background image

527 01 2701 00

Specifications subject to change without notice.

9

Fig. 4 —  Unit Leveling Tolerances

Step 5 — Field Fabricate Ductwork 

Cabinet  return-air  static  pressure  (a  negative  condition)

shall  not  exceed  0.35  in.  wg  (87  Pa)  with  economizer  or

0.45 in. wg (112 Pa) without economizer.

For vertical ducted applications, secure all ducts to roof curb

and building structure. 

Do not connect ductwork to unit.

Fabricate  supply  ductwork  so  that  the  cross  sectional  di

-

mensions are equal to or greater than the unit supply duct

opening  dimensions  for  the  first  18  in.  (458  mm)  of  duct

length from the unit basepan.

Insulate and weatherproof all external ductwork, joints, and

roof  openings  with  counter  flashing  and  mastic  in  accor

-

dance with applicable codes.

Ducts passing through unconditioned spaces must be insu

-

lated and covered with a vapor barrier.

If  a  plenum  return  is  used  on  a  vertical  unit,  the  return

should be ducted through the roof deck to comply with ap

-

plicable fire codes.

FOR UNITS WITH ACCESSORY ELECTRIC HEATERS 
All installations require a minimum clearance to combustible

surfaces of 1-in. (25 mm) from duct for first 12-in. (305 mm)

away from unit.

Outlet grilles must not lie directly below unit discharge.

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are re

-

quired.  Rollers  may  be  used  to  move  unit  across  a  roof.

Level by using unit frame as a reference. See Table 2 on

page 7 and Fig. 5 on page 10 for additional information.

Lifting holes are provided in base rails as shown in Fig. 5.

Refer to rigging instructions on unit. 

Rigging materials under unit (cardboard or wood to prevent

base pan damage) must be removed PRIOR to placing the

unit on the roof curb.

When using the standard side drain connection, ensure the

red plug in the alternate bottom connection is tight. Do this

before setting the unit in place. The red drain pan can be

tightened with a 

1

/

2

-in. square socket drive extension. For

further details see Step 10 — Install External Condensate

Trap and Line on page 12.

Before setting the unit onto the curb, recheck gasketing on

curb.

POSITIONING ON CURB
Position unit on roof curb so that the following clearances

are maintained: 

1

/

4

 in. (6.4 mm) clearance between the roof

curb  and  the  base  rail  inside  the  front  and  back,  0.0  in.

clearance between the roof curb and the base rail inside on

the duct end of the unit. This will result in the distance be

-

tween the roof curb and the base rail inside on the condens

-

er end of the unit being approximately

1

/

4

 in. (6.4 mm).

Although  unit  is  weatherproof,  guard  against  water  from

higher level runoff and overhangs.

After unit is in position, remove rigging skids and shipping

materials.

CAUTION

PROPERTY DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  damage  to

roofing materials.

Membrane roofs can be cut by sharp sheet metal edges.

Be careful when placing any sheet metal parts on such

roof.

MAXIMUM ALLOWABLE DIFFERENCE IN. (MM)

A-B

B-C

A-C

0.5 (13)

1.0 (25)

1.0 (25)

A

B

C

WARNING

PERSONAL INJURY HAZARD

Failure  to  follow  this  warning  could  cause

personal injury.

For vertical supply and return units, tools or parts could

drop  into  ductwork  and  cause  an  injury.  Install  a  90

degree turn in the return ductwork between the unit and

the conditioned space. If a 90 degree elbow cannot be

installed, then a grille of sufficient strength and density

should be installed to prevent objects from falling into the

conditioned  space.  Due  to  electric heater,  supply  duct

will require 90 degree elbow.

CAUTION

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment

damage.

All  panels  must  be  in  place  when  rigging.  Unit  is  not

designed  for  handling  by  fork  truck  when  packaging

is removed.

If  using  top  crate  as  spreader  bar,  once  unit  is  set,

carefully  lower  wooden  crate  off  building  roof  top  to

ground. Ensure that no people or obstructions are below

prior to lowering the crate.

Summary of Contents for RHW036-060

Page 1: ...ors 36 COMPLETING RETURN AIR SMOKE SENSOR INSTALLATION ADDITIONAL APPLICATION DATA Step 12 Adjust Factory Installed Options 37 SMOKE DETECTORS ECONOMI ER IV OCCUPANCY SWITCH Step 13 Install Accessorie...

Page 2: ...ON AND SAFETY HAZARD Failure to follow this warning could cause personal inju ry death and or equipment damage R 410A refrigerant systems operate at higher pressures than standard R 22 systems Do not...

Page 3: ...e K voltage code models the following are not available as factory installed options Coated or copper fin coils Economizers and 2 position damper Powered convenience outlet 1 See Specification Sheet f...

Page 4: ...4 Specifications subject to change without notice 527 01 2701 00 Fig 2 RHW036 060 Unit Dimensional Drawing...

Page 5: ...527 01 2701 00 Specifications subject to change without notice 5 Fig 2 RHW036 060 Unit Dimensional Drawing cont...

Page 6: ...6 Specifications subject to change without notice 527 01 2701 00 Fig 2 RHW036 060 Unit Dimensional Drawing cont...

Page 7: ...ed ductwork at unit duct openings 6 Install outdoor air hood 7 Install condensate line trap and piping 8 Make electrical connections 9 Install other accessories FRAME MOUNTED INSTALLATION Frame mounte...

Page 8: ...BER TITLE 1041738 CURB ASY ROOF ENGINEERING MANUFACTURING ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRAFTER CHECKER D 48TC400427 B WEIGHT MMC 06 17 11 SHEET 5 OF 5 SURFACE FINISH MF...

Page 9: ...n place The red drain pan can be tightened with a 1 2 in square socket drive extension For further details see Step 10 Install External Condensate Trap and Line on page 12 Before setting the unit onto...

Page 10: ...o the flanges Insulate and weatherproof all external ductwork joints and roof or building openings with counter flashing and mastic in accordance with applicable codes Do not cover or obscure visibili...

Page 11: ...installed on the unit the hood shipped with the unit will not be used and must be discarded Save the aluminum filter for use in the power exhaust hood assembly 1 The indoor coil access panel will be...

Page 12: ...he convenience outlet s transformer primary are not factory connected Installer must connect these leads according to required operation of the conve nience outlet If an always energized convenience o...

Page 13: ...the handle Fig 18 Power Wiring Connections Field Install the NFD Shaft and Handle 1 Remove the control box access panel The NFD enclosure is located below the control box see Fig 19 2 Remove 3 cap he...

Page 14: ...wiring connections Provide a ground fault and short circuit over current protec tion device fuse or breaker per NEC Article 440 or local codes Refer to unit informative data plate for MOCP Max imum O...

Page 15: ...t access is through the unit s control box access panel See Fig 21 The primary leads to the convenience outlet transformer are not factory connected Selection of primary power source is a customer opt...

Page 16: ...does not get into the building or conduit in the interim Check tightness of connector lock nuts before connecting electrical conduits Field supplied and field installed liquid tight conduit connector...

Page 17: ...nal features which might require addi tional conductors in the cable For wire runs up to 50 ft 15 m use no 18 AWG Ameri can Wire Gage insulated wire 35 C 95 F minimum For 50 to 75 ft 15 to 23 m use no...

Page 18: ...delay feature user selectable The DFB also provides an indoor fan off delay feature user selectable See Fig 29 for board arrangement The DFB is located in the main control box of the RHW unit see Fig...

Page 19: ...1 Heating cycle for an Emergency Heating sequence compressors are off and only the elec tric heaters are energized and also during the Defrost cycle to eliminate a cold blow condition in the space De...

Page 20: ...value exceeds 60 A unit mounted supplementary fuses are required for each heater circuit These fuses are included in accessory Single Point Boxes with power distribution and fuse blocks The single poi...

Page 21: ...e left of the Heater module Connect the VIO lead from Heater circuit 1 to terminal TB4 1 For 2 stage heating connect the VIO lead from Heater circuit 2 to terminal TB4 2 See Fig 36 Fig 36 Accessory El...

Page 22: ...22 Specifications subject to change without notice 527 01 2701 00 Fig 37 Typical Control Wiring Diagram Electro Mechanical with W7220 RHW036 060 208 230 3 60 Unit Shown...

Page 23: ...527 01 2701 00 Specifications subject to change without notice 23 Fig 38 Typical Control Wiring Diagram Electro Mechanical with W7220 RHW036 060 460 575 3 60 Unit Shown...

Page 24: ...24 Specifications subject to change without notice 24 Fig 39 Typical RHW036 060 Power Wiring Diagram 208 230 3 60 Unit Shown...

Page 25: ...527 01 2701 00 Specifications subject to change without notice 25 Fig 40 Typical RHW036 060 Power Wiring Diagram 460 575 3 60 Unit Shown...

Page 26: ...vailable with bus sensors User Interface Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display and four button keyp...

Page 27: ...ity Insensitive Connection Bottom Left Terminal Block IAQ 2 10 2 10 vdc Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source AC...

Page 28: ...Enter button to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus Fig 45 W7220 Controller Navigation Buttons To...

Page 29: ...d stage cooling ON 24 Vac on terminal Y2 I OFF 0 Vac on terminal Y2 I COOL Y2 OUT OFF ON OFF SECOND STAGE COOLING RELAY OUTPUT Cool Stage 2 Relay Output to mechanical cooling Y2 OUT terminal MA TEMP _...

Page 30: ...y sensor option Enthalpy boundary curves for economizing using single enthalpy DCV SET 1100ppm 500 to 2000 ppm increment by 100 DEMAND CONTROLLED VENTILATION SETPOINT Displays only if CO2 sensor is co...

Page 31: ...ivate power exhaust EXH2 H SET 75 0 to 100 EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3 speed with 1 heat and 2 cool Based on economizer OA damper position to activate power exhaust SYSTEM SET...

Page 32: ...perator to adjust for an out of calibration temperature sensor OA H CAL 0 RH 10 RH OUTSIDE AIR HUMIDITY CALIBRATION Allows for operator to adjust for an out of calibration humidity sensor RA T CAL 0 0...

Page 33: ...onnected check wiring then replace sensor if the alarm continues RA SYLK H ERR N A N A DA SYLK T ERR N A N A DISCHARGE AIR S BUS SENSOR ERROR Discharge air sensor has failed or become disconnected che...

Page 34: ...OA temperature and humidity input from the OA enthalpy sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary the economizer sets the economizing mode to YES e...

Page 35: ...YPE 2SPEED With stage 3 delay STG3 DLY in Advanced setup COOL Y2 OUT will be turned ON after the delay time specified N A Not applicable STATE FAN SPEED OCC Low Y1 Low Y2 High W High INPUTS OUTPUTS DE...

Page 36: ...has been no keypad activity for at least 5 minutes the Alarms menu dis plays and cycles through the active alarms You can also navigate to the Alarms menu at any time Clearing Alarms Once the alarm h...

Page 37: ...utdown terminals on the UCB and then attach the wiring harness from the smoke detector ECONOMI ER IV OCCUPANCY SWITCH See Fig 49 on page 38 for general EconoMi er IV wiring External occupancy control...

Page 38: ...a multimeter to the Vdc terminals on the UCB 4 Set the Range Switch to either A B or C per the Switch Range table 5 Using a straight blade screwdriver turn the Vdc con trol dial to fine tune the Vdc...

Page 39: ...5 2250 2375 2500 0 1 0 4 6 2 6 5 6 8 7 1 7 4 7 7 8 0 8 4 8 7 0 1 0 6 6 9 7 1 7 4 7 7 7 9 8 2 8 5 8 8 0 1 0 8 7 5 7 7 8 0 8 2 8 5 8 7 9 0 0 1 1 0 8 1 8 3 8 5 8 7 9 0 0 1 1 2 8 6 8 8 9 0 9 2 0 1 1 4 9 1...

Page 40: ...tion operation and converging coil circuits during the condenser function operation Fig 52 Typical Piping Schematic Table 14 Cooling Mode each circuit COMPONENT STATUS POSITION Reversing Valve Energiz...

Page 41: ......

Page 42: ...Specifications are subject to change without notice 527 01 2701 00 2020 Carrier Lewisburg TN 37091 USA Replaces New...

Page 43: ...e of obstructions and rotor spins freely Y N _____ Verify that scroll compressors are rotating in the correct direction Y N _____ Verify installation of thermostat Y N _____ III START UP ELECTRICAL Su...

Page 44: ...CUT ALONG D OTTED LINE CUT ALONG DOTTED LINE CL 2 Specifications are subject to change without notice 7 2020 527 01 2701 00 2020 Carrier Lewisburg TN 37091 USA Replaces New...

Reviews: