in. wg)
OUTPUT
RANGE
OUTPUT
AT 0 IN. WG
USAGE
HK05ZG019
0 to 5
4 to 20 mA
4 mA
Supply Duct/
Air Foil
Fan Cfm
HK05ZG020
0 to 1
4 to 20 mA
4 mA
Forward
Curved
Fan Cfm
HK05ZG021
0 to 15
4 to 20 mA
4 mA
Return/
Exhaust
Fan Cfm
HK05ZG022
–0.25 to 0.25 4 to 20 mA
12 mA
Building
Pressure
CAUTION
UNIT DAMAGE HAZARD
Do not apply any chemical cleaners to MCHX condenser
coils. These cleaners can accelerate corrosion and damage
the coil.
PRE
SS
URE POR
T
S
LOW
HIGH
S
Z
COM OUT EXC
Summary of Contents for Weathermaster 48P2030-100
Page 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Page 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Page 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Page 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Page 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Page 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Page 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Page 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Page 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Page 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...