28
Fig. 36 —
CRBARHOD001A00 Hood Sides and Top
Caulk the backside of the mating flanges to ensure a watertight
seal. Install the CRBARHOD001A00 over the relief damper and
screw to the return duct, as illustrated in Fig. 35.
Step 10 — Economizer – Horizontal Airflow Units
The barometric relief damper ships attached to the exterior return
opening panel on the unit. See Fig. 37. Remove shipping cover to
access the barometric relief damper, rain angle, and parts bag.
These items are to be repositioned on the side of the field supplied
ductwork. In addition, the barometric relief hood should be used
and can be ordered separately (P/N CRBARHOD001A00) or can
be field supplied.
Fig. 37 — Barometric Relief Damper — Shipping
Location
Step 11 —
Install External Condensate Trap/Line
The unit has one
3
/
4
-in. condensate drain connection on the end of
the condensate pan. See Fig. 38. See Fig. 4, 9, and 14, Item E in
the view labeled “BACK (HORIZONTAL DISCHARGE W/O
ECON)” for the location of the condensate drain connection.
Fig. 38 —
Condensate Drain Pan Connection
The piping for the condensate drain and external trap can be com
-
pleted after the unit is in place. Hand-tighten fittings to the drain
pan fitting. Provide adequate support for the drain line. Failure to
do so can result in damage to the drain pan. See Fig. 39.
Fig. 39 —
Condensate Drain Pan Piping Details
All units must have an external trap for condensate drainage. In
-
stall a trap at least 4-in. (102 mm) deep and protect against
freeze-up. If drain line is installed downstream from the external
trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm
per 3 m) of run. Do not use a pipe size smaller than the unit con
-
nection (
3
/
4
-in.).
Step 12 —
Make Electrical Connections
NOTE: Field-supplied wiring shall conform with the limitations
of minimum 63°F (33°C) rise.
SHIPPING
COVER
BAROMETRIC
RELIEF
DAMPER
RETURN
OPENING
PANEL
RAIN ANGLE
WARNING
ELECTRIC SHOCK HAZARD
Failure to follow this warning could result in personal injury or
death.
Unit cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if an
electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control
compartment, or conduit approved for electrical ground when
installed in accordance with NEC; ANSI/NFPA 70, latest
edition (in Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical codes.
CONDENSATE
DRAIN
CONNECTION
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. (102 mm) trap is recommended.
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
BASE RAIL
OPEN
VENT
TO ROOF
DRAIN
DRAIN PLUG
ROOF
CURB
SEE NOTE
3 in. (76 mm)
MIN
Summary of Contents for WeatherExpert 50LC14
Page 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Page 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Page 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Page 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Page 8: ...8 Fig 6 50LC Bottom View Size 14...
Page 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Page 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Page 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Page 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Page 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Page 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Page 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Page 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Page 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Page 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Page 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Page 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Page 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Page 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Page 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Page 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Page 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Page 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Page 80: ......
Page 81: ......