12
7. Install condensate line trap and piping
8. Make electrical connections
9. Install other accessories
FRAME-MOUNTED INSTALLATION
Frame-mounted applications generally follow the sequence for
a curb installation. Adapt as required to suit specific installa-
tion plan.
Step 3 — Inspect Unit
Inspect unit for transportation damage. File any claim with
transportation agency.
Confirm before installation of unit that voltage, amperage and
circuit protection requirements listed on unit data plate agree
with power supply provided.
On units with hinged panel option, check to be sure all latches
are snug and in closed position.
Locate the carton containing the outside air hood parts (see
Fig. 16 on page 16). Do not remove carton until unit has been
rigged and located in final position.
Step 4 — Provide Unit Support
ROOF CURB MOUNT
Accessory roof curb details and dimensions are shown in
Fig. 9. Assemble and install accessory roof curb in accordance
with instructions shipped with the curb.
NOTE: The gasketing of the unit to the roof curb is critical for a
watertight seal. Install gasket supplied with the roof curb as shown
in Fig. 9. Improperly applied gasket can also result in air leaks and
poor unit performance.
Curb should be level. This is necessary for unit drain to func-
tion properly. Unit leveling tolerances are shown in Fig. 8. Re-
fer to Accessory Roof Curb Installation Instructions for addi-
tional information as required.
Fig. 8 — Unit Leveling Tolerances
Install insulation, cant strips, roofing felt, and counter flashing
as shown.
Ductwork must be attached to curb and not to the
unit. The accessory thru-the-base power package must be in-
stalled before the unit is set on the roof curb.
If electric and control wiring is to be routed through the basepan,
attach the accessory thru-the-base service connections to the base-
pan in accordance with the accessory installation instructions.
SLAB MOUNT (HORIZONTAL UNITS ONLY)
Provide a level concrete slab that extends a minimum of 6-in.
(150 mm) beyond unit cabinet. Install a gravel apron in front of
condenser coil air inlet to prevent grass and foliage from ob-
structing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
SLAB MOUNT)
A non-combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the long
sides of the unit with a minimum of 3 equally spaced 4-in. x
4-in. (102 mm x 102 mm) pads on each side.
A-B
0.5″ (13)
B-C
1.0″ (25)
A-C
1.0″ (25)
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
Summary of Contents for WeatherMaker 50TCQ*08
Page 4: ...4 Fig 2 Unit Dimensional Drawing 08 and 09 Size Units ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing 08 and 09 Size Units cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing 12 Size Unit ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing 12 Size Unit cont ...
Page 19: ...19 Fig 25 Typical 50TCQ Control Wiring Diagram Sizes 08 09 ...
Page 20: ...20 Fig 26 Typical 50TCQ Control Wiring Diagram Size 12 ...
Page 21: ...21 Fig 27 50TCQ 08 09 Power Wiring Diagram ...
Page 22: ...22 Fig 28 Typical 50TCQ 12 Power Wiring Diagram 208 230 v 3 Phase 60Hz Unit Shown ...
Page 45: ......