*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y–I and
Y2–I have not been satisfied.
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for sec-
ond stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y–I and
Y2–I have not been satisfied.
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for sec-
ond stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y–I and
Y2–I have not been satisfied.
Table 19 —
Enthalpy Operation without DCV (CO
2
Sensor) — 1 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
NONE
No
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
24-v/On
0-v/Off
MIN POS
Closed
On
On
High
24-v/On
24-v/On
MIN POS
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
0-v/Off
0-v/Off
MIN POS to
Full-Open
Closed to
Full-Open
On
On
High
24-v/On
0-v/Off*
MIN POS to
Full-Open
Closed to
Full-Open
Table 20 —
Enthalpy Operation with DCV (CO
2
Sensor) — 1 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
Below CO
2
set
No
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN
Closed
On
On
High
24-v/On
24-v/On
VENTMIN
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to
Full-Open
Closed to
Full-Open
On
On
High
24-v/On
0-v/Off†
VENTMIN to
Full-Open
Closed to
Full-Open
Above CO
2
set
No
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to
VENTMAX
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
On
High
24-v/On
24-v/On
VENTMIN H to
VENTMAX
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
VENTMIN L to
VENTMAX
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to
Full-Open
Closed to
Full-Open
On
On
High
DELAY*
24-v/On
0-v/Off†
VENTMIN to
Full-Open
Closed to
Full-Open
Table 21 —
Dry Bulb Operation without DCV (CO
2
Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
NONE
No
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
24-v/On
0-v/Off
MIN POS L
Closed
On
On
High
24-v/On
24-v/On
MIN POS H
Closed
NONE
Yes
Off
Off
Low
0-v/Off
0-v/Off
MIN POS L
Closed
On
Off
Low
0-v/Off
0-v/Off
MIN POS L
to Full-Open
Closed to
Full-Open
On
On
High
DELAY*
24-v/On
0-v/Off†
MIN POS H
to Full-Open
Closed to
Full-Open
Summary of Contents for WeatherMaker 50TC 17-30 Series
Page 34: ...34 Fig 48 RTU Open Overlay for Economizer Wiring ...
Page 35: ...35 Fig 49 VFD Overlay for W2770 Controller Wiring ...
Page 80: ...80 Fig C 50TC 17 28 Control Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 81: ...81 Fig D 50TC 30 Control Wiring Diagram 208 230 3 60 Units APPENDIX D WIRING DIAGRAMS ...
Page 82: ...82 Fig E 50TC 30 Control Wiring Diagram 460 3 60 575 3 60 Units APPENDIX D WIRING DIAGRAMS ...
Page 83: ...83 Fig F 50TC 17 30 Power Wiring Diagram 208 230 3 60 Units APPENDIX D WIRING DIAGRAMS ...
Page 84: ...84 Fig G 50TC 17 30 Power Wiring Diagram 460 3 60 575 3 60 Units APPENDIX D WIRING DIAGRAMS ...
Page 89: ...89 Fig L 50TC PremierLink System Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 90: ...90 Fig M 50TC RTU Open Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 91: ...91 Fig N 50TC SAV VFD System Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 93: ......