Adjusting the TV-UCXP683T-V driver properties
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
46
Communication Status
The
Communication Status
page shows the status of the protocols currently running on the TV-UCXP683T-V's
ports.
Standalone Controller Detection
You can use the fields on this page with a binary input in your control program to detect when the controller does
not receive a write request from the selected network within the specified amount of time. The input remains OFF
as long as write requests are received, but switches to ON if the controller does not receive a request within the
specified time. The binary input must have the Expander number and Input number set to
99
and the I/O Type set
to
Special
.
Modbus Serial, Modbus TCP/IP, and Modbus Error Definitions pages
If the controller will be used with Modbus devices, see the
Modbus Integration Guide
for information on using
these pages.
Flow Calibration Archive
NOTE
This driver property only applies to controllers with built-in airflow sensors.
The
Flow Calibration Archive
page shows measured flow and sensor readings that were entered in the i-Vu® Test
and Balance tool or through the stand-alone Test & Balance Utility.
To set up Network Statistic trends
PREREQUISITE
To view Network Statistic trends, you must have a i-Vu® v6.5 or later system with the latest
cumulative patch.
To view the
Network Statistics
(page 42) as trend graphs, select the controller in i-Vu®'s navigation tree and go to
one of the following:
•
On the
Driver Properties
>
Network Diagnostics
>
Statistics
page, click a
Trend
link at the bottom of each
section.
•
Click the
Trends
drop-down button, select
Enabled Points
and then the graph you want.