![Carrier Transicold X4 7300 Operation & Service Manual Download Page 167](http://html1.mh-extra.com/html/carrier/transicold-x4-7300/transicold-x4-7300_operation-and-service-manual_2564193167.webp)
7–41
62-11637
00097
CHECK SV2 CIRCUIT
• ACTIVATION: A problem has been detected in the SV2 coil circuit . If this alarm is activated while the con-
trol system is calling for SV2 to be energized, the circuit is detected shorted. If this alarm is activated at any
other time, the circuit is detected open.
• UNIT CONTROL: Alarm only.
• RESET CONDITION: Auto reset when unit calls for cooling and the SV2 coil circuit is normal, or Alarm may
be manually reset using the display mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any
active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check Coil
a. Inspect coil & connector pins & terminals. Verify no damage to coil. Verify no damaged or corroded pins.
b. Check resistance of coil. Refer to
for specifications.
c. Use Component Test Mode (Refer to
) to test actual current draw of the circuit. Refer to
for specifications. Verify that the actual current is within specifications.
2. Check Power and Wiring
a. Use Component Test Mode (Refer to
) to energize circuit. Check for power at SV2 termi-
nal A and 3MM-2. Minimum 11 VDC. If not, check connectors and wiring between terminals. Verify no
damage, moisture or corrosion.
b. Check for ground at SV2 terminal B (including SP-3) to GND RING1. Good ground. If not, check con-
nectors and wiring between terminals. Verify no damage, moisture or corrosion.
00121
CHECK AMBIENT AIR SENSOR
• ACTIVATION: Ambient Air Temperature Sensor (ATA) is not within range of -53 to +158°F (-47° to +70° C).
• UNIT CONTROL: Alarm and a value of 122°F (50°C) will be used for any calculations.
• RESET CONDITION: Auto reset when sensor is in range or alarm may be manually reset using the display
mounted keys or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
CORRECTIVE ACTIONS:
1.
Check Sensor
a. Inspect sensor & connector. Verify no damage to sensor. Verify no damage, moisture, or corrosion in
connector.
b. Check sensor resistance. (Refer to Note 3 in
Section, page 7-2.) 10,000 Ohms @ 77°F
for chart of resistances for different sensors.
2.
Check Sensor Wiring
a. Inspect connector pins & terminals at sensor and connector 2MM. (See wiring schematic
.)
Verify there is no physical damage to harness, and no damage, moisture, or corrosion in connectors.
b. Place the system in PC Mode. Refer to Note 2 in
Section, page 7-2. Disconnect sensor from
harness. Check for 3.0 ± 0.1 VDC at harness plug between pins. Voltage should be 3.0 ± 0.1 VDC
volts at harness plug between pins. This verifies microprocessor output and wiring connections to
the sensor.
Summary of Contents for Transicold X4 7300
Page 21: ...62 11637 1 6 1 3 SAFETY DECALS ...
Page 22: ...1 7 62 11637 62 03958 ...
Page 23: ...62 11637 1 8 ...
Page 24: ...1 9 62 11637 ...
Page 119: ...62 11637 SECTION 6 MESSAGECENTER PARAGRAPH NUMBER Page 6 1 MESSAGECENTER MESSAGES 6 1 ...
Page 278: ......