background image

I

N
D
O
O

U
N

I

CONNECT THE CABLE TO THE INDOOR UNIT

Minimum nominal cross-sectional area of  conductors: 

Rated cur rent 

of  a ppliance

(A)

>3  and  

6

>6  and  

10

>10  and  

16

>16  and  

25

Nominal cross-sectional 

area

(mm2)

0.75

1

1.5
2.5

The cable size and the current of thefuse
 or switch are determined by the maximum
 current indicated on the nameplate which 
located on the side panel of the unit. 
Please refer to the nameplate before 
selecting the cable, fuse and switch.
  

,

Install the outdoor unit on a rigid base to prevent increasing noise level and vibration.
Determine the air outlet direction where the discharged air is not blocked.
In the case that the installation place is exposed to strong wind such as a seaside, make 
sure the fan operating properly by putting the unit lengthwise along the wall or using a dust 
or shield plates.
Specially in windy area, install the unit to prevent the admission of wind. If need suspending 
installation, the installation bracket should accord with technique requirement in the 
installation bracket diagram. The installation wall should be solid brick, concrete or the same 
intensity construction, or actions to reinforce, damping supporting should be taken. 
The connection between bracket and wall, bracket and the air conditioner should be firm, 
stable and reliable.
Be sure there is no obstacle which block radiating air.

Strong 
wind

Strong 
wind

Barrier 

Incorrect

Correct

Seal

Drain joint

Base pan hole
of outdoor unit

(A)

(B)

              The drain joint is slightly different according to the 
different outdoor unit.
For the drain joint with the seal(Fig.A), first fit the seal onto 
the drain joint, then insert the drain joint into the base pan 

hole of outdoor unit, rotate  90

to securely assemble them. 

To install drain joint as shown in Fig.B, insert  the  drain 
 joint into the base pan hole of outdoor unit until it remains 
fixed with a clicking sound. Connecting the drain joint with 
an extension drain hose (Locally purchased), in case of the 
water draining off the outdoor unit during the heating mode.

2

DRAIN JOINT INSTALLATION

OUTDOOR INSALLATION PRECAUTION

3

Oblique

O

90

Roughness

Burr

REFRIGERANT PIPE CONNECTION

1. Cut a pipe with a pipe cutter.
2. Remove flare nuts attached to indoor and 
    outdoor unit, then put them on pipe/tube 
    having completed burr removal and flare 
    the pipe.
3. Firmly hold copper pipe in a die in the 
    dimension shown in the table below.

..

Align pipes to be connected.
Sufficiently tighten the flare nut with fingers,
and then tighten it with a spanner and torque 
wrench as shown.
Excessive torque can break nut depending 
on installation conditions.

Outer diam.

(mm)

A(mm)

Max.

Min.

6.35

1.3

0.7

9.52

1.6

1.0

12.7

1.8

1.0

12.7

16

1.8

2.2

1.0

2.0

Bar

Copper pipe

Clamp handle

Handle

Bar

"A"

Indoor unit tubing

Flare nut

Pipings

.

Outer

diam.

Tightening

torque(N.cm)

Additional tightening

torque(N.cm)

φ

6.35mm

φ

12.7mm

φ

16mm

φ

9.52mm

1500

(153kgf.cm)

1600

(163kgf.cm)

3500

(357kgf.cm)

4500

(459kgf.cm)

3600

(367kgf.cm)

4700

(479kgf.cm)

2500

(255kgf.cm)

2600

(265kgf.cm)

AIR PURGING AND TEST OPERATION

4

5

1. Remove the electrical control board cover from the outdoor unit by loosening the screw.
2. Connect the connective  cables to the terminals as identified with their respective matched numbers 
    on the terminal block of indoor and outdoor units.
3. Secure the cable onto the control board with the cord clamp.
4. To prevent the ingress of water, form a loop of the connective cable as illustrated in the installation 
    diagram of indoor and outdoor units.
5. Insulate unused cords (conductors) with PVC-tape. Process them so they do not touch any electrical 
    or  metal parts.

Cover

Screw

Liquid side:

φ

6.35mm

R22: (Pipe length-5)x30g/m

 R410A: (Pipe length-5)x20g/m        

Liquid side:

φ

9.52mm:

R22: (Pipe length-5)x60g/m

R410A: (Pipe length-5)x40g/m        

Connective pipe length

Less than 5m

More than 5m

Air purging method

Use vacuum pump

Additional amount of refrigerant to be charged

Open the valve stem until it hits against 
the stopper. Do not try to open it further.
Securely tighten the valve stem cap with 
a spanner or the like.
Valve stem cap tightening torque. See 
Tightening torque table.

.

.

.

.

Flare nut

Stopper

Cap

Valve body

Valve stem

Use vacuum pump

For the R407C refrigerant model, make sure the refrigerant added into air conditioner is liquid 
form in any cases.
When relocate the unit to another place, using vacuum pump to perform evacuation.

.

.

.

.

Air and moisture in the refrigerant system have undesirable effects. Therefore, the indoor unit 
and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove 
any noncondensables and moisture from the system.
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have 
 been properly connected and all wiring for the test run has been completed. 
Pipe length and refrigerant amount:

Outdoor
unit

Indoor
unit

Refrigerant 

Packed valve

Half union

Gas side
Liquid side

A

C

D

B

1. Completely tighten the flare nuts, A, B, C, D, connect 
    the manifold valve charge hose to a charge port of the 
    packed valve on the gas pipe side.
2. Connect the charge hose connection to the vacuum 
    pump.
3. Fully open the handle Lo of the manifold valve.
4. Operate the vacuum pump to evacuate. After starting 
    evacuation, slightly loose the flare nut of the packed 
    valve on the gas pipe side and check that the air is 
    entering. (Operation noise of  the vacuum pump changes 
    and a compound meter indicates 0 instead of minus)
5. After the evacuation is complete, fully close the handle 
    Lo of the manifold valve and stop the operation of the 
    vacuum pump.
    Make evacuation for 15 minutes and more and check 

5

    that the compound meter indicates  -76cmHg(-1.0x10 Pa).

O

6. Turn the stem of the packed valve B about 45  counter-
    clockwise for 6~7 seconds after the gas coming out, then 
    tighten the flare nut again. Make sure the pressure display 
    in the pressure indicator is a little higher than the atmosphere 
    pressure.
7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the packed valve stems B and A.
9. Securely tighten the cap of the packed valve.

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Packed valve

Perform  test operation after completing gas leak check at the flare nut connections and electrical 
safety check.
    Check that all tubing and wiring have been properly connected.
    Check that the gas and liquid side service valves are fully open.
1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.
2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions works 
     well. 

O

3.  When the ambient temperature is too low(lower than 17 C), the unit cannot be controlled by the 
     remote controller to run at cooling mode, manual operation can be taken. Manual operation is 
     used only when the remote controller is disable or maintenance necessary.
     Hold the panel sides and lift the panel up to an angle until it remains fixed with a clicking sound.
     Press the Manual control button to select the AUTO or COOL, the unit will operate under Forced 
     AUTO or COOL mode(see User Manual for details).
4.  The test operation should last about 30 minutes.

Connect the cable to the indoor unit

Flaring

Tightening connection

1. Air purging

2. When using the Vacuum Pump

4. Test running

3. Safety and leakage check

A: Lo packed valve  B: Hi packed valve 
C and D are ends of indoor unit connection.

CAUTION

1. Soap water method:
     Apply a soap water or a liquid neutral detergent on the indoor 
     unit connections and outdoor unit connections by a soft brush 
     to check for leakage of the connecting points of the piping. If 
     bubbles come out, it indicates that the pipes have leakage.
2.  Leak detector
     Use the leak detector to check for leakage.

O
U

T
D

O
O

U
N

I

CONNECT THE CABLE TO THE OUTDOOR UNIT

CAUTION

1

Indoor unit
check point

D

B

C

A

Outdoor unit
check point

Cover

NOTE:

                  Before performing any electrical work, turn off the main power to the system.
1. The inside and outside connecting cable can be connected without removing the front grille.
2. The indoor power cord type is H05VV-F or H05V2V2-F, the outdoor power cord and 
    interconnected cord type is H07RN-F.
3. Lift the indoor unit panel up, remove the electrical box cover by loosening the screw.
4. Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor s
    respectively.
5. Wrap those cables not connected with terminals with insulation tapes, so that they will not touch
    any electrical components. Secure the cable onto the control board with the cord clamp.

NOTE:

 For the standby control needs, the cross section area of cable connected to  L(1), 1,  2(N) 

must be sufficient for the maximum system current. The maximum system current is equal to the sum 
of indoor unit and outdoor unit rated current. 
    

NOTE:

NOTE: 

Panel

Electrical box
cover

Manual control 

button

AUTO/COOL

Electric safety regulations for the initial Installation
1. If there is serious safety problem about the power supply, the technicians should refuse to install 
    the air conditioner and explain to the client until the problem is solved. 
2. Power voltage should be in the range of 90%~110%of rated voltage.
3. The  surge protector and main power switch with a 1.5 times capacity of Max. Current of the 
    unit should be installed in power circuit.
4. Ensure the air conditioner is grounded well.
5. According to the attached Electrical Connection Diagram  located on the panel of the outdoor unit 
    to connect the wire.
6. All wiring must comply with local and national electrical codes and be installed by qualified and 
    skilled electricians. 
7. An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual 
    current device(RCD) with the rating of not exceeding 30mA shall be incorporated in the fixed wiring 
    according to the national rule. 
8. An individual branch circuit and single receptacle used only for this air conditioner must be 
   available. See the following table for suggested wire sizes and fuse specifications:

Electrical work

Terminal block of indoor unit

To outdoor unit

To outdoor unit

L(1)

2(N)

S

1

Terminal block of outdoor unit

To indoor unit

Power supply

1 2(N) S L

N

L(1)

L(1)

2(N)

S

1

or

Reviews: