Start-up
UPC Open
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Integration Guide
All rights reserved
14
Use one of the following interfaces to start up, access information, read sensor values, and test the controller.
This interface...
Provides a...
Field Assistant
application -
Runs on a laptop that connects to controller's Local Access port
1
Temporary interface
Equipment Touch
device -
Connects to controller's Rnet port
2
Temporary or permanent
interface
i-Vu®
application
Available for BACnet systems only
Permanent interface
System Touch
device
Available only for BACnet MS/TP systems.
Wire to a BACnet MS/TP network connector and a 24 Vac power supply
3
Temporary or permanent
interface
1
Requires a USB Link (Part #USB-L).
2
See the
Equipment Touch Installation and Setup Guide
for detailed instructions.
3
See the
System Touch Installation and Setup Guide
for detailed instructions.
CAUTION
If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.
Select or create a custom control program and graphic for the UPC Open
The field-installed UPC Open does not come from the factory with a control program or graphic. You must load a
control program and graphic as part of the installation/commissioning of the UPC Open. You can select a control
program and graphic from EquipmentBuilder that has all the configurations that are currently available on a
factory-installed UPC Open. You can also create a custom control program using Snap. See Snap Help for details.
NOTES
•
You MUST have installed the February 2017 or later cumulative update and the 6.04.xxx or later driver to be
able to create custom control programs, .view files, or .touch files for the ZS sensors, wireless sensors, or
touchscreen.
•
Third party mapping information for current Carrier PIC products, whether on a factory-installed UPC Open or
selected from EquipmentBuilder, can be found on the
Carrier Control Systems Support Site
under
Support Center
>
Controls Support
>
Controls Product Information
.
Start-up