56
Fig. 81 —
V-Belt Force Label
BELT TENSION METHOD
Requires belt tension gage that measures tension in belt in units of
lbs force.
Fig. 82 —
Belt Drive Motor Mounting
Pre-Start and Start-Up
This completes the mechanical installation of the unit. Refer to the
unit’s Service Manual for detailed Pre-Start and Start-Up instruc
-
tions. Download the latest versions from HVAC Partners
(www.hvacpartners.com).
Troubleshooting the Ultra Tech™ Compressor
The Ultra Tech
1
compressor’s molded plug should be used at all
times. The maximum power is 5A.
MODULATION CONTROL INPUT SPECIFICATIONS
The compressor will modulate from part load to full load when the
voltage supplied to the molded plug is 18 to 28vdc or 18 to 28 vac
rectified to vdc. The compressor will modulate from full load to
part load when the current in the circuit drops below 0.9 MA. See
Table 24 and Fig. 83 for details.
TORQUE ALL SHEAVE SET SCREWS TO 110-130 in. lbs
SET
SCREW
SET
SCREW
STRAIGHT
EDGE
BELT SPAN
BELT DEFLECTION FORCE - SEE TABLE 1
DEFLECTION = BELT SPAN
64
Table 1
Table 2
BELT
CROSS
SECTION
SMALLEST
SHEAVE
DIAMETER
BELT DEFLECTION FORCE (LBS)
UNNOTCHED
BELTS
NOTCHED BELTS
USED
NEW
USED
NEW
A, AX
3.0-3.6
3.7
5.5
4.1
6.1
3.8-4.8
4.5
6.8
5.0
7.4
5.0-7.0
5.4
8.0
5.7
8.4
B, BX
3.4-4.2
—
—
4.9
7.2
4.4-5.6
5.3
7.9
7.1
10.5
5.8-8.6
6.3
9.4
8.5
12.6
BELT CONDITION
TENSION FORCE IN BELT (LBS)
New
100
Used
80
1. UltraTech™ is a trademark of Emerson Climate Technologies, Inc.
BLOWER PULLEY
V-BELT
MOTOR
PULLEY
MOTOR
MOTOR MOUNTING
PLATE
MOUNTING
BOLTS (4)
Table 24 —
Troubleshooting Ultra Tech Compressor
STAGE
CAPACITY
METERING
LIQUID LINE
SOLENOID
COMPRESSOR
UNLOADER
FOR ULTRA TECH
COMPRESSOR
TROUBLESHOOTING
(COMPRESSOR CURRENT)
FOR LIQUID LINE SOLENOID
VALVE TROUBLESHOOTING
(TOP EVAPORATOR COIL
TEMPERATURE)
Y1
Part Load
(66%)
TXV
Closed (De-
energized)
De-energized
Approx. 80% or less
Top section of the evaporator coil
will not be cold (U-bend tubes)
Y1+Y2
Full Load
(100%)
TXV+Fixed Open (Energized)
Energized
100%
Top section of the evaporator coil
will be cold (U-bend tubes)
Summary of Contents for WeatherMaker 48TC A/B07 Series
Page 5: ...5 Fig 2 Dimensional Drawing for Units Built On and After 4 15 19 Size 07 ...
Page 6: ...6 Fig 3 Dimensional Drawing for Units Built Prior To 4 15 19 Size 07 ...
Page 7: ...7 Fig 4 Unit Corner Weights and Clearances Size 07 ...
Page 8: ...8 Fig 5 Base Rail Details Size 07 ...
Page 9: ...9 Fig 6 Thru the Base Charts Size 07 ...
Page 10: ...10 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 11: ...11 Fig 7 Unit Dimensional Drawing Size 08 09 12 ...
Page 12: ...12 Fig 8 Unit Dimensional Drawing Size 14 ...
Page 13: ...13 Fig 8 Unit Dimensional Drawing Size 14 cont ...
Page 14: ...14 Fig 9 Unit Dimensional Drawing Size 16 ...
Page 15: ...15 Fig 9 Unit Dimensional Drawing Size 16 cont ...
Page 20: ...20 Fig 14 48TC 16 Roof Curb Details ...
Page 39: ...39 Fig 69 48TC 07 14 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 40: ...40 Fig 70 48TC 16 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Page 57: ...57 Fig 83 Ultra Tech Scroll Compressor Diagram ...