Fig. 10 — Rigging Details
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without
factory-installed economizer or return-air smoke detector op-
tion may be field-converted to horizontal ducted configuration.
To convert to horizontal configuration, remove screws from
side duct opening covers (see Fig. 11) and remove covers. Use
the screws to install the covers on vertical duct openings with
the insulation-side down. The panels must be inserted into the
notches on the basepan to properly seal. The notches are cov-
ered by the tape used to secure the insulation to the basepan
and are not easily seen. See Fig. 12 for position of the notches
in the basepan. Seals around duct openings must be tight. Se-
cure with screws as shown in Fig. 13. Cover seams with foil
duct tape.
Field-supplied flanges should be attached to horizontal duct
openings and all ductwork should be secured to the flanges. In-
sulate and weatherproof all external ductwork, joints, and roof
or building openings with counter flashing and mastic in accor-
dance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data
plate when insulating horizontal ductwork.
Fig. 11 — Horizontal Conversion Panels
Fig. 12 — Location of Notches
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.
”
Holes in base rails are centered around the unit center of gravity. Use
wooden top to prevent rigging straps from damaging unit.
UNIT
MAX WEIGHT
DIMENSIONS
A
B
C
LB
KG
IN.
MM
IN.
MM
IN.
MM
50TCQD08
1235
560
88.13
2238
39.94
1014
49.38
1253
50TCQD09
1260
572
88.13
2238
39.63
1006
49.38
1253
50TCQD12
1695
770
88.0
2235
36.5
925
49.5
1255
REMOVABLE HORIZONTAL
SUPPLY DUCT OPENING COVER
REMOVABLE HORIZONTAL
RETURN DUCT OPENING COVER
BASEPAN
NOTCHES
NOTCHES
Summary of Contents for WeatherMaker 50TCQ*08
Page 4: ...4 Fig 2 Unit Dimensional Drawing 08 and 09 Size Units ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing 08 and 09 Size Units cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing 12 Size Unit ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing 12 Size Unit cont ...
Page 19: ...19 Fig 25 Typical 50TCQ Control Wiring Diagram Sizes 08 09 ...
Page 20: ...20 Fig 26 Typical 50TCQ Control Wiring Diagram Size 12 ...
Page 21: ...21 Fig 27 50TCQ 08 09 Power Wiring Diagram ...
Page 22: ...22 Fig 28 Typical 50TCQ 12 Power Wiring Diagram 208 230 v 3 Phase 60Hz Unit Shown ...
Page 45: ......