54
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The
actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should
drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal after
completing troubleshooting.
EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to operation.
No troubleshooting or testing is done by performing the following
procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previous
setting.
4. Set minimum position, DCV set point, and exhaust poten-
tiometers to previous settings.
5. Remove 620-ohm resistor from terminals SR and +.
6. Remove 1.2 kilo-ohm checkout resistor from terminals SO
and +. If used, reconnect sensor from terminals SO and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Reconnect
wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and
P1.
11. Apply power (24 vac) to terminals TR and TR1.
EconoMi$er
®
X (Factory Option)
The EconoMi$er X system is an expandable economizer control
system, which includes a W7220 economizer module (controller)
with an LCD and keypad (see Fig. 78). The W7220 can be config-
ured with optional sensors.
Fig. 78 — W7220 Economizer Module
The W7220 economizer module can be used as a stand-alone
economizer module wired directly to a commercial set-back space
thermostat and sensors to provide outside air dry-bulb economizer
control.
The W7220 economizer module can be connected to optional
sensors for single or differential enthalpy control. The W7220
economizer module provides power and communications for the
sensors.
The W7220 economizer module automatically detects sensors by
polling to determine which sensors are present. If a sensor loses
communications after it has been detected, the W7220 economizer
controller indicates a device fail error on its LCD.
SYSTEM COMPONENTS
The EconoMi$er X system includes an economizer module, 20k
mixed air sensor, damper actuator, and either a 20k outdoor air
temperature sensor or S-Bus enthalpy sensors.
Economizer Module
The module is the core of the EconoMi$er X system. The module
is mounted in the unit’s control box, and includes the user
interface for the system. The W7220 economizer module provides
the basic inputs and outputs to provide simple economizer control.
When used with the optional sensors, the economizer module
provides more advanced economizer functionality.
S-Bus Enthalpy Control Sensors
The sensor is a combination temperature and humidity sensor
which is powered by and communicates on the S-Bus. Up to three
sensors may be configured with the W7220 economizer module.
CO
2
Sensor (optional)
The CO
2
sensor can be added for Demand Controlled Ventilation
(DCV).
SPECIFICATIONS
W7220 Economizer Module
The module is designed for use with 2 to 10 vdc or bus communi-
cating actuator. The module includes terminals for CO
2
sensor,
Mixed Air sensor, and an Outdoor Dry Bulb sensor. Enthalpy and
other options are available with bus sensors.
User Interface
Provides status for normal operation, setup parameters, checkout
tests, and alarm and error conditions with a 2-line 16 character
LCD display and four button keypad.
Electrical
• Rated Voltage —
20 to 30 vac RMS, 50/60 Hz
• Transformer — 100 va maximum system input
• Nominal Power Consumption (at 24 vac, 60 Hz) —
11.5 VA without sensors or actuators
• Relay Digital Output Rating at 30 vac (maximum power
from Class 2 input only) — 1.5A run:
3.5A inrush at 0.45PF (200,000 cycles) or
7.5A inrush at 0.45PF (100,000 cycles)
• External Sensors Power Output — 21 vdc ± 5% at 48mA
INPUTS
Sensors
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor for dry bulb
change over or an OA bus sensor for outdoor enthalpy change
over is required in addition to the MA sensor. An additional
Return Air (RA) bus sensor can be added to the system for dif-
ferential enthalpy or dry bulb changeover. For differential dry
bulb changeover, a 20k ohm sensor is required in the OA and a
bus sensor in the RA. DIP switch on RA bus sensor must be set
in the RA position.
Dry Bulb Temperature (optional) and Mixed Air (required),
20k NTC
2-wire (18 to 22 AWG);
Temperature range –40°F to 150°F (–40°C to 66°C)
Temperature accuracy: 0°F/+2°F
Temperature and Humidity, C7400S1000 (optional)
S-Bus; 2-wire (18 to 22 AWG)
Temperature: range –40°F to 150°F (–40°C to 65°C)
Temperature accuracy: 0°F/+2°F (–18°C/–17°C)
IMPORTANT: All inputs and outputs must be Class 2
wiring.
Summary of Contents for WeatherMaster 48HC04 Series
Page 37: ...37 Fig 60 Integrated Gas Control IGC Board RED LED STATUS ...
Page 45: ...45 Fig 65 RTU Open Overlay for Economizer Wiring ...
Page 46: ...46 Fig 66 VFD Overlay for W2770 Controller Wiring ...
Page 98: ...98 Fig E 48HC A07 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 100: ...100 Fig G 48HC D11YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 101: ...101 Fig H 48HC D12 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 102: ...102 Fig I 48HC A04 A06 YAC Power Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Page 103: ...103 Fig J 48HC A04 A06 YAC Power Diagram 208 230 3 60 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 104: ...104 Fig K 48HC A04 A06 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 107: ...107 Fig N 48HC A07 A12 YAC Power Diagram 208 230 3 60 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 108: ...108 Fig O 48HC A07 A12 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 109: ...109 Fig P 48HC D08 D09 YAC Power Diagram 230 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 110: ...110 Fig Q 48HC D08 D09 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 111: ...111 Fig R 48HC D11 YAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 112: ...112 Fig S 48HC D11 YAC Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 113: ...113 Fig T 48HC D11 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 114: ...114 Fig U 48HC D12 YAC Power Diagram 230 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 115: ...115 Fig V 48HC D12 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 116: ...116 Fig W 48HC D14 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 117: ...117 Fig X 48HC D14 YAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 118: ...118 Fig Y 48HC D14 YAC Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 119: ...119 Fig Z 48HC D14 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 142: ...142 Fig AW PremierLink System Control Wiring Diagram System APPENDIX D WIRING DIAGRAMS ...
Page 144: ...144 Fig AY RTU Open Wiring Diagram APPENDIX D WIRING DIAGRAMS ...