Each status code is a two-digit number. The  rst number is determined by the number of short  ashes and the
second digit by the number of long  ashes.

When to call a professional to repair your Carrier

furnace

Error
Code 1-
2

The blower is on after
power up

Blower runs for 90 seconds if the unit is powered up during a call for heat.

Error
Code 2-
4

Secondary voltage
fuse is open

Check for a short circuit in the secondary voltage wiring.

Error
Code 3-
1

Pressure, draft
safeguard, aux-limit
switch, or blocked
vent switch didn’t
close (or reopened,
down ow only)

If open for longer than 5 minutes, the inducer will shut off for 15 minutes before retry. Check for: low inducer
voltage; proper vent sizing; defective inducer motor; defective blower motor or capacitor; defective pressure
switch; restricted vent; excessive wind, inadequate combustion air supply; or obstructed pressure tubing.

Error
Code 2-
3

Pressure switch
didn’t open

Check for an obstruction in the pressure tubing or a pressure switch that is stuck closed.

Error
Code 1-1

No previous code

Stored status codes are erased when power to control is interrupted.

Rapid
LED

ashing

Line voltage polarity
is reversed.

If twinned, refer to twinning kit instructions.

Error
Code 1-
3

Limit or  ame roll-out
switch lockout

Control will auto-reset after 3 hours. Reset the switch or replace fuse link.

Error
Code 3-
3

Limit or  ame roll-out
switch is open

If the switch is open for longer than 3 minutes, the code will change to #1-3. Flame roll-out switch requires
manual reset. Check for: defective blower motor or capacitor; dirty  lter or restricted duct system; loose
blower wheel; faulty switch or connections; or inadequate combustion air supply.

Error
Code 3-
4

Ignition proving
failure

Control will try three more times before lockout #1-4 will occur. If the  ame signal is lost after the trial for
ignition period, the blower will come on for a 90 second recycle delay. Check for: build-up on the  ame
sensor; proper microamp distribution to the  ame sensor; defective gas valve or turned off gas valve; faulty
hot surface ignitor; low inlet gas pressure; the manual valve is shut-off; continuity of control ground; low

ame carryover or rough ignition; ungrounded  ame sensor.

Error
Code 1-
4

Ignition lockout

Control will auto-reset after 3 hours.

Error
Code 2-
1

Gas heating lockout

Control won’t auto-reset. Check for either a badly-wired gas valve or a defective control.

Error
Code 2-
2

Abnormal  ame-
proving signal

Flame is proved while the gas valve is de-energized. Check for either a leaky or stuck-open gas valve.