Integrated Staging Control (ISC)
SEQUENCE OF OPERATION
The Carrier Integrated Staging Control (ISC) is intended for use
with a standard thermostat, direct digital controls (DDC) capable
of three cooling stages, or the VAV-RTU Open controller (for
LC*B units). After initial power to the board, a Green LED will
blink with a 1 second duty cycle indicating the unit is running
properly. In the event of the ISC board failing, the Green LED will
be OFF or continuously ON. When the unit is not running proper
-
ly, the Green LED will blink along with Red LED lights. The Red
LED light configuration will indicate the type of error the board
has identified. See Fig. 65 for LED locations and Table 3 for a list
of status codes.
The ISC board can be remotely shutdown by removing Jumper 4
and wiring to the Remote Shutdown terminal. The Smoke Control
Module can shutdown the unit by removing Jumper 3 and wiring
to the Smoke Shutdown terminal. The Smoke Alarm terminal on
the ISC Board provides a pass thru connection should a smoke
alarm signal be connected. In the case of the RTU Open option,
the RTU Open controller provides the signal which is passed
through the ISC board to the Smoke Alarm terminal.
The crankcase heater will run at all times except when the com
-
pressors are running. An auxiliary power supply (24Vac) available
at TB-4 Terminal is provided to power auxiliary equipment. An
optional Phase Monitor Relay can be wired to the PMR terminal
by removing Jumper 5. An optional Condensate Flow Switch can
be wired to the COFS Terminal by removing Jumper 7.
Fig. 65 —
Integrated Staging Control (ISC) Board
DDC
Control
Indoor Fan
“On” Status
IGC
Board
Power
Plug
Phase
Monitor
Relay
Auxilary
Shutdown
Condensate
Overflow
Economizer
Occupancy
Status Code LEDs
Thermostat
DDC
Control
Remote
Shutdown
Smoke
Shutdown
Smoke
Alarm
Low Ambient
Outdoor Fan
Control
Compressors
Reheat
Low-Pressure
Switch
High-Pressure
Switch
Indoor Fan
Motor
Outdoor Fan
Motors
Phase
Monitor
Relay
Summary of Contents for WeatherExpert 50LC14
Page 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Page 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Page 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Page 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Page 8: ...8 Fig 6 50LC Bottom View Size 14...
Page 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Page 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Page 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Page 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Page 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Page 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Page 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Page 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Page 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Page 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Page 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Page 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Page 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Page 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Page 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Page 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Page 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Page 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Page 80: ......
Page 81: ......